PTU15

 

Calibration

The PTU15 calibration can be done in two different ways:

a) By means the P1 and P2 push-buttons.
b) With PC or PLC soft. communication with RS485 port.

a) By means the P1 and P2 push-buttons

To calibrate by-means 2 push-buttons P1 and P2 (see
figure), needs to put the “PTU15”  respectively at the
distance refers to 0% and 100% level, in order to
memorise the relevant distance electronically.
In the condition of normal working the PTU15 shows led

flashing (when echo is received).

To calibrate 4mA

 needs to put the PTU15 at the distance

at which you want 4mA output current. Wait till the led is
flashing than: press simultaneously P1 and P2, release
them and verify that led will stay fix lightened.
Press two times P1, release it and wait until led is flashing
again before move the sensor. The distance has been
memorised and associated to 4mA output.

To calibrate 20mA

 needs to put the PTU15 at the distance

at which you want 20mA output. Wait till the led is flashing
than: press simultaneously P1 and P2, release them and
verify that led will be fix lightened.
Press two times P2, release it and wait until led is flashing
again before move the sensor. The distance has been
memorised and associated to 20mA output.

b) With PC or PLC soft. communication with RS485 port

Refers to the “SoniSoft” S/W operating manual

Calibrations via SWING RS485 connection

Refers to the “SWING” operating manual

fig.8

fig.9

fig.10

fig.11

Содержание PTU15

Страница 1: ...applications TECHNICAL DATA Enclosure material PP Mechanical installation 1 BSP on request with PP DN150 PN6 flange screwed Mechanical protection IP68 Electrical connection n 1 output cables L 3m or IP68 male connector with linking cable Working temperature 25 75 C Pressure from 0 5 to 1 5bar absolute Power supply 24Vdc Power consumption 1W Analog output 4 20mA max load 750 ohm Serial port RS485 M...

Страница 2: ... connected to the negative output current A special J box with P1 and P2 calibration push buttons built in is available on request The picture below shows the connectors and the push buttons for the 4 20mA version calibration Available a RS485 serial port to communicate to PC or PLC On request the SoniSoft S W communication for PC and the RS485 RS232 conversion module are available Analog output v...

Страница 3: ...han press simultaneously P1 and P2 release them and verify that led will stay fix lightened Press two times P1 release it and wait until led is flashing again before move the sensor The distance has been memorised and associated to 4mA output To calibrate 20mA needs to put the PTU15 at the distance at which you want 20mA output Wait till the led is flashing than press simultaneously P1 and P2 rele...

Страница 4: ...ade in conformity to the SGM LEKTRA procedu re Quality Control Manager Production and ceck date documentation subject to technical change with no prior warning 5 1 U T P e d o C n o i s r e V A m 3 e l b a c g n i k n i l h t i w 5 8 4 S R t i n u g n i w S o t d e t c e n n o c e b o t d e n g i s e D B m 3 e l b a c g n i k n i l h t i w r e t t i m s n a r t t u p t u o 5 8 4 S R A m 0 2 4 C m ...

Отзывы: