The temperature unit at the time of a sensor input is set up from      
     (℃) ,     (

).

Not displayed when the linear input is chosen.

 Scaling lower limit value at the time of linear input is set up.

Initial value :   
Setting range :     

Initial value : 0.0
Setting range : -1999 

 9989 digits

Initial value : 100.0
Setting range : -1989 

 9999

 

digits

Initial value: multi         , voltage        , current   
Setting range: Chosen from 5-5.measuring range code table.

Combination of input type and measuring range is set by code.

6

Initial value : 0
S etting range : 

500

500 Digits

Initial value : 0.00
Setting range : ±5.00%

Initial value : 0
Setting range : 0 

 9999 seconds

Used for correction of input errors such as sensor.
If offset correction is performed, control is also performed with the 
corrected value.

Maximum input value is corrected within limit of ±5.00% of 
measuring range. 
If corrected, inclination of spang changes in straight line which 
connects zero point and correction maximum value.

When input change is violent or noise is overlapped, used in order to 
ease the influences.
In 0 second setting, filter does not function.

If       key is pressed, it shifts to the first setting screen PV offset 
correction screen.

Mode 2 lead screen

Output 1 PID1 proportional-band (P) setting screen

Output 1 PID1 Integral time (I) setting screen

PV offset correction (PV bias) setting screen

PV gain correction setting screen

PV filter setting screen

Mesuring range setting screen

Temperature unit setting screen

Input scaling lower limit value setting screen

Input scaling upper limit value setting screen

Input scaling Decimal point position Setting screen

Return to mode 2 lead screen.

(

4

)

 Mode 2 screens Scale and PV setting 

Mode 3 lead screen

key

key

key

key

Initial value : 3.0%
Setting range : OFF, 0.1 

 999.9%

When performing auto tuning, no necessity for a setting basically.
If OFF is chosen, it  becomes ON-OFF (two positions) operation.

Initial value : 120 seconds
Setting range : 0FF, 1 

〜 

6000 seconds

Output 1 PID1 Derivative time (D) setting screen

Initial value : 30 second 
Setting range : 0FF, 1 

〜 

3600 seconds

When performing auto tuning, no necessity for a setting basically.
This screen is not displayed at the time of ON-OFF operation.
Becomes P operation or PD operation in I=OFF setting.

When performing auto tuning, no necessity for a setting basically.
This screen is not displayed at the time of ON-OFF operation.
Becomes P operation or PI operation in D=OFF setting.

The offset correction at the time of I = OFF ( P operation,PD operation]) 
is performed.
This screen is not displayed at the time of ON-OFF operation.

The differential gap at the time of ON-OFF operation is set.
Displayed at the time of  P=OFF ( ON-OFF operation) setup.

Output1 PID1 manual reset setting screen

Initial value : 0.0
Setting range : 

50.0

50.0%

Output 1 PID1 differential-gap setting screen

Initial value : 5  
Setting range : 1 

〜 

999 unit

Output lower limit value of output 1 PID1 is set up.

Output1 PID1  minimum limiter setting screen

Initial value : 0.0
Setting range : 0.0 

〜 

99.9%

Upper limit value of output 1 PID1 is set .

Output 1 PID1 maximum limiter setting screen

Initial value : 100.0
Setting range : output limiter lower limiter 0.1

100.0%

Content is the same with output 1 PID1. 

Output 1 PID2 proportional band (P) setting screen

 Initial value : 3.0%
Setting range : OFF, 0.1

 999.9%

Contents is the same with output 1 PID1. 

Output 1 PID2 integral-time (I) setting screen

Initial value : 120 seconds
Setting range : 0FF, 1

6000 seconds

Contents is the same with output 1 PID1.

        

Output 1 PID2 derivative-time (D) setting screen

Initial value : 30 seconds
Setting range : 0FF, 1

 3600 seconds

 Contents is the same with output 1 PID1.

Output 1 PID2 manual reset setting screen

Initial value : 0.0
Setting range : 

50.0

50.0%

Scaling upper limit value at the time of linear input is set up.

No setup
If      key is pressed, it shift  to the first setting screen, output 1 
proportional band 
setting screen. In this screens, PID which can be used in output 1, 1

related Items and soft start of output 1,and proportional period output 
characteristics are set up. 

Initial value : the first place after decimal point (0.0)
Setting range : no decimal point 0

the third place after decimal point 

(0.000)
            Decimal point position of input scaling is set .

Suppose that the difference between a lower limit value and 
upper limit value is 10 or less,or over 10,000. In this setting, 
upper limit value is compulsorily changed into that of +10 or ± 
10000 digits. Upper limit value cannot be set as lower limit  
value of +10 digits or less,or that of over 10,000 digits.

The screen of input scaling serves as a monitor at the time of a 
sensor input. 
Setting change cannot be performed.

NOTE

At the time of STBY (RST) and scale over output, limiter 
value is disregarded.

NOTE

NOTE

(

5

)

 Mode 3 screen Out 1 setting

key

key

key

key

key

key

key

key

key

key

key

key

key

key

key

key

key

Press

       

key in mode1 lead screen, or press     

 

key in mode3 lead screen, 

then being displayed.

Содержание MAC3 Series

Страница 1: ...t 7 DI N none D external control input DI 1 2 3 three points 8 CT Input N none H CT Input two points 9 Analog Output N none T current 4 20mA V voltage 0 5V 10 Communication N none R RS485 11 Program F...

Страница 2: ...dimension and panel cutout MAC3 external dimensions unit mm MAC3 panel cutout unit mm Do not turn on electricity while wiring to avoid an electric shock Do not touch a terminal or live part while turn...

Страница 3: ...c screen then it jumps to the lead screen of Mode 1 Press key for three seconds on the lead screen of each Mode screens then it jumps to the basic screen Press key for three seconds on the lead screen...

Страница 4: ...ol stop Output OFF 0 operation conduct of control operation Choose RUN by key Decide by key then Monitor LED s RUN lights up to start control operation Initial value stanby Initial value at the time o...

Страница 5: ...lized when measuring range unit and scaling are changed Lower limit value of target value is set The operation mode of each deviation alarm is Effective at the time of automatic output Each deviation...

Страница 6: ...peration or PI operation in D OFF setting The offset correction at the time of I OFF P operation PD operation is performed This screen is not displayed at the time of ON OFF operation The differential...

Страница 7: ...1 standby operation setting screen Event 1 latching setting screen Event 1 output characteristics setting screen Event 2 mode setting screen Initial value 0 0 Setting range 0 0 99 9 Contents is the s...

Страница 8: ...tion is possible no decimal pont 0 1 0 01 0 001 Unit Code Measureing Range Input Type Code Unit Code The same as event 1 Event 2 output characteristics setting screen Initial value Setting range The s...

Отзывы: