When you choose pressing at lower limit value, the SV
display turn off at basic screen. But it will turn on at the setting screen.
No setting on this screen. Press the key, then it shifts to the first
setting screen, keylock setting screen.
Setting range : measuring range lower limit value~measuring range
upper limit value
−
1 and (SV display turn off)
When upper limit value is smaller than lower limit value, the value
compulsorily becomes lower limit value +1.
Initial value : measuring range upper limit
Setting range : SV limiter lower limit value +1~ measuring range
upper limit value
Setting upper limit value of target value is set.
Only change of Execution SV (basic screen) and keylock is possible.
Possible to change numerical value value manualy, and key lock level
Only change of a keylock is possible.
Only change of a keylock is possible It can be locked key
Notes : Even when keylock is set as 1 and 2, manual output value is
possible to change.
On the latching setting screen of each EV mode,
and which
chose are displayed. If latching is once EV is outputted, EV
output state is maintained even if EV is in the state of OFF. When EV is
in a latching state, decimal point of the minimum digit blinks, and it
shows that release of EV is possible. If key is pressed, EV is released
and a decimal point lights off.
However, release is impossible when a state is in EV power range.
5
AT is performed by ON selection ,and canceled by OFF selection.
Not displayed at the time of STBY (RST), a manual output, and P
(proportional band) =OFF.
Except in the setting of keylock OFF, AT is unable to perform in scale over.
(At the time of DI allotment, execution of AT by DI can be performed.)
Even in such a case,halfway release is performed on this screen.
Release of AT, STBY (RST), EV operating point, setting of keylock, and
mode 5
〜
9screen are operateable with key.
Except in th setting of AT normal end, execution of AT is canceled
compulsorily at the time of STBY (RST) selection and AT release setup.
At the time of no program option and with program option and is chosen
on Action mode2 screen of basic screens,lead screen of FIX setting screens is
displayed when key is pressed for 3 seconds.
If
key is pressed for 3 seconds on lead screen, it returns to basic screen.
Initial value : At the time of sensor input 0
linear input time scaling lower limit
Setting range: sensor input time within measuring range
linear input time
within scaling range
Moreover, within limit of SV limiter.
Initial value : 1
Setting range : 1, 2, 3
When SV1 is Execution SV,being reflected in basic screen.
Being initialized when measuring range, unit, and scaling are changed.
Lower limit value of target value is set .
The operation mode of each deviation alarm is
Effective at the time of automatic output.
Each deviation alarm serves as PV’s deviation to Execution SV.
Event operation other than each deviation alarm is always effective.
Setting range: upper limit absolute value
within measuring range
within scaling
lower limit absolute value within measuring range within scaling limit
The operating point of the alarm type allotted to EV1 is set up.
No option, No display when
and are allotted to EV1.
Initial value: upper limit absolute value measuring range Scaling upper
lower limit absolute value measuring range Scaling lower limit
Initial value,setting range, contents are the same with EV1
Initial value:
Setting range:
release EV1
release EV3
release EV2
release all EVs at a time
upper limit deviation
lower limit deviation
within deviation
outside deviation
CT1 or CT2
guarantee
upper limit deviation
lower limit deviation
within upper-lower limit deviation
outside upper-lower limit deviation
AT (Auto Tuning) execution screen
EV1 (event 1) operating-point setting screen
EV2 (event 2) operating-point setting screen
Latching release screen
Return to basic screen
Initial value:
Setting range:
unit
unit
unit
unit
(
2
)
FIX
(
constant value control
)
setting screens
(
3
)
Mode 1 screens key lock and SV limiter Setting
basic screen
three seconds
three seconds
lead screen of FIX setting
FIX lead screen
SV1 setting screen
SV1 output1 PID No. setting screen
SV1 output2 PID No. setting screen
Return to FIX lead screen
Mode 1 lead screen
Keylock setting screen
SV limiter lower limit setting screen
SV limiter upper limit value setting screen
Return to mode1 lead screen.
key
When SV1 is Execution SV, PID No. that will be used for control of
output 1 is chosen from 1
〜
3.
Initial value : 1
Setting range : 1, 2, 3
Initial value :
Setting range :
Initial value : measuring range lower limit
When SV1 is Execution SV, PID No. that will be used for control of
output 2 is chosen from 1
〜
3.
Displayed when output 2 option is added.
Press key for 3 seconds on basic screen, then displayed
key
key
key
key
key
key
key
key
key
Chosen PID No. is displayed when FIX is in operation.
PID No. chosen at each step and on-going step No. are displayed by tums
when PROG is in operation.
PID No. of output 1 is displayed in the first digital, and PID No. of output 2 is
displayed in the third digital. The third digital is shown as when there is no
output 2 option.
This screen is not displayed in the state of STBY (RST).
Initial value:
Setting range:
PID No. monitoring screen
key
key
Execution SV setting screen
key
key
No setting on this screen.
Press key, then it shifts to the first setting screen SV1 setting screen.