Plastic Radial Roof Mounted Fans

              SDR 63 Sizes 355-710

9. Inspection / Maintenance

The reliability and service life of the fans depend also on
correct inspection and maintenance. Fans in continuous
and trouble-free operation must be checked every three
months as follows:

Visual check for cracks and/or fractures in the fan enclo-
sure caused by vibration.

Visual inspection of the impeller for wear and/or caked-
ondeposits caused by abrasive media.

Inspection of the duct connections for tightness.

The inspection of the ventilation orifices and the condensate
drain bore as in Item 8, para. 3, should be carried out at fairly
short intervals to be determined by the user.

SGL ACOTEC Centrifugal Roof Mounted Fans are
maintenance-free, the bearings of the motors are generally
permanently lubricated for their nominal service life.

10. Servicing / Conversion

Fans are machines which should be provided with preventive
and condition-oriented servicing to avoid breakdowns and
lengthy downtimes as far as possible.

The servicing operations must be carried out with reference to
the safety instructions as in Item 3 and the applicable
operational protection at work instructions, and must only
be carried out by authorized and qualified persons who
are familiar with this operating manual.

Below, only work is described which must be carried out
within the scope of the replacement of original parts
(e.g. impeller) or when converting the fan.

Important!

Before starting work, stop the fan, switch off the main
switch and secure against unintentional or unauthorized
switching on again!

10.1 Removal / installation of the impeller

Removal becomes necessary in case of wear, fracture or
imbalance of the impeller as well as during the conversion
of a fan size to another one (e.g. SDR 63-355 to SDR 630-
400 or vice versa). Specified component numbering acc.
to fig. 1.

Disconnect the supply (11) at the terminal box (12)

Remove the nuts of the six fixing screws (21) and lift off
the fan. Air intake and liner (4, 5) remain in the assembled
condition on the roof mount (14).

Turn the fan and place with the discharge opening
downwards.

After removing the plug and unscrewing the fixing
screw, the impeller (3) can extracted from the motor
shaft.

Assembly is in the reverse order.

10.2 Changing impeller and liner

This becomes necessary when converting the fan to a
different size, e.g. SDR 63-355 to 400, SDR 63-450 to 500
or vice versa.

Removal of the impeller as in Item 10.1

Remove the suction-side duct connection from the
liner (5) and remove the air intake with liner (4, 5) from
the roof mount (14).

Assemble the replaced components in reverse order.

Содержание SDR 63

Страница 1: ...OPERATING INSTRUCTIONS PLASTIC CENTRIFUGAL ROOF MOUNTED FANS SDR 63 3 SIZES 355 710 ...

Страница 2: ...tating impeller and by deflection downstream of the horizontal impeller outlet again passed axially around the enclosed motor and to the outlet branch SDR fans of sizes 355 710 are of welded construction and consist of the following sub assemblies enclosure motor support impeller air intake and tubular liner Motor support as well as the top and bottom section of the enclosure are welded together F...

Страница 3: ...ion hose 9 Motor 10 Motor lead 11 Fan supply cable 12 Terminal box 13 Moisture proof union 14 Roof mount 15 Roof covering 16 Roof penetration 17 Roof liner 18 Hitching point 19 Fixing screw motor 20 Fixing screw motor flange 21 Fixing screw fan 7 9 18 2 19 20 3 1 4 21 5 17 15 16 14 13 6 11 8 10 12 Issued PA S Operating manual No 28 95 103 Valid from Serial No 29956 Date 01 03 2001 Plastic Radial R...

Страница 4: ...perations must only be carried out with the fan at rest and the power supply shut off The removal of information instruction and prohibition plates from the product is not permissible In all cases the fan must also be operated in accordance with all local safety and accident prevention regulations 4 Transport and storage The fans must be transported carefully and safely to prevent damage through e...

Страница 5: ... of the cooling air exceeds 40o C a performance reduction of the motors must be taken into account Values are shown in the catalogues of the motor manufacturers 8 Commissioning Commissioning and operation of the fans must only be carried out by appropriately trained persons who are familiar with the applicable operating and safety regulations After installation of the fan and connection of the suc...

Страница 6: ...structions and must only be carried out by authorized and qualified persons who are familiar with this operating manual Below only work is described which must be carried out within the scope of the replacement of original parts e g impeller or when converting the fan Important Before starting work stop the fan switch off the main switch and secure against unintentional or unauthorized switching o...

Страница 7: ... in the motor support 2 the motor lead 10 must be passed through the lower fan hose 8 All unused motor fixing bores in the support flange must be sealed with PE plugs GPN 300 V7 V10 V041 Note For conversion of the fans only original components must be used The selection of the drive motors must be made according to the respective characteristic diagrams Consultation with the fan manufacturer is re...

Страница 8: ... 355 Characteristics Fan speed rpm Motor output kW Circumferential velocity m s Total pressure differential pt Pa Noise level dB Fan speed rpm Motor output kW Circumferential velocity m s Total pressure differential pt Pa Noise level dB ...

Страница 9: ... 500 Characteristics Fan speed rpm Motor output kW Circumferential velocity m s Total pressure differential pt Pa Noise level dB Fan speed rpm Motor output kW Circumferential velocity m s Total pressure differential pt Pa Noise level dB ...

Страница 10: ...3 560 Characteristics Fan speed rpm Motor output kW Circumferential velocity m s Total pressure differential pt Pa Noise level dB Fan speed rpm Motor output kW Circumferential velocity m s Total pressure differential pt Pa Noise level dB ...

Страница 11: ...11 SDR 63 710 Characteristics Fan speed rpm Motor output kW Circumferential velocity m s Total pressure differential pt Pa Noise level dB ...

Страница 12: ...CARBON GROUP companies This information is based on our present state of knowledge and is intended to provide general notes on our products and their uses It should therefore not be construed as guaranteeing specific properties of the products described or their suitability for a particular application Any existing industrial property rights must be observed The quality of our products is guarante...

Отзывы: