- 20 -
7-1
.
.
.
.
Starting the Engine
1) Turn all breakers (main and 1-P) to "OFF".
2) Turn the fuel lever (on the fuel filter and water separator) to "OPEN".
3) Set the idle control switch to "AUTO".
4) Check that the emergency stop switch has been released.
5) If the temperature is 5°C or less, turn the starter switch to the "PREHEAT"
position and wait until the preheat lamp turns off. (Approx. 5 seconds)
6) Turn the starter switch to the "START" position to start the starter motor,
which then starts the engine.
7) After the engine starts, remove your hand from the starter switch.
8) Allow the engine to warm up for approximately 5 minutes.
<Note>
•
Do not crank the starter motor for 15 seconds or more continuously.
•
If repeating starter switch operation, wait 30 seconds or more between
operations.
•
After the engine starts, do not turn the starter switch to "START" during operation.
■
Restarting after Stopping due to Running Out of Fuel
The equipment includes an automatic air-bleeding device. You can easily restart
the engine according to the following procedures even if the engine stops due to
running out of fuel.
1) Turn all breakers (main and 1-P) to "OFF".
2) Turn the starter switch to the "STOP" position.
3) Add fuel to the fuel tank.
4) Set the idle control switch to "AUTO".
5) Turn the starter switch to the "START" position and crank the starter motor for
approximately 10 seconds.
6) After the engine starts, remove your hand from the starter switch.
7) Wait for air to be completely bled from the fuel pipes and engine speed to
stabilize (approx. 1 minute). (Engine speed is not stable until all air is bled from
the fuel pipes.)
1-P Breaker
Main Breaker
Emergency
Stop
Switch
Fuel Lever
(on fuel filter)
Close
Open
Starter Switch
Idle Control Switch
Preheat Lamp
Fuel Lever
(on water separator)
Open
Close