4
Grounding point 3
5
Insulated mounting
6
Grounding point 2
7
Ground potential difference
8
Grounding point 1
9
Metal housing
ß
Shielded electrical cable
Even in the event of large differences in the ground potential, ground loops are effec‐
tively prevented. As a result, equalizing currents can no longer flow via the cable shields
and metal housing.
NOTICE
The voltage supply for the device and the connected peripheral devices must also
guarantee the required level of insulation.
Under certain circumstances, a tangible potential can develop between the insulated
metal housings and the local ground potential.
6.3
Connection diagram
Power
I/O
Gig E
Encoder
On
State
Link/Data
Result
Laser
PC
24 V DC
Encoder
Photoelectric
switch
1
2
3
4
Figure 15: Connection diagram
1
Encoder
2
PC/Network
3
Photoelectric switch
4
24 V DC, voltage supply
6.4
Encoder
NOTICE
It is strongly recommended to use an encoder for measuring applications, such as
shape measuring and volume measuring. If no encoder is used, analysis results may be
inaccurate due to object traversing speed variations.
The encoder must fulfill the following requirements:
6
ELECTRICAL INSTALLATION
30
O P E R A T I N G I N S T R U C T I O N S | TriSpectorP1000
8022395/19OK/2020-12 | SICK
Subject to change without notice