background image

Connect the inter-panel signal wiring to terminals 1 & 2
on the power supply board, observing polarity. 

WARNING.   Ensure   that   cable   screen,
armouring or conduit is connected to earth
at   both   ends   of   each   run.   Termination
boards must be connected to cable screens

or   earth.   Failure   to   carry   out   these   instructions
WILL   result   in   intermittent   faults   invalidate   the
Declaration Of Conformity.

Two core cable as speci

ed in appendix A, must

be  run  between   all  alarm   panels,   remote  transmitters,
plant to alarm interfaces and computer interfaces.

WARNING.   A   minimum   of   20mm   clearance
must   be   maintained   between   the   alarm
system   cabling   and   any   other   cables
(including the mains supply to the alarms).

Cabling as speci

ed in appendix A must be run

between   alarm   condition   source   (plant,   manifold   etc.)
and   the   transmitter   from   which   the   service   is   to   be
transmitted. (One core per con common for each
service).

Connect   alarm   condition   cabling   between

transmitter   &   plant,   terminating   at   the   plant   with   a
termination board.

WARNING.   Where   over   5   Gases   are
displayed at the Central location (i.e. more
that   one   panel   is   present).   Connect   the
remote   'common',  'mute'  &  'test'  terminals

on   power   supply,   to   similar   terminals   in   the
adjacent  alarm(s).

Section 4
TRANSMITTERS

Transmitters   introduce   signals   from   plant   etc.

onto the multiplexed signal wiring. They also monitor the
wiring between the between the plant contacts and the
transmitter terminals via termination boards mounted in
or near the plant, checking for short or open circuits of
the cable. 

INTERNAL TRANSMITTERS (ITX)

Internal transmitters are available as 1, 2, 3

or  4  service  units  and are  mounted,   1  per   1-5  service
alarm, in the alarm panel enclosure. If a fault is detected
on  the contact  lines,  an   alarm condition  is transmitted

for the condition relating to the faulty line, and a system
fault visual and audible alarm will appear on this panel. 

Each   service   on   the   system   is   allocated   a

channel   when   the  system  is  initially  set   up,   this  being
entered   on   the   log   sheet.   The   alarm   contacts   on   the
plant   or   manifold   are   connected   via   the   termination
board to a service on the transmitter as follows:- 

C

Common

First condition

Second condition

Third condition

Pressure fault

and this service is then set to the channel for this service
with   the   rotary   switch.   For   example,   if   Oxygen   is
allocated   channel   1,   this   plant   could   be   connected   to
service A terminals on the transmitter, which would then
be set to channel 1.

Any condition not transmitted from this 

transmitter must be terminated with a 56k resistor to set
the condition to normal if the condition is not to be used,
or with a 1k8 resistor if the condition is to be transmitted
from another transmitter. The resistors are used to 
prevent a system fault due to short or open circuit. Note 
that if a resistor is 

tted, the condition must NOT be 

connected to the termination board.
Resistor codes:-

1k8 brown grey red silver, gold or red
56k green blue orange silver, gold or red

Important.   Ensure   that   each   condition   is
only transmitted from one location although
other   conditions   on   the   service   may   be

transmitted from other transmitters.

Any service can be displayed on any alarm panel

by   selecting   the   channel   on   which   the   service   is
transmitted (by reference to log sheet) using the rotary
switch for the appropriate column on the alarm.

Internal  transmitters  are  powered  by the  alarm

panel power supply or the reserve battery in the event of
a   power   failure.   Should   the  power   remain   o

  for   long

enough   to   discharge   the   battery,   all   conditions
transmitted   from   this   transmitter   will   show   on   other
alarm   panels   as   gas   fault   conditions   (i.e.   not   system
fault).

REMOTE TRANSMITTERS (RTX).

The Remote transmitter is a self contained unit,

used   where   indication   of   the   alarm   condition   is   not
required  locally,   e.g.   when   a  manifold  or  plant  has   an
integral plant to alarm interface, and are available as 1,
2, 3 or 4 service units. The services are selected, as in
the   alarm   panel,   with   a   rotary   switch.   However,   the
remote   transmitter   has   only   one   switch   for   up   to   4
services.  This  switch  is set  to  the 

rst service  required

and the other services will follow in sequence. e.g. if the
switch on a 3 service transmitter is set to channel 2 then
the services transmitted will be channels 2, 3 & 4.

Connection to the plant (or manifold) is identical

to the internal transmitter above.

A 230Vac, 50/60 Hertz supply is required, which

is connected under the mains terminal cover.

The   2   core   inter-panel   wiring   is   connected   to

signal   terminals  1   &   2.   The   cable   screen   must   be
connected to the ``S'' terminal. Refer to the instruction
sheet supplied with the transmitter.

RTX1 TRANSMITTER

Again, the RTX1  is  a self contained transmitter,

used   where   indication   of   the   alarm   condition   is   not
required   locally   and   is   available   as   a   single   channel
variation only.

These   transmitters   are   often   factory  

tted   by

Plant   or   Manifold   Controller   manufacturers   within   the
same housing as the contact sources, hence the board

C

1

2

3

4

SERVICE A

C

1

SER

C

C

1

1

2

2

3

3

4

4

TO ALARM

TO PLANT

 CABLING BETWEEN

 TRANSMITTER AND

TERMINATION BOARD

TERMINATION BOARD.

TO BE MOUNTED IN

CONTROL PANEL ON

PLANT OR MANIFOLD.

WIRING TO PLANT

ALARM CONTACTS

SDXPIC3

TRANSMITTER

 TYPICAL TRANSMITTER

CONNECTIONS SHOWING

  ONE UN-USED ALARM

CONDITION LINKED OUT

    WITH A RESISTOR

TERMINALS

4

Содержание SDX-15

Страница 1: ...issue 11 02 06 2021 The SDX 15 Alarm System for Piped Medical Gases...

Страница 2: ...IN TELEPHONE 5 GAS CENTRAL LODGE ALARM IN PORTERS 5 GAS REPEATER COMPUTER INTERFACE SDXPIC 4 CORES 5 CORES 5 CORES 2 CORES 2 CORES 2 CORES 2 CORES 2 CORES 2 CORES 2 CORES TYPICAL PLANT ALARM SYSTEM TO...

Страница 3: ...on is to be in an alarm condition for a prolonged period e g for pipeline maintenance the re trigger can be prevented by silencing the audible with the Lockout button within the panel large at white p...

Страница 4: ...e condition to normal if the condition is not to be used or with a 1k8 resistor if the condition is to be transmitted from another transmitter The resistors are used to prevent a system fault due to s...

Страница 5: ...number location and size number of services to be displayed of alarm panel as required by C11 HTM02 01 Select the location and size of transmitters Use internal transmitters if an alarm panel is in th...

Страница 6: ...ice fault remains requiring re muting When a condition is to be at alarm condition for a long time the audible can be continuously muted as follows Open the panel and while the alarm condition is pres...

Страница 7: ...m fault only appears on one section of the system look for a broken wire or loose terminal between the section with the system fault and the rest of the system Contact Line fault This indicates that t...

Страница 8: ...MERGENCY PLANT PLANT FAULT FAULT PLANT PLANT VACUUM AIR MEDICAL CYLINDERS CYLINDERS CYLINDERS CYLINDERS FAULT PRESSURE NORMAL FAULT PRESSURE FAULT RESERVE NORMAL FAULT PRESSURE FAULT RESERVE IMMEDIATE...

Страница 9: ...IQUID IMMEDIATELY RESERVE FAULT PRESSURE FAULT NORMAL CHANGE CHANGE IMMEDIATELY RESERVE FAULT PRESSURE FAULT NORMAL CHANGE IMMEDIATELY RESERVE FAULT PRESSURE FAULT NORMAL RESERVE FAULT PRESSURE FAULT...

Страница 10: ...llowing standards EN60601 1 2 4th Edition 2015 Emissions Standard for Medical Equipment EN55011 Class A 2016 A1 2017 Emissions Standard for ISM Equipment EN60601 1 2 4th Edition 2015 Immunity Standard...

Отзывы: