background image

7. Connection Diagram 

* For model with Triac (SSR), motor 

power supply voltage range must be 20 

~ 120V AC. 

It is recommended that the fuse between 

terminal

and the power supply termi- 

nal be used to protect motor upon mal- 

function. 

(Current rating for fuse must be approx- 

imately twice the size which is appro- 

priate for the motor for which it is being 

used.) 

CONTACT

TRIAC  

• 

Make sure the motor power supply matches the rating of the motor to be used. 

• 

For inverting the operating direction of motor (to open with input at 0% and close with 

input at 100%), permute the wires for terminals

and

as well as those for termi- 

nals

and

respectively. 

11 

CW

: Clockwise rotation (open) 

CCW : Counterclockwise rotation (closed) 

8. Adjustment 

8-1.  Characteristic of Input Signal vs. Operating Output 

8-2. Adjustment of Operating Output 

Confirm that the final control element is at 100% or the open position when 100% input signal is applied and at 0% or the close d posi- 

tion when 0% input signal is applied. 

If there is any dislocation at the 0% position, adjust the Zero trimmer. In the case of dislocation at the 100% position, adjus t the Span trimmer. 

Note: Since the reaction of the final control element is normally slow, adjust the Zero and Span trimmers slowly. 

8-3. Adjustment of Deadband (DB) 

The deadband refers to the sensitivity between the clockwise (open) and counterclockwise (close) actions of the control motor. 

If the control motor repeats quick hunting, turn the deadband from the narrow band gradually to the wide band until hunting sto ps. 

If the deadband is set unnecessarily wide, the control motor may be dull in response. 

(The deadband may be variable within 1 to 10% of the input signal range.) 

9. Relay Application Diagram 

Characteristic

Run

Increased

Balanced

Decreased 

M2 - M1: ON (Open)

M2 - M1, M3: OFF (Stop)

M2 - M3: ON (Close)

RA

Heat 

DA

Cool 

LED Green lights.

LED goes out.

LED Red lights. 

The contents of this manual are subject to change without notice. 

Temperature and Humidity Control Specialists 

Head Office: 2-30-10 Kitamachi, Nerima-Ku, Tokyo 179-0081 Japan 

Phone: +81-3-3931-7891  Fax: +81-3-3931-3089 

E-MAIL: [email protected]  URL: http://www.shimaden.co.jp 

PRINTED IN JAPAN 

F: Fuse 

R2 
R1 
R3 

M2 

M1 
M3 

10 

11 



10 

11 





CW CCW 

F. B POT. 

CCW(closed) 

CW(open) 

Control Motor 

Motor Power 

Supply 

AC Power 

AC Power 

CCW(closed) 

CW(open) 

CW 

POT 

EM51 

DC 

INPUT 


POT 

R2 
R1 
R3 

M2 
M1 
M3 

CCW 

F. B POT. 

Control Motor 

Motor Power 

Supply 



EM51 

DC 

INPUT 


Open 

ZERO 

ZERO 

SPAN 

SPAN 

100%

100% 

70% 

50% 

20% 

0% 

0%

50%

100% 

Zero & Span Adjustment 
    0%=  0 ~ 20% (ZERO) 

100%=70 ~ 100% (SPAN) 

Input Signal 

D. BAND 

COM 

NO 

NO 

M2

M1

M3 

COM 

NO 

NO 

M2

M1

M3 

COM 

NO 

NO 

M2

M1

M3 

[email protected]

Distributed in New Zealand by:

   Christchurch

Ph: +6433430646
Fx: +6433430649

Auckland
098271930
098271931

www.intech.co.nz

Отзывы: