About this document

Symbols and document conventions

This document applies to the optics cover with the following part number:

2111696

A

B

References to the figures at the end of this document are indi‐
cated by a black background.

2

Safety information

WARNING

Incorrect reference value of optical properties
If optics cover calibration is not done correctly, persons and parts of the body to be pro‐
tected may not be detected.

b

Carry out an optics cover calibration with the Safety Designer every time the optics
cover is replaced.

b

Carry out the optics cover calibration at room temperature (10 °C to 30 °C).

b

Only carry out the optics cover calibration using a new optics cover.

b

Make sure that the entire system is clear of contamination when the adjustment is
carried out.

NOTICE

b

The optics cover of the safety laser scanner is an optical component. Make sure
that the optics cover does not become dirty or scratched during unpacking and
mounting. Prevent fingerprints on the optics cover. Wear the gloves supplied with
the new optics cover during replacement.

b

Replace the optics cover in a dry environment free of dust and dirt.

b

Never replace the optics cover during continuous operation, as dust particles
could penetrate into the safety laser scanner.

b

Avoid soiling the inside of the optics cover, e.g, by fingerprints.

b

Do not use any additional sealant, such as silicone, for sealing the optics cover.
Any vapors that are created may damage the optical components.

b

Mount the optics cover according to the following instructions to ensure IP65 leak
tightness of the housing.

b

Only use a new optics cover as a replacement.

b

Provide ESD protection when replacing the optics cover.

NOTICE

Enclosure rating IP65 only applies if the optics cover and the system plug are mounted
and the USB connection is closed with the protective cover.

3

Replacing the optics cover

Fixing screws for the optics cover: 

A

Prerequisites

Tool required:

TX10 Torx wrench

MOUNTING INSTRUCTIONS

8024614/2019-11-20 | SICK

M O U N T I N G   I N S T R U C T I O N S | nanoScan3 optics cover

7

Subject to change without notice

Содержание 2111696

Страница 1: ...M O U N T I N G I N S T R U C T I O N S nanoScan3 optics cover de en...

Страница 2: ...M O N T A G E A N L E I T U N G nanoScan3 Optikhaube de en...

Страница 3: ...kratzt wird Fingerabdr cke auf der Optikhaube vermeiden Beim Tausch die Handschuhe tragen die mit der neuen Optikhaube geliefert werden b Optikhaube in trockener staub und schmutzfreier Umgebung austa...

Страница 4: ...gel nicht ber hrt 9 Optikhaube auf den Sicherheits Laserscanner setzen Darauf achten dass die Optikhaube fl chig aufliegt 10 Optikhaube mit den neuen Befestigungsschrauben anschrauben Anzugsdrehmo men...

Страница 5: ...A 1 1 1 1 MONTAGEANLEITUNG 8024614 2019 11 20 SICK M O N T A G E A N L E I T U N G nanoScan3 Optikhaube 5 Irrt mer und nderungen vorbehalten...

Страница 6: ...M O U N T I N G I N S T R U C T I O N S nanoScan3 optics cover de en...

Страница 7: ...during unpacking and mounting Prevent fingerprints on the optics cover Wear the gloves supplied with the new optics cover during replacement b Replace the optics cover in a dry environment free of dus...

Страница 8: ...cover does not touch the mirror 9 Place the optics cover onto the safety laser scanner Make sure that the optics cover rests over the whole area 10 Screw on the optics cover with the new fixing screw...

Страница 9: ...MOUNTING INSTRUCTIONS 8024614 2019 11 20 SICK M O U N T I N G I N S T R U C T I O N S nanoScan3 optics cover 9 Subject to change without notice...

Страница 10: ...80 7425 E Mail enquiry my sick com Mexico Phone 52 472 748 9451 E Mail mexico sick com Netherlands Phone 31 0 30 229 25 44 E Mail info sick nl New Zealand Phone 64 9 415 0459 0800 222 278 tollfree E M...

Отзывы: