E149703 V.1.11
QS - 5
Shark® 200 Meter Quickstart
Example CT Settings:
200/5 Amps: set the Ct-n value as 200, Ct-S value as 1.
800/5Amps: set the Ct-n value as 800, Ct-S value as 1.
2000/5 Amps: set the Ct-n value as 2000, Ct-S value as 1
10,000/5 Amps: set the Ct-n value as 1000, Ct-S value as 10.
Example PT Settings:
14400/120 Volts: set the Pt-n value as 1440, Pt-d value as 120, Pt-S value as 10.
138000/69 Volts: set the Pt-n value as 1380, Pt-d value as 69, Pt-S value as 100.
345000/115 Volts: set the Pt-n value as 3450, Pt-d value as 115, Pt-S value as 100.
345000/69 Volts: set the Pt-n value as 0345, Pt-d value as 69, Pt-S value as 1000.
For additional programming instructions for the faceplate buttons, see Chapter 6 in the
Shark® 200/
200T Meter Installation and Operation Manual
.
Connect to the Meter through the
RS485 Port:
The Shark® 200 meter has a stan-
dard RS485 port that makes connec-
tion between the meter and a laptop
PC very simple.The Shark
®
200
meter’s RS485 port uses standard 2-
wire, half duplex architecture.
Factory Initial Default Settings:
When the Shark
®
200 is powered up, for 10 seconds you can
connect to the meter using the Factory Default Settings (even if the Device Profile has been changed).
After 10 seconds, the Device Profile reverts to the actual Device Profile in use. This is one way you can
always connect to the meter. The Factory Initial Default Settings are:
Device Address:1
Baud Rate:57600
Protocol:Modbus RTU