5.5 Setup mode
Sets input type, A1, A2 type, High/Low limit control action, etc.
In the PV/SV display mode, press the
key for approx. 3 seconds while holding down the
and
keys to proceed to the Setup mode.
To set values, use the
or
key.
To register the value, use the
key.
Character
Name, Function, Setting range
Default value
Input type selection
K (–200 to 1370 )
• The input type can be selected from thermocouple (10 types), RTD (2 types), DC
current (2 types) and DC voltage (4 types), and the unit
/ can be selected as well.
• When changing the input from DC voltage to other inputs, remove the sensor
connected to this controller first, then change for the input. If the input is changed
with the sensor connected, the input circuit may break.
• Selection range:
: K
-200 to 1370
: K
-199.9 to 400.0
: J
-200 to 1000
: R
0 to 1760
: S
0 to 1760
: B
0 to 1820
: E
-200 to 800
: T
-199.9 to 400.0
: N
-200 to 1300
: PL-
0 to 1390
: C(W/Re5-26)
0 to 2315
: Pt100
-199.9 to 850.0
: JPt100
-199.9 to 500.0
: Pt100
-200 to 850
: JPt100
-200 to 500
: K
-320 to 2500
: K
-199.9 to 750.0
: J
-320 to 1800
: R
0 to 3200
: S
0 to 3200
: B
0 to 3300
: E
-320 to 1500
: T
-199.9 to 750.0
: N
-320 to 2300
: PL-
0 to 2500
: C(W/Re5-26) 0 to 4200
: Pt100 -199.9 to 999.9
: JPt100 -199.9 to 900.0
: Pt100
-300 to 1500
: JPt100
-300 to 900
: 4 to 20mA DC -1999 to 9999
: 0 to 20mA DC -1999 to 9999
: 0 to 1V DC
-1999 to 9999
: 0 to 5V DC
-1999 to 9999
: 1 to 5V DC
-1999 to 9999
: 0 to 10V DC -1999 to 9999
Scaling high limit setting
1370
• Sets scaling high limit value.
• Setting range: Scaling low limit value to input range high limit value
Scaling low limit setting
–200
• Sets scaling low limit value.
• Setting range: Input range low limit value to scaling high limit value
Decimal point place selection
No decimal point
• Selects decimal point place.
• Available only for DC input
• Selection range:
: No decimal point
: 1 digit after decimal point
: 2 digits after decimal point
: 3 digits after decimal point
PV filter time constant setting
0.0 seconds
• Sets PV filter time constant.
(If the value is set too large, it affects control result due to the delay of response)
• Setting range: 0.0 to 10.0 seconds