32
9. Communication command table
Setting/Reading command
Shinko
command
type
Modbus
function
code
Data item
Data
20H/50H 03H/06H
0001H:
SV
Set value, Decimal point ignored
0002H: Not used
20H/50H 03H/06H
0003H: AT setting
0000H: Cancel
0001H: Perform
20H/50H 03H/06H
0004H: OUT1 proportional band
Set value, Decimal point ignored
20H/50H 03H/06H
0005H: OUT2 proportional band
Set value, Decimal point ignored
20H/50H 03H/06H
0006H: Integral time setting
Set value
20H/50H 03H/06H
0007H: Derivative time setting
Set value
20H/50H 03H/06H
0008H: OUT1 proportional cycle
Set value
20H/50H 03H/06H
0009H: OUT2 proportional cycle
Set value
20H/50H 03H/06H
000AH: Manual reset setting
Set value, Decimal point ignored
20H/50H 03H/06H
000BH: A1 (Alarm 1) setting
Set value, Decimal point ignored
20H/50H 03H/06H
000CH: A2 (Alarm 2) setting
Set value, Decimal point ignored
20H/50H 03H/06H
000DH: A3 (Alarm 3) setting
Set value, Decimal point ignored
20H/50H 03H/06H
000EH: A4 (Alarm 4) setting
Set value, Decimal point ignored
20H/50H 03H/06H
000FH: Heater burnout alarm 1
setting
Set value
20H/50H 03H/06H
0010H: Loop break alarm time
setting
Set value, Decimal point ignored
20H/50H 03H/06H
0011H: Loop break alarm span
setting
Set value, Decimal point ignored
20H/50H 03H/06H
0012H: Non-volatile memory
data saving selection
0000H: Save 0001H: Save
0002H: Save
0003H: Unable to save
0013H:
Not
used
0014H:
Not
used
20H/50H 03H/06H
0015H: Sensor correction value
setting
Set value, Decimal point ignored
20H/50H 03H/06H
0016H:
Overlap/Dead
band
Set value, Decimal point ignored
0017H:
Not
used
20H/50H 03H/06H
0018H: Scaling high limit setting
Set value, Decimal point ignored
20H/50H 03H/06H
0019H: Scaling low limit setting
Set value, Decimal point ignored
001AH:
Not
used
20H/50H 03H/06H
001BH: PV filter time constant
setting
Set value,
Decimal point
ignored
20H/50H 03H/06H
001CH: OUT1 high limit setting
Set value
20H/50H 03H/06H
001DH: OUT1 low limit setting
Set value
20H/50H 03H/06H
001EH: OUT1 ON/OFF action
hysteresis setting
Set value, Decimal point ignored
20H/50H 03H/06H
001FH: OUT2 action mode
selection
0000H: Air cooling
0001H: Oil cooling
0002H: Water cooling
20H/50H 03H/06H
0020H: OUT2 high limit setting
Set value
20H/50H 03H/06H
0021H: OUT2 low limit setting
Set value
20H/50H 03H/06H
0022H: OUT2 ON/OFF action
hysteresis setting
Set value, Decimal point ignored