SharpEye
TM
IR3 Flame Detector User Guide
20
Detection Sensitivity
3.1.3
Other Fuels
The detector reacts to other types of fires as shown in Table
Table 2: Response Sensitivity Ranges
Type of Fuel
20/20MPI-R (ft/m)
Type of Fuel
Gasoline
140/43
100%
N-Heptane
140/43
100%
Alcohol 95%
100/30
70%
JP5
100/30
70%
Kerosene
100/30
70%
Diesel Fuel
100/30
70%
Methane
*
39/12
28%
IPA
115/35
80%
Methanol
98/30
70%
LPG
*
39/12
28%
Polypropylene
49/15
35%
Paper
49/15
35%
*
0.5m plume fire
Pan Fire Size: 1ft
2
/0.1m2
Maximum Wind Speed: 6.5ft/sec / 2m/sec
Maximum Response Time: 10sec