25
8.2 Control Output OFF Function
The control action and output of an instrument (or instruments) can be turned OFF without turning
OFF their power supplies using this function.
To turn the control output OFF, press the
key for approximately 1 second.
[
] is indicated on the PV display while the function is working.
(However, indication of the PV display depends on the selection in [Indication when output OFF].)
Once the control output OFF function is enabled, the function cannot be released even if the power
to the instrument is turned OFF and ON again.
To cancel the function, press the
key again for approx. 1 second.
PV/SV display mode (Automatic control)
Control output OFF
8.3 Auto/Manual Control Switching
Select ‘Auto/Manual control function’ in [OUT/OFF key function] in Setup mode.
By pressing the
key in PV/SV display mode, Auto/Manual control function can be switched.
If control action is switched from automatic to manual and vice versa, balanceless-bumpless function
works to prevent a sudden change in the output MV.
When automatic control is switched to manual control, the MEMO display indicates [ ].
The output MV can be increased or decreased by pressing the
or
key to perform the control.
By pressing the
key again, the unit reverts to PV/SV display mode (automatic control).
Whenever the power to the controller is turned on, automatic control starts.
Selecting Auto/Manual control in [OUT/OFF key function]:
Proceed to Setup mode.
Press the
and
key (in that order) together in PV/SV display mode
for approx. 3 seconds.
The unit proceeds to Setup mode.
Proceed to OUT/OFF key function.
Press the
key until [OUT/OFF key function] appears.
OUT/OFF key function selection
Select
(Auto/Manual control function) with the
key.
: Control output OFF function
: Auto/Manual control function
Register the selected function.
Press the
key to register the selected function.
The unit reverts to PV/SV display mode.
Switching from Automatic to Manual control, and vice versa:
PV/SV display mode
(Automatic control)
key
Manual control
Increases or decreases
the Output MV with the
,
key.
(Multiple times)
key (approx. 1 sec)