- 24 -
6. Setup
Setup should occur before using this unit, to set (or select) an Input range, Scaling low limit
value, Scaling high limit value, Alarm type, etc. according to the users’ conditions.
Setup is conducted in the CH1 function group, CH2 function group (SE2 A) and Special
function group.
Refer to the default values in (Table 6-1) to (Table 6-3).
If the users’ specifications are the same as the default value of the instrument, or if setup
has already been completed, it is not necessary to set up the instrument. Proceed to
Section “7. Alarm settings”.
Function Group
(Table 6-1) SE2 A
(CH1 and CH2 have respective setting items.)
Setting Item
Factory Default Value
K -200 to 1370
(SE2EA)
Pt100 -200 to 850
(SE2RA)
4 to 20 mA DC -1999 to 9999 (SE2AA)
Input range
1 to 5 V DC -1999 to 9999
(SE2VA)
Decimal point place
No decimal point
-200
(SE2EA, SE2RA)
Scaling low limit
-1999 (SE2AA, SE2VA)
1370
(SE2EA)
850
(SE2RA)
Scaling high limit
9999
(SE2AA, SE2VA)
Filter time constant
0.0 sec
0.0
(SE2EA, SE2RA)
Sensor correction
0
(SE2AA, SE2VA)
A1 type
A2 type
A3 type
No alarm action
A1 Energized/De-energized
A2 Energized/De-energized
A3 Energized/De-energized
Energized
A1 HOLD function
A2 HOLD function
A3 HOLD function
OFF
A1 hysteresis
A2 hysteresis
A3 hysteresis
1.0
(SE2EA, SE2RA)
1.0% (SE2AA, SE2VA)
A1 delay time
A2 delay time
A3 delay time
0 sec