No air blown out from air conditioner
Cause / Action
• 

Whether air outlet or air inlet is blocked? 

/

 Eliminate the obstacles.

• 

Under heating mode, whether indoor temperature increase set 
temperature? (Cool and Heat model only) 

/

 The unit will stop blowing fan 

after reaching set temperature.

• 

Whether heating mode is started up just now? (Cool&Heat model only) 

/

 In order to prevent cold air, air conditioner will delay for a while to be 

started up, which is the normal phenomenon.

• 

Whether evaporator is defrosted? (confirm this by pulling out the 
filter) 

/

 It's the normal phenomenon. Air conditioner is defrosting. After 

defrosting is finished, it will resume operation.

Set temperature can't be adjusted.
Cause / Action
• 

Whether the unit operates under auto mode? 

/

 Temperature can't be 

adjusted under auto mode.

• 

Whether the required temperature exceeds the temperature setting 
range? 

/

 Temperature setting range: 16°C to 30°C

• 

Whether the unit is turned on or turned off just now? 

/

 There's flowing 

sound of refrigerant inside the air conditioner, which is the normal 
phenomenon.

Error codes

It is possible for error codes to appear in the display. If they do, take the 
appropriate action as shown below.

F1, F2, F4, F0:

Please contact qualified professionals for service.

E8, H3
1. 

Check if the unit is under high-temperature and high-humidity 
environment; if ambient temperature is too high, power off the unit 
and then energize it for operation after the ambient temperature drops 
to 35°C below.

2. 

Check if the evaporator and condenser are blocked by some objects; 
if yes, take away the objects, power off the unit and then energize it 
for operation.

3. 

If the malfunction still occur, please contact service center.

H8
1. 

Drain the water inside chassis.

2. 

If "H8" still exist, please contact the dealer to maintain the unit.

WARNING!

• 

If any of the phenomenon listed below occur, turn off the air conditioner 
and disconnect the power immediately, and then contact the dealer 
immediately.

 

ū

Power cord is overheating or damaged

 

ū

Abnormal sound during operation

 

ū

Odors

 

ū

Water leakage

• 

Do not repair or refit the air conditioner by yourself.

• 

If operate the air conditioner under abnormal condition, it may cause 
malfunction, electric shock or fire hazard.

Installation Precautions

WARNING!

• 

Observe all governing codes and ordinances.

• 

Do not use damaged or non-standard power cord.

• 

Be caution during installation and maintenance. Prohibit incorrect 
operation to prevent electric shock, casualty and other accidents.

Selection of installation location

Basic requirement

Installing the unit in the following places may cause malfunction. If it is 
unavoidable, please consult your dealer for advice.

1. 

Locations with high temperature heat sources, vapors, flammable or 
explosive gas, or volatile objects spread in the air.

2. 

Anywhere which has high-frequency devices installed (such as welding 
machine, medical equipment).

3. 

Near to a coastal area.

4. 

Anywhere which has oil or fumes in the air.

5. 

Near to sulfureted gas.

6. 

Other places with special circumstances.

7. 

Do not install on unstable or motive base structure (such as truck) or in 
a corrosive environment (such as chemical factory).

Requirement of air conditioner
1. 

Air inlet should be far away from obstacles and do not put any objects 
near to the air outlet. Otherwise, it will affect the performance of heat 
discharge pipe.

2. 

Select a location where the noise and outflow air emitted by the unit 
will not affect your local neighborhood.

3. 

Please try your best to keep far away from fluorescent lamps.

4. 

Do not install this appliance in a laundry room.

5. 

Do not install near stairs or steps.

Requirements for electric connection

Safety precaution

1. 

You must follow the electric safety regulations when installing the unit.

2. 

Follow your local safety regulations and ensure that the correct 
electrical supply is used.

3. 

If the supply cord is damaged, it must be replaced by the manufacturer, 
its service agent or similarly qualified persons in order to avoid a 
hazard.

4. 

Properly connect the live wire, neutral wire and grounding wire of 
power socket.

5. 

Be sure to turn off the power supply before proceeding any work 
related to electricity and safety.

6. 

Do not connect the power before finishing installation.

7. 

The air conditioner is a class 1 electric appliance and must be correctly 
grounded. Please make sure it is always grounded effectively, 
otherwise it may cause electric shock.

8. 

The yellow-green wire or green wire in air conditioner is grounding 
wire, which can't be used for other purposes.

9. 

The grounding resistance should comply with your local electrical 
safety regulations.

10. 

The appliance shall be installed in accordance with your countries 
wiring regulations.

11. 

To be in compliance with IEC 61000-3-11, impedance value of power-
supply system connected to product must be less than or equal to the 
allowable maximum value of |Zsys| in the following sheet:

models

max |Zsys| unit:ohm

UL-C10EA-W
UL-C12EA-W
UL-Y12EA-W
UL-C10UA-W

0.13

Содержание UL-C10UA-W

Страница 1: ...Product images are for illustration purposes only Actual product may vary EN UL C10UA W Portable air conditioner User manual ...

Страница 2: ......

Страница 3: ...OOL DRY LOCK AUTO H OPER 1 2 4 5 3 6 7 4 T OFF COOL DRY LOCK AUTO H OPER 1 6 7 2 3 4 8 9 10 11 5 14 12 13 5 5 6 7 8 9 11 10 12 2 1 2 4 3 1 1 2 3 6 8 9 10 11 14 13 12 7 4 5 3 only for model UL Y12EA W Images are for guidance only ...

Страница 4: ...2 FAN ON OFF MODE SLEEP SWING TIMER SWING T ON T OFF COOL AUTO DRY FAN HEAT SLEEP LOCK SPEED H AUTO OPER 1 2 3 4 5 6 7 9 10 8 2 2 2 6 Images are for guidance only ...

Страница 5: ...er than 11m The appliance is not to be stored in a room with continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater The appliance shall be stored in a well ventilated area where the room size corresponds to the room area as specified for operation The appliance shall be stored so as to prevent mechanical damage from occurring Duct...

Страница 6: ...reas Allow a gap of at least 30 cm around the appliance and ensure floor surface is smooth and flat Do not operate the air conditioner at humid environment Keep the air inlet and outlet clean and unobstructed During operation close doors and windows to improve cooling effect Locate the appliance on a smooth and flat surface to avoid excessive noise and vibration This air conditioner is equipped wi...

Страница 7: ...6 Air inlet 7 Middle drainage port 8 Power cord 9 Power cord hooks 10 Plug storage space 11 Bottom drainage port 12 Castors NOTICE Some installation accessories can t be discarded Control Panel Refer to the pictures 3 on page 1 1 Fan speed indicator 2 Fan button 3 Swing button 4 Swing indicator 5 button 6 Display panel 7 Timer indicator 8 Timer button 9 Mode button 10 Cool mode indicator 11 Dry mo...

Страница 8: ... MODE 3 4 FAN 5 SWING 6 SLEEP 7 TIMER Remote control display Refer to the pictures 5 on page 1 1 AUTO Auto mode 2 COOL Cool mode 3 DRY Dry mode 4 FAN Fan mode 5 HEAT Heat mode Cool and Heat models only 6 T ON Timer on 7 T OFF Timer off 8 SWING Swing operation 9 SLEEP Sleep operation 10 LOCK Lock 11 SPEED Set fan speed 12 Set temperature 13 Set time 14 Send signal Remote control functions NOTE ū Th...

Страница 9: ...al between two motions can t exceed 5 seconds otherwise the remote control will exit setting status Functions by Combination Buttons Child lock function Press and buttons simultaneously can turn on or turn off child lock function When child lock function is started up child lock indicator on remote controller is ON If you operate the remote control remote control won t send signal This function wo...

Страница 10: ... method Troubleshooting Before calling for service please review the troubleshooting list below since the problem may not be a main unit malfunction Air conditioner can t operate Cause Action Power failure Wait after power recovery Is plug loose Reinsert the plug Whether the air switch is tripped off or fuse is burnt Ask professional person to replace air switch or fuse Is there malfunction for th...

Страница 11: ...intenance Prohibit incorrect operation to prevent electric shock casualty and other accidents Selection of installation location Basic requirement Installing the unit in the following places may cause malfunction If it is unavoidable please consult your dealer for advice 1 Locations with high temperature heat sources vapors flammable or explosive gas or volatile objects spread in the air 2 Anywher...

Страница 12: ...rom the middle drainage port NOTE ū Water can be automatically emptied into a floor drain by attaching 13 mm inner diameter hose not included 1 Remove the continuous drain cap by turning it counter clockwise then remove the rubber stopper from the spout 2 Screw the drain connector to included in the package the spout by turning clockwise 3 Insert a 13 mm inner diameter hose not included onto drain...

Страница 13: ...P2 DISP1 AP2 M3 PE PE YEGN DISP1 PE PE M2 OFAN YEGN MOTOR DOWN FAN C3 C2 RD UP FAN MOTOR BN M1 YEGN FAN AP3 AP1 MAIN BOARD COMP CAP CAP RD BN CAP HIGH WP RD RD SA SWING M4 STEPPING MOTOR SENSOR TUBE TEMP T SENSOR ROOM TEMP SENSOR UL CY12EA W R M OUTTUBE RT3 BOARD DISPLAY REC RECEIVER BOARD SWITCH WATER LEVEL RT2 RT1 OUTTUBE TEMP SENSOR WATER MOTOR POWER L BN BK N YEGN GN BU WH BU N1 S COMP C YE C1...

Страница 14: ...s and signs that are illegible shall be corrected Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded Checks to electrical devices R...

Страница 15: ...ssential that the technician is completely familiar with the equipment and all its detail It is recommended good practice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to reuse of reclaimed refrigerant It is essential that electrical power is available before the task is commenced a Bec...

Страница 16: ...upply 220 240V AC 50Hz Energy Efficiency Class Cooling A Heating N A Running Power Consumption Cooling W 935 Heating W N A Standby Power Consumption W 0 5 Cooling Capacity W 2900 Heating Capacity W N A Noise Level dB A Fan speed High Medium Low 65 64 62 Air Flow High Medium Low m h 385 355 325 Operating Temperature Range C 16 30 Room Size m 13 19 Size W x D x H in mm 393 x 425 x 804 Weight kg 32 5...

Страница 17: ...EN ...

Страница 18: ...16 ...

Страница 19: ......

Страница 20: ...www sharpconsumer eu Sharp Consumer Electronics Poland sp z o o Ostaszewo 57B 87 148 Łysomice Poland Made in China SDA MAN 0197 ...

Отзывы: