 The cable

 from the appliance is equipped with 

3-wire.
IMPORTANT: Use the 3-wire cable from Home Power Supply 

where local codes permit a 3-wire connection.
Use the 4-wire cable from Home Power Supply where local codes 

do not allow grounding through neutral.
Connecting to a 3-wire power OR 4-wire power supply cable 

electrical system
1.  Disconnect the power supply.
2.  In the circuit breaker, fuse box, or junction box, connect appliance 

and power supply cable wires as shown below (3-wire, Figure 1; 

4-wire, Figure 2).

3.  Circuit breaker fuse rating must be above 40 A, and wire should 

be 2/8 or 3/8 copper.

4.  Minimum acceptable size of conductors should be no less than 

10AWG, copper only, and no less than 167°F.

5.  A wire-binding screw or stud used in the wire terminal should 

be 10 or larger.

 

•  The electrical power to the cooktop must be shut off while line 

connections are being made. Failure to do so could result in 

serious injury or death.

•  An extension cord must not be used with this appliance. Such 

use may result in a fire, electrical shock or other personal injury.

Cable from Power Supply

3-Wire Cable from Home Power Supply

Cable from Appliance

Red Wire

Red Wire

Green Wire

(Grounding)

Black Wire

Junction Box

Figure 1

Cable from Power Supply

4-Wire Cable from Home Power Supply

Cable from Appliance

Red Wire

Red Wire

Green Wire

(Grounding)

White Wire

Black Wire

Junction Box

Figure 2

 

The cooktop conduit wiring is approved for cop-

per wire connection only, if you have aluminum house wiring, use 

only special connectors which are approved for joining copper and 

aluminum wires conform with local codes and ordinances. Follow the 

electrical connector manufacturer’s recommended procedure closely.
IMPORTANT - Save for the local electrical inspector's use.

Содержание SDH3042DB

Страница 1: ...are shown in Figures 3 7 must be used Given dimensions provide minimum clearance Contact surface must be solid and level Check location where the cooktop will be installed for proper electrical supply Approximate location of junction box min 12 304 8mm below the cooktop See Figure 4 Your cooktop can be installed into a countertop by itself or above a gas or electric wall oven All electric cooktops...

Страница 2: ... or larger The electrical power to the cooktop must be shut off while line connections are being made Failure to do so could result in serious injury or death An extension cord must not be used with this appliance Such use may result in a fire electrical shock or other personal injury Cable from Power Supply 3 Wire Cable from Home Power Supply Cable from Appliance Red Wire Red Wire Green Wire Groun...

Страница 3: ... COOKTOP AND CUTOUT DIMENSIONS See Figure 3 COOKTOP CUTOUT OPENING DIMENSIONS See Figure 4 I A D B E C H G F J 30 76 2 cm min for cabinet Do not obstruct these areas A B D E G F C H I Approximate location of junction box min 12 304 8 mm below cooktop Countertop Do not remove spacer Spacer Graphic Profile 2 1 2 63 5 mm OVEN CAUTION Note do not put a divider between the oven and cooktop It is very i...

Страница 4: ... 914 mm B 13 330 mm C 30 762 mm min to unprocted wood D 18 457 mm E 35 5 8 899 mm F 19 7 8 505 mm G 4 1 2 min 114 mm H Minimum 2 51 mm I Minimum 2 51 mm Figure 7 Figure 8 COOKTOP AND CUTOUT DIMENSIONS See Figure 7 COOKTOP CUTOUT OPENING DIMENSIONS See Figure 8 I A D B E C H G F J 30 76 2 cm min for cabinet Do not obstruct these areas A B D E G F C H I Approximate location of junction box min 12 30...

Страница 5: ...igned to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation Please note that cha...

Страница 6: ...NOTES ...

Страница 7: ...NOTES ...

Страница 8: ...SHARP ELECTRONICS CORPORATION 100 Paragon Drive Montvale New Jersey 07645 USA SHARP ELECTRONICS OF CANADA LTD 335 Britannia Road East Mississauga Ontario L4Z 1W9 Canada ...

Отзывы: