7. Settings
7.1 Main Setting Mode
To enter Main setting mode, press the
key in PV/SV display mode.
Character
Name, Function, Setting range
Default value
SV
0
• Sets SV.
• Setting range: Scaling low limit to Scaling high limit
SV2
0
• Sets SV2.
Not available if the SM option is not ordered, if C5 option is ordered or if ‘OUT/OFF
external selection 2’ is selected in [Contact input function].
• Setting range: Scaling low limit to Scaling high limit
SV3
0
• Sets SV3.
Not available if the SM option is not ordered, if C5 option is ordered or if ‘OUT/OFF
external selection 1 or 2’ is selected in [Contact input function].
• Setting range: Scaling low limit to Scaling high limit
SV4
0
• Sets SV4.
Not available if the SM option is not ordered, if C5 option is ordered or if ‘OUT/OFF
external selection 1 or 2’ is selected in [Contact input function].
• Setting range: Scaling low limit to Scaling high limit