17
PVC/CPVC vent piping materials
Use only the materials listed in Table 2A
for vent pipe, and fittings. Failure to
comply could result in severe personal
injury, death, or substantial property
damage.
Installation must comply with local
requirements and with the National Fuel
Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.
Venting and combustion air
DANGER
The Shield water heater must be vented
and supplied with combustion and
ventilation air as described in this section.
Ensure the vent and air piping and the
combustion air supply comply with these
instructions regarding vent system, air
system, and combustion air quality. See
also Section 1 of this manual.
Inspect finished vent and air piping
thoroughly to ensure all are airtight and
comply with the instructions provided and
with all requirements of applicable codes.
Failure to provide a properly installed vent
and air system will cause severe personal
injury or death.
All vent pipes must be glued, properly
supported, and the exhaust must be
pitched a minimum of a 1/4 inch per foot
back to the water heater (to allow drainage
of condensate).
WARNING
NOTICE
WARNING
WARNING
For closet and alcove installations, CPVC
material MUST BE used in a closet/alcove
structure. Failure to follow this warning
could result in fire, personal injury, or
death.
NOTICE
Requirements for installation in Canada
1.
Installations must be made with a vent pipe system
certified to ULC-S636.
IPEX is an approved vent manufacturer in Canada
supplying vent material listed to ULC-S636.
2.
The first three (3) feet of plastic vent pipe from the
appliance flue outlet must be readily accessible for visual
inspection.
3.
The components of the certified vent system must not be
interchanged with other vent systems or unlisted
pipe/fittings. For concentric vent installations, the inner
vent tube must be replaced with field supplied certified
vent material to comply with this requirement.
4.
The 3" Concentric Vent Kit available from Lochinvar (see
Section 3 –
Sidewall Termination – Optional Concentric
Vent
) and the 3" Concentric Vent Kit available from IPEX
are both approved for use on the Shield Water Heater. Both
kits are listed to the ULC-S636 standard for use in Canada.
2
General venting
(continued)
Installation & Service Manual
TM
This appliance requires a special venting
system. The vent connection to the
appliance must be made with the starter
CPVC pipe section provided with the
appliance if PVC/CPVC vent is to be used.
For stainless steel venting use an adapter
from Table 2B (pg. 20) that corresponds
with the intended vent manufacturer to be
used and discard the CPVC starter piece.
The field provided vent fittings must be
cemented to the CPVC pipe section using
an “All Purpose Cement” suitable for PVC
and CPVC pipe. Use only the vent
materials, primer, and cement specified in
this manual to make the vent connections.
Failure to follow this warning could result
in fire, personal injury, or death.
Installing vent and air piping
Improper installation of PVC or CPVC
systems may result in injury or death.
CAUTION
Use only cleaners, primers, and solvents that
are approved for the materials which are
joined together.
NOTICE
1.
Work from the water eater to vent or air termination. Do
not exceed the lengths given in this manual for the air or
vent piping.
2.
Cut pipe to the required lengths and deburr the inside and
outside of the pipe ends.
3.
Chamfer outside of each pipe end to ensure even cement
distribution when joining.
4.
Clean all pipe ends and fittings using a clean dry rag.
(Moisture will retard curing and dirt or grease will prevent
adhesion.)
5.
Dry fit vent or air piping to ensure proper fit up before
assembling any joint. The pipe should go a third to
two-thirds into the fitting to ensure proper sealing after
cement is applied.