Upper and lower limit functions:

 

  The setting of HS and LS limit the set range of OFF temperature point , for 
example: HS is set to +15, LS is set to -10, the OFF temperature can only be 
adjusted between -10 and +15, when the OFF temperature to -10 then press 
"▼" key, the display will remain on the status of -10 and not decrease; when the 
OFF temperature to +15 then press "▲" key, the display will on the status of 15 
and not increase. If the set point outside this range, it needs to firstly change 
the value of HS and LS, then it can be achieved. 

Upper and lower limit settings:

 

  Press "SET" key and hold more than 3 seconds to enter the menu display, 
with "▲" or "▼" key adjusted to the screen, appearing "HS" or "LS" code, press 
the "SET" key to display the upper or lower limit set value, Then press "▲" or 
"▼" key to adjust the parameters. HS means upper limit. LS means lower limit.

◆High temperature alarm: 

 

If the measured temperature≥  OFF tempe AH alarm output relay. 
Thermostat alarm will sound, the display alternately shows H and the current 
temperature. Alarm, press any key to stop the alarm and relay output.   

◆  High temperature alarm settings: 

 

Press "SET" button and hold more than 3 seconds to enter the menu display, 
with "▲" or "▼" button transferred to the screen appears "AH" code, press the 
"SET" key to display the high-temperature alarm settings, press "▲ "or" ▼ "key 
to adjust the parameters, When AH is set to 0, the High temperature alarm 
function will be invalid   

◆  Low temperature alarm function:

   

If the measured temperature  <OFF temperature-AL when the alarm output 
relay. Thermostat alarm will sound, the display alternately shows L and the 
current temperature. Alarm, press any key to stop the alarm and relay output.   

◆  low temperature alarm settings: 

 

Press "SET" button and hold more than 3 seconds to enter the menu display, 
with "▲" or "▼" button transferred to the screen appears "AL" code, press the 
"SET" key to display the low temperature alarm settings, press "▲ "or" ▼ "key to 
adjust the parameters 
When AL is set to 0, the low temperature alarm function will be invalid

   

 
 
 

Содержание WH1603C

Страница 1: ...Thermostat Product Manual Shenzhen Willhi Electronics Co Ltd Tel 0755 29539385 Fax 86 0755 2953 9395 Technical support Engineer Tian ...

Страница 2: ...24V 110V 220V 10A Tone output WH7016G 1 degrees NO Optional 12V 24V 110V 220V 10A Tone output WH7016D 30 300 22 572 1 degrees NO Optional 12V 24V 110V 220V Optional 10A 30A NO WH7016D 0 1 1 degrees YES Optional 12V 24V 110V 220V Optional 10A 30A Tone WH1603D 0 1 1 degrees YES Optional 12V 24V 110V 220V Optional 10A 30A Tone WH7016J 1 degrees NO Optional 12V 24V 110V 220V 10A Tone output WH7016J 0 ...

Страница 3: ...16J WH7016E WH7016J WH1603E WH1603J Terminals 1 and 2 Connect the cooler or heater Terminals 1 and 3 Connect alarm Terminals 4 and 5 Connect the power Terminals 6 and 7 Connect temperature sensor Lock switch Switch either 1 or 2 to ON press SET 3 seconds to disable t he advance model user only can change temperature but can t reset the system ...

Страница 4: ...erminals 3 and 4 Connect the power Terminals 5 and 6 Connect temperature sensor Lock switch Switch either 1 or 2 to ON press SET 3 seconds to disable the advance model user only can change temperature but can t reset the system LED Status Description The WORK light is used as working indicator lights flashing is to indicate the delay of cooling or heating if the LED is always on it indicates it is...

Страница 5: ...justing mode press the SET key again and back to the standby mode ON temperature s In Heating mode ON temperature OFF temperature Difference In Cooling mode ON temperature OFF temperature Difference Set The Difference in the setting menu system menu settings Press SET key and hold on for three seconds to enter the controlled parameters setting press the or key to select the adjustment menu press S...

Страница 6: ...ple for Setting If it is set to cooling mode set the OFF temperature to 25 degrees Difference is set to 5 then when the measured temperature is below 25 degrees the relay is off close the output When the temperature is higher than or equal to 30 degrees pick up the relay again to start the output Cooling heating mode setting Press SET key and hold more than 3 seconds to enter the menu display the ...

Страница 7: ...erature we need to adjust the CA parameters because of the heat loss of the cup so that the display temperature can be in accordance with the one of the cup Delay Protection Function In the cooling mode the first power on when the measured value above the OFF temperature Difference value the machine will not immediately start cooling it needs to set the delay time then the machine can run to start...

Страница 8: ...perature AH alarm output relay Thermostat alarm will sound the display alternately shows H and the current temperature Alarm press any key to stop the alarm and relay output High temperature alarm settings Press SET button and hold more than 3 seconds to enter the menu display with or button transferred to the screen appears AH code press the SET key to display the high temperature alarm settings ...

Страница 9: ...settings value press or key to adjust the parameters Advanced settings Only for model WH7016C WH7016D WH7016E WH7016J WH1603C WH1603D WH1603E WH1603J Press SET and UP key and hold on for three seconds to enter the System Advanced menu settings press the or key to select the adjustment menu press SET key once to enter the appropriate parameter settings press or to adjust the parameters needed to be...

Страница 10: ...splays HHH Caution for using Please connect the correct operating voltage the machine normally works under the standard input voltage within range of 10 The load power should not exceed the maximum thermostat control power when exceeding please connect external AC contactor Please connect the power load correctly and the sensor or it will damage the thermostat when connect the wrong line Please do...