33
Input Range
Input Status
2 to 10 mA
Equals 0 mA input.
0 to 10 mA
Equals 0 mA input.
1 to 5 mA
Equals 0 mA input.
0 to 1 mA
Equals 0 mA input.
10 to 50 mA
Equals 0 mA input.
0 to 10 mV
Overscale *
0 to 50 mV
Overscale *
0 to 60 mV
Overscale *
0 to 100 mV
Overscale *
0 to 1 V
Overscale *
0 to 5 V
Equals 0 V input.
1 to 5 V
Equals 0 V input.
-5 to 5 V
Equals 0 V input.
0 to 10 V
Equals 0 V input.
-10 to 10 V
Equals 0 V input.
* For the overscale status, the Alarm indicator lights up, and
flashes
as an input value.
8.2.4
Indication Time Setting
After preset indication time has elapsed, Multi-Display A, Multi-Display B and each
action indicator are turned OFF. They will light up again if any key is pressed.
They remain lit during setting mode, or in the event of an input error or input
disconnection.
If the indication time is set to 00:00, they will remain lit.
8.2.5
Ratio and Bias Settings
●
Ratio setting
If ‘Ratio setting’ is selected in [Ratio setting method], ratio and bias value for the
output corresponding to the input value can be set.
Output 1 ratio setting
Sets the ratio for Output 1 output value.
The output will be produced by [(Input x Ratio) + Bias value] (for normal output)
based on the slope set in [Output 0% value] and [Output 100% value].
Output 2 ratio setting
Sets the ratio for Output 2 output value.
The output will be produced by [(Input x Ratio) + Bias value] (for normal output)
based on the slope set in [Output 0% value] and [Output 100% value].
Output 1 bias setting
Sets the bias value for Output 1 output value
The bias value is added to [Input x Ratio] to produce the output based on the
slope set in [Output 0% value] and [Output 100% value].
Output 2 bias setting
Sets the bias value for Output 2 output value.
The bias value is added to [Input x Ratio] to produce the output based on the
slope set in [Output 0% value] and [Output 100% value].