Wiring the LCB Pump Controller

 

 
a. 

Float  switch  (remote)  ON/OFF  Circuit  is  used  to  turn  the 
pump on and off from a remote location, e.g. a float switch 
in  a  reservoir.  (Short  the  two  terminals  to  turn  the  pump 
off.) The resistant on the wire should not exceed 250 ohms.  

 
b. 

HIGH water level sensor turns the pump on. ( * Mount the 
brass  electrode  below  the  static  water  level  at  the  desired 
turn point.) 

 
c. 

LOW  water  level  sensor  turns  the  pump  off.  (Mount  the 
brass electrode 1 foot above the ground sensor. 

 
d. 

GROUND  or  common  water  level  sensor  must  be  under 
water all times. Mount the electrode 1 foot (30cm) above the 
pump. 

 

 * The distance between the HIGH  and GROUND sensor 

should not exceed 60cm 

 

 (2 feet).  It depends on the water conductivity   

 

If more distance is required a test will give best results 

  
 e. 

 PV- (IN) Negative wire from the PV array. 

 f. 

 PV+ (IN) Positive wire from the PV array. 

 g. 

 PUMP- (OUT) Negative wire from the pump (load). 

 h. 

 PUMP+ (OUT) Positive wire from the pump (load). 

 i. 

 ON/OFF Switch MANUAL SWITCH turns the pump on / 

off. 

k.

 

12V/24V Switch select system voltage.

  

 

( presentadjustment:25V ) 

   

 

 

 

Switch no. 

 

 

 

25 V  

solar direct 

two modules in 
series

 

"direct

ON 

 

OFF 

OFF 

OFF 

22 V  

battery based 

two batteries in 
series 

OFF 

ON 

OFF 

 

OFF 

12.5V 

solar direct 

one module 

"direct"  

 OFF 

OFF 

ON 

 

OFF 

11 V 

one battery 

OFF 

OFF 

 

OFF 

ON 

 
* Note:  

If the low water level circuit (HI/LOW/GRD) is not used, 
jumper wires must be connected all three terminals. 
Do not extend sensor wires more than 300 feet (100 m) total 
length 

 

IMPORTANT = Watch for the correct electric connection = 

IMPORTANT

 

("+" / "-" cable connection)

 

 

 DO NOT EXPOSE THE CONTROLLER INTO 

DIRECT SUNLIGHT 

 

 