FP23 2-input
I n s t r u c t i o n M a n u a l
http://www.shimaden.co.jp
F o r q u e s t i o n s , p l e a s e c o n t a c t
Y O U R L O C A L A G E N T
or
e x p - d e p t @ s h i m a d e n . c o . j p
ڦ
External Dimensions
ڦ
Panel Cutout Dimensions
ڦ
Mounting
Caution
To ensure safety and maintain the functions of this device, do not disassemble this device.
If this device must be disassembled for replacement or repair, contact your dealer.
Follow the procedure below to mount this device on a panel.
1.
Drill mounting holes referring to the panel cutout dimensions described in the previous
section.
The applicable thickness of the mounting panel is 1.0 to 8.0 mm.
2.
Press this device into the panel from the front of the panel.
3.
Insert the mounting fixtures at the top and bottom of this device, and tighten the screws
from behind to fasten the device in place.
4.
Over-tightening the screws may deform or damage the device housing.
Take care not to tighten the screws too tight.
5.
After completing wiring after installation, attach the terminal cover.
ڦ
Rear Terminal Arrangement Diagram
ڦ
Wiring Example of Open Collector Output
The following is an example of wiring open collector output for external control output
terminals (DO).
Open collector output (for connecting to relays)
DO1 to DO3: Darlington output
Output rating: 24V DC 50mA max.
DO terminals other than DO1 to DO3
All the terminals other than DO1 to DO3 are open collector output terminals (24V DC 8mA max.).
Note that the output ratings differ from that of DO1 to DO3.
Termi
nal
No
Symbol Description
1
2
+
-
Analog output 1 (optional)
3
4
+
-
Analog output 2 or Sensor
power supply (optional)
5
6
+
-
Heater Break alarm
CT input (optional)
8
10
+
-
mV,
thermocouple
input
Input 1
8
10
11
A
B
B
RTD input
7
10
+
-
V, mA input
45
46
L
N
Power supply
47
48
Grounding (internal
shorting across terminals)
49
50
51
COM +
NO -
NC
Control output 1
23 COM
External
control
output DO
(standard)
24
25
26
DO1
DO2
DO3
Darlington
output
27
28
DO4
DO5
Open
collector
output
29
30
31
32
33
DI1
DI2
DI3
DI4
COM
External control output DI
(standard)
Termi
nal
No
Symbol
Description
34
35
36
37
DO6
DO7
DO8
DO9
External control output DO
Open collector output
(optional)
38
39
40
41
42
43
44
DI5
DI6
DI7
DI8
DI9
DI10
COM
External input DI5 to DI10
(optional)
12
13
14
SG
SD +
RD -
Communication function
(optional)
15
16
17
COM +
NO -
NC
Control output 2
(optional)
19
21
+
-
mV,
thermocouple
input
Input 2
19
21
22
A
B
B
RTD input
18
21
+
-
V, mA input
A receiving resistor of 1/2W 250
ȍ
0.1% is
attached across input terminals (7-10) for
use for the 0 to 20mA, and 4 to 20mA
inputs.
➃Ꮚ䜹䝞䞊䚷䚷༢䠖㼙㼙
with terminal cover
Unit: mm
Unit: mm
or more
or more
Mounting fixture
FP23
Mounting fixture
࣮ࣜࣞ