36
20H 03H
00A1H: Instrument information
reading
2
0
digit: Alarm 1
0: Not applied 1: Applied
2
1
digit: Alarm 2
0: Not applied 1: Applied
2
2
digit: Alarm 3
0: Not applied 1: Applied
2
3
digit: Alarm 4
0: Not applied 1: Applied
2
4
digit: Loop break alarm
0: Not applied 1: Applied
2
5
digit: Heater burnout alarm 1
0: Not applied 1: Applied
2
6
digit: Heater burnout alarm 2
0: Not applied 1: Applied
2
7
digit: Heater burnout alarm
rating
0: 100A 1: 20A
2
8
digit:
Heating/Cooling function
0: Not applied 1: Applied
2
9
to 2
15
digit: Not used
(Always 0)
Setting data
•
When the data (setting value) has a decimal point, the decimal point is removed.
The data is represented as a whole number, and expressed in hexadecimal figures.
Data item
(*1) When the alarm action type is changed during Alarm 1, 2, 3, 4 action selection, the
alarm setting value returns to the default value.
The alarm output (A1) and status flag (A1, A2, A3, A4) are also initialized.
(*2) Selects whether to turn the control output (OUT1) and cooling output (OUT2) ON or
OFF when the PV goes outside the control range.
(*3) In the case High limit alarm with standby, Low limit alarm with standby or High/Low
limit alarm with standby is selected during Alarm action selection, and when alarm
output is on, the alarm status returns to the standby again by selecting (0001H:
Alarm status flag and standby reset), and the alarm status flag is also initialized.
Note
Setting of OUT1 (OUT2) high limit or low limit value during standby or warm-up status
is not effective.