PID Group (Group 3)
- 47 -
PID Group
[Key Lock 1]
Code
Description of function
Setting range
Initial value
P
1
Proportional band (%)
OFF, 0.1~999.9%
3.0%
I
1
Integral time (sec.)
OFF, 1~6000 sec.
120 sec.
D
1
Differential time (sec.)
OFF, 1~3600 sec.
30 sec.
DF
1
Action hysteresis
1~9999 unit
20 unit
Zone
Setting of zone
Within measuring range
0 unit
MR
Manual reset
-50.0~50.0%
0.0% (1 output)
-50.0% (2 outputs)
PID Group
[Key Lock 1]
Code
Description of function
Setting range
Initial value
P
2
Proportional band (%)
OFF, 0.1~999.9%
3.0%
I
2
Integral time (sec.)
OFF, 1~6000 sec.
120 sec.
D
2
Rate time (sec.)
OFF, 1~3600 sec.
30 sec.
DF
2
Action hysteresis
1~9999 unit
20 unit
DB
Dead band
-20000~20000 unit
0 unit
PID Group
[Key Lock 1]
Code
Description of function
Setting range
Initial value
m_O
1
, Lmt_L
Lower limit value of output 1 limit
-5.0~104.9%
0.0%
m_O
1
, Lmt_H
Higher limit value of output 1 limit
-4.9~105.0%
100.0%
m_O
2
, Lmt_L
Lower limit value of output 2 limit
-5.0~104.9%
0.0%
m_O
2
, Lmt_H
Higher limit value of output 2 limit
-4.9~105.0%
100.0%
PID
[Key Lock 1]
Code
Description of function
Setting range
Initial value
Zone HYS
Zone hysteresis
0~10000 unit
20 unit
Zone PID
Zone PID mode
Singl
Zone
Singl
REM PID
Remote PID No.
01~10
01
SF
Target value function
0.00~1.00
0.40
m=1~10
Содержание SR253 Series
Страница 63: ...59...