SHIRE CONTROLS SDX-15 Скачать руководство пользователя страница 7

SECTION 8
FAULT FINDING

Properly installed, the SDX-15 alarm system will

give   many   years   of   trouble-free   service.   Experience
shows that the majority of problems are due to incorrect
connection   or   poor   workmanship   during   installation.
Problems   with   intermittent   faults   are   usually   due   to
screens not connected to earth, badly made connections
or water-

lled junction boxes. 

Most  problems   will  be  identi

ed  by  the  system

fault  indicator  below  the  system  fault  lamp,  which  will
illuminate when the test button is pressed. See appendix
B to decode these numbers.

If   no   lamps   show   when   the   test   button   is

pressed, check that the power supply is present at the
panel   and   that   the   battery   is   not   discharged.   (a
discharged   battery   will   take   about   72   hours   to   fully
recharge)
.

Flashing circuit has failed.

Fit   a   service  exchange   or   replacement   SDX-15

control PCB

Incoming Signal fault.

If   this   fault   is   present   on   all   panels   on   the

system,   using   an   analoge   voltmeter   on   a   10   volt   DC
range,  measure the  voltage across terminals  1  &  2  on
the central panel. If no voltage is present, disconnect the
signal   wiring   from   terminals   1&2  on   the   central   panel
and repeat  the test. If a voltage  of between  about  2-8
volts  is  now   present   then   a  short   circuit   exists   on   the
signal wiring or a repeater panel has been wired with the
signal  wires   reversed   (check   the  polarity  of  the  wiring
with the meter with the signal wires disconnected from
the repeater. Number 1 should be positive).

Reconnect the central panel and disconnect each

part  of the  signal  wiring until the  fault  clears. The last
part of the wiring to be disconnected has the fault on it. 

If   no  voltage  was   present   at   the  central  panel

after disconnecting the signal wires, 

rst ensure that the

panel is   set   to   be   a  central.   If   it   is   then  

t   a   service

exchange board (Remember. A board can be “borrowed”
from   another,   less   critical,   location   and   used   to   get   a
system running).

If the system fault only appears on one section of

the   system,   look   for   a   broken   wire   or   loose   terminal
between the section with the system fault and the rest of
the system.

Contact Line fault.

This   indicates   that   the   wiring   between   the

transmitter in the alarm panel showing the system fault,
and   the   termination   board   is   open   or   short   circuit.   A
service fault will be showing at the same time. This fault
(or faults) indicates which cable has the problem on it.
e.g. if a panel is showing a number 4 system fault and
say, pressure fault on nitrous oxide, the cable connected
to   condition   4   on   the   nitrous   oxide   service   on   the
transmitter   is   broken   or   shorted   to   common   or   earth.
Note   that   unused   inputs   to   transmitters   must   be
connected   to   common   with   a   resistor   to   prevent   a
system fault (see Transmitter section).

On   Remote   Transmitters   and   Plant   To   Alarm

Interfaces a 5mm round yellow LED provides warning for
a contact Line Fault when present at that transmitter.

Power Failure.

 

Check that the mains supply is sound. If sound,

check the fuses on the power supply board and replace
as necessary. If sound, 

t service exchange boards.

 

IMPORTANT   NOTE.   If   any   control   or
transmitter   boards   are   replaced,   ensure
that the replacement boards are set for the
correct  channels.  Carry  out   anti-confusion

tests when work is complete.

7

Appendix A - Cable types

Use only the following types of cable for wiring the alarm system:-
SWA
Overall screened cable
Single core cable in steel conduit. Must not contain any other cables.
A minimum cable size of 0.5 sq.mm is recommended. Solid cable such as telephone cable should NOT be used.

Continuity of screen, armouring or conduit must be maintained at all times. Particular 
attention should be given to plastic junction boxes. Multicore cables must not be shared with 
other systems.

Appendix B - System Faults

0. . . . . No fault
1. . . . . Incoming signal fault
2. . . . . Power failure
3. . . . . Incoming signal and power faults
4. . . . . Contact line fault
5. . . . . Contact line and incoming signal faults
6. . . . . Contact line and power faults
7. . . . . Contact line, power&incoming signal faults
8. . . . . Flashing circuit failed
9. . 

Flashing circuit&incoming signal faults

Содержание SDX-15

Страница 1: ...issue 11 02 06 2021 The SDX 15 Alarm System for Piped Medical Gases...

Страница 2: ...IN TELEPHONE 5 GAS CENTRAL LODGE ALARM IN PORTERS 5 GAS REPEATER COMPUTER INTERFACE SDXPIC 4 CORES 5 CORES 5 CORES 2 CORES 2 CORES 2 CORES 2 CORES 2 CORES 2 CORES 2 CORES TYPICAL PLANT ALARM SYSTEM TO...

Страница 3: ...on is to be in an alarm condition for a prolonged period e g for pipeline maintenance the re trigger can be prevented by silencing the audible with the Lockout button within the panel large at white p...

Страница 4: ...e condition to normal if the condition is not to be used or with a 1k8 resistor if the condition is to be transmitted from another transmitter The resistors are used to prevent a system fault due to s...

Страница 5: ...number location and size number of services to be displayed of alarm panel as required by C11 HTM02 01 Select the location and size of transmitters Use internal transmitters if an alarm panel is in th...

Страница 6: ...ice fault remains requiring re muting When a condition is to be at alarm condition for a long time the audible can be continuously muted as follows Open the panel and while the alarm condition is pres...

Страница 7: ...m fault only appears on one section of the system look for a broken wire or loose terminal between the section with the system fault and the rest of the system Contact Line fault This indicates that t...

Страница 8: ...MERGENCY PLANT PLANT FAULT FAULT PLANT PLANT VACUUM AIR MEDICAL CYLINDERS CYLINDERS CYLINDERS CYLINDERS FAULT PRESSURE NORMAL FAULT PRESSURE FAULT RESERVE NORMAL FAULT PRESSURE FAULT RESERVE IMMEDIATE...

Страница 9: ...IQUID IMMEDIATELY RESERVE FAULT PRESSURE FAULT NORMAL CHANGE CHANGE IMMEDIATELY RESERVE FAULT PRESSURE FAULT NORMAL CHANGE IMMEDIATELY RESERVE FAULT PRESSURE FAULT NORMAL RESERVE FAULT PRESSURE FAULT...

Страница 10: ...llowing standards EN60601 1 2 4th Edition 2015 Emissions Standard for Medical Equipment EN55011 Class A 2016 A1 2017 Emissions Standard for ISM Equipment EN60601 1 2 4th Edition 2015 Immunity Standard...

Отзывы: