10
⑤
HORN RESET button
Use this button deactivate the horn output without acknowledging the alarms.
⑥
FAULT RESET button
Use this button to acknowledge alarms and deactivate the horn output. Inactive alarm
will disappear immediately and status of active alarms will be changed to “confirmed”
so they will disappear as soon as their reasons dismiss.
⑦
UP button
Use this button to move up or increase value.
⑧
PAGE button
Use this button to switch over display pages.
⑨
DOWN button
Use this button to move down or decrease value.
⑩
ENTER button
Use this button to finish editing a setpoint or moving right in the history page.
⑪
GCB button
No use.
⑫
GENERATOR status indicator
There are two states
– Gen-set OK (indicator is green) and Gen-set failure (indicator is
red). Green LED is on if the generator voltage is present and within limits. Red LED
starts flashing when gen-set failure occurs. After FAULT RESET button is pressed,
goes to steady light (if an alarm is still active) or is off (if no alarm is active).
⑬
GCB on
No use.
⑭
Load
No use.
⑮
Operation Display
< Note>
The displayed information is structured into “pages” and “screens”. USE PAGE button to switch
over the pages.