background image

- 3 -

Ver. 6.0U _ May 31, 2011

Installation Manual for PV Modules

For grounding, each PV module has a hole in the frame for either a bolt, 

nut and washer, a ground lug fastened by bolt or screw, or an appropriate 

screw (hardware not provided). Installation for wiring and grounding 

method shall be in accordance with national, regional and local codes, 

laws, standard, and the relevant instructions below. In a connection of this 

type, the hardware (such as a star washer) must score the frame surface 

to make positive electrical contact with the frame. The ground wire must 

not be smaller than No.12 AWG.
The National Electrical Code (NEC) 690.33 requires that connectors are 

installed in a readily accessible location, circuits operating at over 30 

volts, shall require a tool to open. PV module’s connectors comply with 

the NEC corresponding section.
Grounding
(1) Grounding Using Existing Ground Hole (Figure 2, GBL-4DBT)

1.  Place Grounding lug (GBL-4DBT, Ilsco corp, E34440) onto the frame, 

making sure that the #8-32 or #10-32 ground bolt (Material; stainless 

steel) straddles the grounding hole.

2.  Thread the lock nut (Material; stainless steel) and tooth washer onto 

the end of the bolt, tighten the nut. Recommended torque is between 

2.0 and 2.2 Nm.

3.  Insert the grounding wire into the lug. The grounding conductor wire 

should be sized according to national, regional and local codes, laws 

and standards.

4.  Fix the grounding wire by tightening the wire binding screw. This will 

terminate the wire.

Please contact ”Ilsco corp.” about detail information of “GBL-4DBT”.

(2) Grounding Using Existing Ground Hole (Figure 3, 1954381-2)  
The grounding clip (SolKlip grounding Clip Assemblies 1954381-2, 

Tyco electronics corp., E69905) assembly consists of a slider, base and 

#8-32 screw and hex nut (screw and hex nut are parts in component of 

1954381-2).

1.  Place the grounding onto the frame, making sure that the screw 

straddles the grounding hole.

2.  Thread the hex nut onto the end of the screw, tighten the nut. 

Recommended torque is between 2.0 and 2.2 Nm.

3.  Insert the grounding wire into the wire slot. Press down on both ends 

of the wire (the wire slot will cause the wire to form a slight curve). 

The grounding wire should be sized according to local, regional and 

national codes and standards. Note that the TYCO SolKlip 1954381-2 

only accepts wire sizes 10 -12 AWG.

4.  Manually, or using channel lock pliers, push the slider over the base 

until it covers the base. This will terminate the wire.

Please contact “Tyco electronics corp.” about detail information of 

“1954381-2”  

A-6. MAINTENANCE

SHARP PV modules are designed for long life and require very little 

maintenance. If the angle of the PV module is 5 degrees or more, normal 

rainfall is usually sufficient to keep the module glass surface clean under 

most weather conditions. Do not touch the glass since finger prints or 

stains will easily mark the glass. If dirt build-up becomes excessive, clean 

the glass surface with water only. If cleaning the back of the module is 

required, take utmost care not to damage the back side materials. In 

order to ensure proper operation of the system, please check all wiring 

connections and the condition of the wire insulation periodically.

SERIES WIRING (VOLTAGE ADDITIVE)

PARALLEL WIRING (CURRENT ADDITIVE)

Figure 1

Figure 1

Wire Binding Screw

Figure 2 (Ilsco, GBL-4DBT)

Figure 3 (Tyco Electronics Corp. 1954381-2)

Содержание NU-Q240F2

Страница 1: ...ect PV modules directly to motor loads Variation in PV module output power as a function of solar irradiance may damage directly connected loads For example 1 In the case of a brushless motor the lock function may become active and the motor may be damaged 2 In the case of a brush type motor the coil may be damaged GENERAL SAFETY 1 Wiring and grounding method of the frame of arrays shall comply wi...

Страница 2: ...g or in a raceway to prevent movement of the interconnect cable over time Cable support should be done in a way to avoid the connector from scratching or impacting the back sheet of the module 11 Do not touch the terminal box and the end of the interconnect cables connectors with bare hands during installation or under sunlight regardless of whether the PV module is connected to or disconnected fr...

Страница 3: ...e Figure 3 1954381 2 The grounding clip SolKlip grounding Clip Assemblies 1954381 2 Tyco electronics corp E69905 assembly consists of a slider base and 8 32 screw and hex nut screw and hex nut are parts in component of 1954381 2 1 Place the grounding onto the frame making sure that the screw straddles the grounding hole 2 Thread the hex nut onto the end of the screw tighten the nut Recommended tor...

Страница 4: ...surface Mounting Using Frame Bolt Holes Figures 6 7 The modules may be fastened to a support using the bolt holes in the bottom of the frame at location C as shown in Figure 7 back view of the module and Figure 6 mounting detail The module should be fastened with four 4 M8 5 16 bolts Recommended torque value is 12 5 Nm For your reference please use the washer specified as below for the minimum req...

Страница 5: ...required dimensions Clamp Thickness Minimum mm Clamp Width Minimum mm Catch Width Minimum mm Support Width Minimum mm Option A 3 3 mm 38 mm 5 mm 10 mm Option B 3 0 mm 43 6 mm 5 mm 10 mm C C C C Figure 6 Figure 7 5 9 150 mm e 16 1 410 mm 5 9 150 mm s 16 1 410 mm Figure 8 Figure 9 ...

Страница 6: ... H240Q2 ND Q240Q2 ND H235Q2 ND Q235Q2 ND H230Q2 ND Q230Q2 Maximum Power Pmax 245 0 W 240 0 W 235 0 W 230 0 W Open Circuit Voltage Voc 37 6 V 37 5 V 37 2 V 37 1 V Short Circuit Current Isc 8 63 A 8 61 A 8 59 A 8 48 A Voltage at maximum power Vpmax 30 4 V 30 2 V 30 1 V 30 0 V Current at maximum power Ipmax 8 06 A 7 95 A 7 81 A 7 67 A Maximum System Voltage 600 V 600 V 600 V 600 V Minimum Blocking di...

Страница 7: ...output This warranty is transferable when product remains installed in original location at the time of product warranty registration This warranty does not apply to any alteration of the appearance of the Product that does not affect the performance or functionality of the Product nor to the additional excluded item s set forth below nor to any Product in Sharp s sole discretion the exterior of w...

Страница 8: ...ction with the Product if any shall not exceed the purchase price paid to Sharp for the Product or service which gave rise to the claim under the Limited Warranty The repair replacement of the Product or the supply of additional Product does not cause the beginning of new warranty terms nor shall the original warranty terms of this Limited Warranty be extended Any replaced product shall become Sha...

Отзывы: