background image

 

-1-

 

 

PAC18 Series 

Single-Phase Thyristor Power Regulator

 

Instruction Manual 

 

Thank you for purchasing a Shimaden PAC18 Series Single-Phase Thyristor Power Regulator. 
After making sure the product fits the desired description, you should carefully read the instructions and get a good understanding of the contents before 
attempting to operate the equipment. 

 

Request 

The instruction manual should be kept in a handy place where the end user can refer to it when necessary. 

Preface

 

The instruction manual has been prepared for those involved in setup, wiring, operation or routine maintenance of PAC18 Series equipment. 
The manual provides information concerning mounting, wiring and precautions when working with PAC18 Series equipment. 
You should therefore keep it in a handy place to refer to when operating and handling the equipment. 
Be sure to observe all precautions and adhere to the procedures provided in the manual. 
Safety rules, precautions concerning equipment damage, additional instructions and notes are written based on the following headings. 

 

Matters that could result in injury or death if instructions are not followed. 

WARNING 

Matters that could result in equipment damage if instructions are not followed. 

CAUTION 

additional instructions and notes 

Note 

 

 

 

WARNING

 

PAC18 Series equipment is designed to control heater power, etc., of common industrial equipment. It should not be used for nuclear power generation, 
traffic control, communications or medical equipment. You should either take appropriate safety measures or avoid using for control that could have a 
serious effect on human life. The manufacturer shall not be liable for an accident that results if used without taking appropriate safety measures. 

 
 

 

 

WARNING

 

1. The power regulator should be used so the terminal elements in the control box, etc., are not touched by human beings. 
2. The power regulator should not be used as a switch. 

Even if output is zero, power is present in the capacitors and resistors of the output circuit, and could result in accident involving human life or serious 
bodily injury due to electrical shock. 

3. Radiation fins and chassis become extremely hot. Never touch the radiation fins or chassis. Doing so could result in burn injury. 
4. Do not supply power when wiring. Doing so could result in electrical shock. 
5. Do not touch terminal elements or other charged parts while conducting electricity. Also, do not introduce foreign objects or matter into the equipment. 

If a foreign object or matter accidentally gets inside, be sure to turn off the power and make sure all is safe before introducing tools or your hands. 

 
 

 

 

CAUTION

 

If there is danger of damage to any peripheral device or equipment due to failure of the power regulator, you should take appropriate safety measures such 
as mounting a rapid fuse or overcurrent circuit breaker. 

 
 

 

 

CAUTION

 

1. Concerning the 

 

alert symbol on the power regulator’s plate, a 

 

alert symbol is printed on the label applied to the outer surface of the device. 

The symbol is provided to prompt you to employ special care not to touch the device because doing so could result in electrical shock if parts that   
conduct power are touched when power is present, or could result in burn injury if touched when hot, etc. 

2. Provide a switch or breaker as a means of cutting off power for external power circuit connected to the power terminal of the device. 

Mount a switch or breaker near the controller where the operator can get to it easily and label it as an electrical breaker for the device. 

3. Be sure to securely fasten conductor cable connections before using. 

Failure to do so could result in burning from overheating due to contact resistance. 

4. Be sure power supply voltage and frequency do not exceed the rating. 
5. Do not apply voltage/current other than rated input to the input terminal. 

Doing so could shorten the life of the product or result in equipment failure. 

6. Voltage/current of load connected to the output terminal should not exceed the rating. 

Using voltage/current that exceeds the rating could shorten the life of the device by raising the temperature, and could result in equipment failure. 

7. Be sure to mount the terminal cover that comes with the device after wiring. 
8. The user should absolutely not modify or use the device in any way other than it was intended to be used. 
9. Be sure to observe the notes and precautions provided in the manual to use the device safely and maintain its reliability.

 

Note: Shimaden shall bear no responsibility, monetarily or otherwise, for accident or damages caused by failure to observe warnings, notes and precautions   

contained in the instruction manual. 

                                                                                                                                 

MPA018-E01-B 

                                                                                                                                  JUN.

 2010 

Содержание PAC18 Series

Страница 1: ...Do not supply power when wiring Doing so could result in electrical shock 5 Do not touch terminal elements or other charged parts while conducting electricity Also do not introduce foreign objects or...

Страница 2: ...ter break alarm function 13 12 1 Rapid fuse sold separately 13 12 2 Heater break alarm function optional 14 12 2 1 Operation overview 14 12 2 2 Setting method 14 12 2 3 Precautions when setting 14 13...

Страница 3: ...lation zero voltage switching control P0 C1 X1 3 4 6 9 Voltage 1 5V DC input resistance 200 built in contact common Current 4 20mA DC receiving impedance 100 built in contact common Voltage 0 10V DC i...

Страница 4: ...ontrol power supply input terminal 100 240 V AC B characteristic 10k Display Status display red 1 digit Displays parameter screen group and alarm contents Parameter display green 3 digits Displays par...

Страница 5: ...5 3 External dimensions terminal dimensions weight 20 30A Weight Approx 0 8 kg Unit mm 45 60A Weight Approx 1 8 kg Unit mm 80 100A Weight Approx 3 0 kg Unit mm...

Страница 6: ...r corrosive gases oil mist or excessive dust that could cause insulation to deteriorate Places subject to vibration or impact Places exposed to water dripping or direct sunlight Places directly expose...

Страница 7: ...in circuit wiring 7 1 Wiring Open the terminal block cover to connect wires to the terminal block Loosen the fastening screws mounted on the device and wire 7 2 Power supply and load main circuit wiri...

Страница 8: ...ve Controller PAC18 C1 C2 Voltage current Connection with contact output controller Controller PAC18 C2 C3 On off signal If connecting with on off signal connect between C3 and C2 8 2 Multiple units c...

Страница 9: ...yed Output is automatically reset if abnormal state is eliminated Set key sequence 1 3 Power failure alarm when outputting power failure alarm to optional alarm contact output AL 10 2 Overcurrent Curr...

Страница 10: ...displayed in the alarm display of the left LED digit The key sequence 0 0 Output monitor basic screen display does not display less than 0 or more than 100 If control input is less than 10 the key seq...

Страница 11: ...adjuster output cannot be changed by variation limit of key sequence 1 10 Variation limit 11 2 Ramp lower limit base power adjustment Set adjustment target by key sequence 1 7 Ramp lower limit setting...

Страница 12: ...ts the thyristor if using loads with large inrush current such as pure metal heaters or lamp heaters Detects output current by built in CT and produces delay time to control the control angle of the t...

Страница 13: ...set Rapid fuse Fuse holder QSF006 20 30A 350GH 50UL Hinode Electric Co Ltd 45 60A 350GH 100UL Hinode Electric Co Ltd Separately sold part type 80 100A CF5R06 150 Fuji Electric FA Components Systems C...

Страница 14: ...break do so with device output set to maximum within the output range actually used If set outside the actually used output range or when output is small load current is less than 25 of the rated cur...

Страница 15: ...down by Manual operation can be conducted by key sequence 3 1 Manual operation 2 Manual operation by external adjuster VR3 Shorting the C2 C3 terminals selects external adjuster VR3 In this case the m...

Страница 16: ...characteristics 10 0 50 55 100 90 Elevation m Load current Elevation load current characteristics 0 2000 100 80 500 14 3 Control type and output waveform The device includes phase control and cycle ca...

Страница 17: ...tional output You can obtain output voltage proportional to control input signal The current limit function is necessary for large inrush current loads 14 4 3 Phase control voltage square proportional...

Страница 18: ...harmonic wave voltage check the power supply waveform 16 Precautions for inductive load Transformer usage objective 1 To match voltage when heater voltage differs from power supply voltage 2 When it...

Страница 19: ...le adjustment is required for complex control With complex control slow up is conducted by phase control ahead of cycle calculation zero voltage switching control to cancel magnetic flux imbalance of...

Страница 20: ...quence 18 1 Screen sequence Standard screens are indicated by a solid line box and optional screens are indicated by a dotted line box Optional screens may not be displayed depending on the product sp...

Страница 21: ...imal point not displayed for 100 0 4 VR2 operation amount Operation amount of VR2 is displayed in the range of 0 100 Set either key sequence 1 7 Ramp lower limit setting key sequence 1 8 Ramp higher l...

Страница 22: ...key setting ramp higher limit cannot be set below ramp lower limit For VR setting ramp lower limit drops if ramp upper limit is lower than ramp lower limit If the difference between ramp higher limit...

Страница 23: ...reen is displayed if you have selected communication optional Displays communication protocol MODBUS RTU 1 14 Communication address optional This screen is displayed if you have selected communication...

Страница 24: ...nals are shorted When communication manual output operation be enabled the manual output screen group can not be selected by key operation When Contact 2 position control input be selected the manual...

Страница 25: ...ristics resistance value B 10k Lead Vinyl lead 1 m M3 crimp terminal Scale plate knob 1 each provided External dimensions and mounting method unit mm 19 2 External rapid fuse 20 30A Model QSF006 80 10...

Страница 26: ...al dimensions unit mm 80 100A Model QSH003 External dimensions unit mm Insulation board 41 65 26 4 5 18 2 65 1 1 2 4 1 5 35 3 4 27 22 17 8 8 1 5 4 3 2 3 5 2 M6 17 8 16 26 1 132 116 102 70 48 16 72 13...

Страница 27: ...ure metal load etc inrush current limitation response time 0 1 sec or less initial value 100 or rated current 0 100 of rated current set by external adjuster current limiter or 0 120 of rated current...

Страница 28: ...nce Between control power supply terminals and control input terminals 500V DC 20M min Between main power supply terminals and chassis 500V DC 20M min Dielectric strength Between control power supply...

Страница 29: ...to zero for ramp lower limit function Check the value of the parameter setting screen and position of the external adjuster VR to which the ramp lower limit is allocated Check VR position on monitor...

Страница 30: ...30 MEMO...

Страница 31: ...31 MEMO...