5.5 Setup mode 

Sets input type, A1, A2 type, High/Low limit control action, etc. 
In the PV/SV display mode, press the 

  key for approx. 3 seconds while holding down the 

 and 

  keys to proceed to the Setup mode. 

To set values, use the 

 or 

 key. 

To register the value, use the 

 key. 

Character 

Name, Function, Setting range 

Default value 

Input type selection 

K (–200 to 1370 ) 

• The input type can be selected from thermocouple (10 types), RTD (2 types), DC 

current (2 types) and DC voltage (4 types), and the unit 

/   can be selected as well. 

• When changing the input from DC voltage to other inputs, remove the sensor 

connected to this controller first, then change for the input. If the input is changed 
with the sensor connected, the input circuit may break. 

• Selection range: 

 

: K     

-200 to 1370  

: K     

-199.9 to 400.0  

: J     

-200 to 1000  

: R     

0 to 1760  

: S     

0 to 1760  

: B     

0 to 1820  

: E     

-200 to 800  

: T     

-199.9 to 400.0  

: N     

-200 to 1300  

: PL-      

0 to 1390  

: C(W/Re5-26) 

0 to 2315  

: Pt100       

-199.9 to 850.0  

: JPt100     

-199.9 to 500.0  

: Pt100   

 

-200 to 850  

: JPt100     

-200 to 500  

: K     

-320 to 2500  

: K     

-199.9 to 750.0  

: J     

-320 to 1800  

: R     

0 to 3200  

: S     

0 to 3200  

: B     

0 to 3300  

: E     

-320 to 1500  

: T     

-199.9 to 750.0  

: N     

-320 to 2300  

: PL-      

0 to 2500  

: C(W/Re5-26)     0 to 4200  
: Pt100      -199.9 to 999.9  
: JPt100      -199.9 to 900.0  
: Pt100     

-300 to 1500  

: JPt100     

-300 to 900  

 

: 4 to 20mA DC  -1999 to 9999 
: 0 to 20mA DC  -1999 to 9999 
: 0 to 1V DC   

-1999 to 9999 

: 0 to 5V DC   

-1999 to 9999 

: 1 to 5V DC   

-1999 to 9999 

: 0 to 10V DC    -1999 to 9999 

 
 
 
 
 
 

Scaling high limit setting 

1370  

 

• Sets scaling high limit value. 
• Setting range: Scaling low limit value to input range high limit value 

Scaling low limit setting 

–200  

 

• Sets scaling low limit value. 
• Setting range: Input range low limit value to scaling high limit value 

Decimal point place selection 

No decimal point 

 

• Selects decimal point place. 
• Available only for DC input 
• Selection range: 

: No decimal point 
: 1 digit after decimal point 
: 2 digits after decimal point 
: 3 digits after decimal point 

PV filter time constant setting 

0.0 seconds 

 

• Sets PV filter time constant. 

(If the value is set too large, it affects control result due to the delay of response) 

• Setting range: 0.0 to 10.0 seconds 

 
 
 
 
 
 

Содержание JCS-33A-R/M T6080

Страница 1: ...t being used under conditions not otherwise stated in this manual Caution with respect to Export Trade Control Ordinance To avoid this instrument from being used as a component in or as being utilized in the manufacture of weapons of mass destruction i e military applications military equipment etc please investigate the end users and the final use of this instrument In the case of resale ensure t...

Страница 2: ...tes set or selected value during the setting mode 3 RST RESET indicator Lights when OUT Limit control output terminals between 6 and 7 is OFF with a green LED 4 EXCD EXCEEDED indicator High limit action The yellow LED lights when PV SV Low limit action The yellow LED lights when PV SV 5 A1 indicator When A1 output is ON the red LED lights 6 EVT indicator When A2 output A2 option is ON a red LED li...

Страница 3: ...sence of corrosive gases No flammable explosive gases Few mechanical vibrations or shocks No exposure to direct sunlight an ambient temperature of 0 to 50 32 to 122 that does not change rapidly An ambient non condensing humidity of 35 to 85 RH No large capacity electromagnetic switches or cables through which large current flows No water oil or chemicals or where the vapors of these substances can...

Страница 4: ...ont side of the panel Fig 3 4 1 2 Attach the mounting brackets by the holes at the top and bottom of the case and secure the controller in place with the screws Fig 3 4 2 Fig 3 4 1 Fig 3 4 2 Caution As the case is made of resin do not use excessive force while screwing in the mounting bracket or the case or screw type mounting bracket could be damaged The torque is approximately 0 12N m ...

Страница 5: ...uit near the external controller Recommended fuse Time lag fuse rated voltage 250V AC rated current 2A For a 24V AC DC power source do not confuse polarity when using direct current DC For the OUT Limit control output terminals 6 7 externally use a relay according to the capacity of the load to protect the built in relay contact When wiring keep input wires thermocouple RTD etc away from AC source...

Страница 6: ...he next setting item Setting items with dotted lines are optional and they appear only when the options are added If the key is pressed for approx 3sec the controller reverts to the PV SV display mode from any mode Outline of operation procedure Set Input type Alarm type value etc and SV desired value following the procedures below Setting item numbers 1 to 7 are indicated on the flowchart Step 1 ...

Страница 7: ...9 to 750 0 J 320 to 1800 R 0 to 3200 S 0 to 3200 B 0 to 3300 E 320 to 1500 T 199 9 to 750 0 N 320 to 2300 PL 0 to 2500 C W Re5 26 0 to 4200 Pt100 199 9 to 850 0 JPt100 199 9 to 500 0 Pt100 200 to 850 JPt100 200 to 500 Pt100 199 9 to 999 9 JPt100 199 9 to 900 0 Pt100 300 to 1500 JPt100 300 to 900 4 to 20mA DC 1999 to 9999 0 to 20mA DC 1999 to 9999 0 to 1V DC 1999 to 9999 0 to 5V DC 1999 to 9999 1 t...

Страница 8: ...caling high limit setting the set value is indicated on the SV display During this time all outputs and the LED indicators are in OFF status Control will then start indicating the PV process variable on the PV display and SV desired value on the SV display Table 5 1 Sensor input PV display SV display PV display SV display K J R S B E T N PL C W Re5 26 Pt100 JPt100 4 to 20mA DC 0 to 20mA DC 0 to 1V...

Страница 9: ...V display mode press the key while holding down the key to proceed to the Main setting mode To set values use the or key To register the value use the key Character Name Function Setting range Default value SV setting 0 Sets SV desired value Setting range Scaling low limit to Scaling high limit A1 value setting 0 Sets the action point of A1 output Not available if No alarm is selected during A1 ty...

Страница 10: ...r PV Current actual temperature Sensor correction value Setting range 100 0 to 100 0 or 1000 to 1000 Communication protocol selection Shinko protocol Selects the communication protocol Available only when the C5 option is applied Selection range Shinko protocol Modbus ASCII mode Modbus RTU mode Instrument number setting 0 Sets the instrument number individually to each instrument when communicatin...

Страница 11: ...00 199 9 to 500 0 Pt100 200 to 850 JPt100 200 to 500 K 320 to 2500 K 199 9 to 750 0 J 320 to 1800 R 0 to 3200 S 0 to 3200 B 0 to 3300 E 320 to 1500 T 199 9 to 750 0 N 320 to 2300 PL 0 to 2500 C W Re5 26 0 to 4200 Pt100 199 9 to 999 9 JPt100 199 9 to 900 0 Pt100 300 to 1500 JPt100 300 to 900 4 to 20mA DC 1999 to 9999 0 to 20mA DC 1999 to 9999 0 to 1V DC 1999 to 9999 0 to 5V DC 1999 to 9999 1 to 5V ...

Страница 12: ...hysteresis for A1 Not available if No alarm action is selected during A1 type selection Setting range 0 1 to 100 0 or 1 to 1000 A2 hysteresis setting 1 0 Sets hysteresis for A2 Not available if A2 option is not added or if No alarm action is selected during A2 type selection Setting range 0 1 to 100 0 or 1 to 1000 A1 action delayed timer setting 0 seconds Sets action delayed timer for A1 When sett...

Страница 13: ...cator is not lit When A1 A2 Deenergized is selected the A1 EVT A2 output between terminals 3 4 or 3 5 is not conducted OFF while the A1 EVT A2 output indicator is lit The A1 EVT A2 output is conducted ON while the A1 EVT A2 output indicator is not lit High limit alarm when Energized is set High limit alarm when Deenergized is set Fig 5 5 1 Fig 5 5 2 6 Running After the unit is mounted to the contr...

Страница 14: ...als between 6 7 is turned OFF 3 If PV drops below SV OUT hysteresis the EXCEEDED indicator goes off At this time the RESET indicator is lit and OUT Limit control output terminals between 6 7 is in OFF status 4 If the key is pressed or if External reset input terminals between 13 14 are shorted the RESET indicator goes off OUT Limit control output terminals between 6 7 is turned ON and limit contro...

Страница 15: ...and OUT Limit control output terminals between 6 7 is turned OFF Press the key or connect the External reset input terminals13 14 Limit control action will initiate However while the EXCEEDED indicator is lit limit control action does not initiate 7 4 A1 A2 action A1 action A1 output side OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON High Low limits alarm High Low limit range alar...

Страница 16: ...ut External resistance 40 or less RTD Pt100 JPt100 3 wire system Allowable input lead wire resistance 10 or less per wire DC current 0 to 20mA DC 4 to 20mA DC Allowable input current 50mA or less DC voltage 0 to 1V DC Input impedance 1M or more Allowable input voltage 5V or less Allowable signal source resistance 2k or less 0 to 5V DC 1 to 5V DC 0 to 10V DC Input impedance 100k or more Allowable i...

Страница 17: ...high limit value 50 100 DC input Indication range Scaling low limit value Scaling span x 1 to Scaling high limit value Scaling span x 10 However or flashes when a range of 1999 to 9999 is exceeded Control range Scaling low limit value Scaling span x 1 to Scaling high limit value Scaling span x 10 DC input disconnection When DC input is disconnected the PV display flashes for 4 to 20mA DC and 1 to ...

Страница 18: ...electable by keypad Parity Even Odd and No parity Selectable by keypad Stop bit 1 and 2 Selectable by keypad Communication protocol Shinko protocol Modbus ASCII Modbus RTU Selectable by keypad Number of units connectable Maximum 31 units to 1 host computer Communication error detection Double detection by parity and checksum External reset input Option code SM If this option is added the C5 option...

Страница 19: ...are securely mounted to the instrument input terminal Connect the sensor terminals to the instrument input terminals securely is flashing on the PV display Check whether input signal source for DC voltage 1 to 5V DC or DC current 4 to 20mA DC is disconnected How to check whether the input signal wire is disconnected DC voltage 1 to 5V DC If the input to the input terminals of the instrument is 1V ...

Страница 20: ...dicating Internal memory is defective Contact our agency or us 9 2 Key operation Problem Presumed cause and solution Unable to set the SV A1 value etc The values do not change by keys Set value lock Lock 1 or Lock 2 is selected Release the lock The setting indication does not change within the input range even if the keys are pressed and new values are unable to be set value Scaling high or low li...

Отзывы: