(2) Wiring 

Connect the main unit lead wire to 

the wire from the wall side.

 

(A) 

(A) 

(B) 

(B) 

(C) 

(C) 

(C) 

Mounting Plate 

Main Unit 

Main Unit Cover 

(C) 

  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

3. Wiring 

DSW-100-H   

DSW-100-H W4, DSW-100-HV W4 

 

 

 

 

 

(Fig. 3-1)   

(Fig. 3-2) 

 

Lead Wire Color 

Lead Wire Type 

ORG: Orange 

4 to 20 mA DC or 

0 to 1 V DC 

YLW: Yellow 

BRW: Brown 

Power supply   

BLK: Black 

 

4. Replacing Humidity Sensor (HD-S2) 

 

Follow the procedure below to replace the humidity sensor (HD-S2). 

(1)  Turn the power to the unit OFF, then remove the cover of the main unit. 

(2)  Pull the humidity sensor (HD-S2) out from the socket. 

(3)  Insert the new humidity sensor (HD-S2), with the model label facing 

   downward. 

[NOTE] 

As the humidity sensor (HD-S2) is polarity sensitive, so be sure to 

insert the sensor correctly, otherwise the sensor will be broken, 

and measurement will be impossible.

 

Never disassemble the humidity sensor as it may lead to   

malfunction. 

(4) Mount the main unit cover, then turn the power to the unit ON. 

Socket 

Humidity sensor (HD-S2) 

(3) Mounting Main Unit 

Screw 4 places (C) as indicated by the dotted lines, 

and fix the sensor main unit to the Mounting Plate. 

For screws, use M3 screw (4 pieces) provided.

 

(4) Fitting Main Unit Cover 

Insert the main unit cover protrusion (2 places) into 

the cover mounting holes (2 places) located on the 

upper part of the sensor main unit, then fit the cover 

to the sensor main unit. 

 

(1) Fixing the Mounting Plate 

Screw either (A) or (B), and fix the Mounting Plate 

to the outlet box, via outlet box cover located   

inside the wall. 

For screws, use M4 screw (2 pieces) and spring 

washer provided.

 

Содержание DSW-100-H

Страница 1: ...lead to dangerous conditions and cause death or serious injury if not carried out properly Caution Procedures which may lead to dangerous conditions and cause superficial to medium injury or physical damage or may degrade or damage the product if not carried out properly Warning To prevent an electrical shock or fire only Shinko or other qualified service personnel may handle the inner assembly To...

Страница 2: ...sive gases No mechanical vibrations or shocks No exposure to direct sunlight an ambient temperature of 0 to 50 32 to 122 that does not change rapidly and no icing An ambient non condensing humidity of 5 to 90 RH An absence of chlorinated and sulfidizing gases No large capacity electromagnetic switches or cables through which large current is flowing No water oil chemicals or the vapors of these su...

Страница 3: ...ty sensitive so be sure to insert the sensor correctly otherwise the sensor will be broken and measurement will be impossible Never disassemble the humidity sensor as it may lead to malfunction 4 Mount the main unit cover then turn the power to the unit ON Socket Humidity sensor HD S2 3 Mounting Main Unit Screw 4 places C as indicated by the dotted lines and fix the sensor main unit to the Mountin...

Страница 4: ...m up period 60 minutes The output accuracy will be affected if the conditions above are changed Response characteristics Approx 20 seconds Time to reach 90 of the RH value when the RH shifts between 30 85 RH However airflow 5 l min 0 16 m s Waterproof filter attached Hysteresis Approx 0 RH Stabilization time 20 minutes Power Consumption Approx 550 mW 2 wire type Approx 3 W 4 wire type Operating En...

Отзывы: