8. Specifications
8.1 Standard specifications
Mounting
:
Flush
Setting
: Input system using membrane sheet key
Display
PV display : Red LED 4 digits, character size 10.2 x 4.9 mm (H x W)
SV display
: Green LED 4 digits, character size 8.8 x 4.9 mm (H x W)
Accuracy (Setting and Indication)
:
Thermocouple
:
Within
0.2% of each input span
1digit, or within
2 (4 ),
whichever
is
greater
However R, S inputs, 0 to 200 (400 ): Within
6 (12 )
B input, 0 to 300 (600 ): Accuracy is not guaranteed.
K, J, E, T, N inputs, less than 0 (32 ): Within
0.4% of input span 1digit
RTD
:
Within
0.1% of each input span
1digit, or
within
1 (2 ), whichever is greater
DC current
: Within
0.2% of each input span
1digit
DC voltage
: Within
0.2% of each input span
1digit
Input sampling period
: 0.25 seconds
Input
Thermocouple : K, J, R, S, B, E, T, N, PL- , C(W/Re5-26) External resistance, 100 or less
(However, B input: External resistance, 40 or less)
RTD
: Pt100, JPt100, 3-wire system
Allowable input lead wire resistance (10 or less per wire)
DC current
: 0 to 20mA DC, 4 to 20mA DC
Allowable input current, 50mA or less
DC voltage
: 0 to 1V DC
Input impedance (1M or more)
Allowable input voltage (5V or less)
Allowable signal source resistance (2k or less)
: 0 to 5V DC, 1 to 5V DC, 0 to 10V DC
Input impedance (100k or more)
Allowable input voltage (15V or less)
Allowable signal source resistance (100 or less)
OUT (Limit control output)
Relay contact : 1a, Control capacity 3A 250V AC (resistive load)
1A 250V AC (inductive load cosø=0.4)
Electrical life, 100,000 times
A1 output
Action : ON/OFF action
Hysteresis
: 0.1 to 100.0 ( ), or 1 to 1000
Output : Relay contact 1a
Control capacity, 3A 250V AC (resistive load)
Electrical life, 100,000 times
Control action
High limit control action, Low limit control action
OUT
(
Limit control output) hysteresis: 0.1 to 100.0 ( ), or 1 to 1000
Circuit insulation configuration
Insulation resistance
: 10M or more, at 500V DC
Dielectric strength
: 1.5kV AC for 1 minute between input terminal and power terminal