1. General notes

This operating manual is valid for all plastic centrifugal roof
fans of series

SDR 63 Sizes 355 - 710

manufactured and supplied by SGL ACOTEC GmbH in
56427 Siershahn, Berggarten 1, Germany.

The instructions must be handed to the user, who has to
inform the people responsible for operation, servicing and
repair. No liability is accepted for damage resulting from
non-observance of the instructions.

The fans supplied by SGL ACOTEC are designed with
reference to the order on the basis of flow rate, total
pressure differential, medium, operating temperature and
installation site. The actual parameters are shown on the
machine card or rating plate.

The product supplied must only be used for the application
specified in the contract and within the scope of the
conversion possibilities listed in this operating manual. Any
other use is regarded as not in accordance with the
intended purpose. SGL ACOTEC do not accept liability for
any damage arising from such a use.

2. Construction and operating principle

SGL ACOTEC Centrifugal Roof Mounted Fans of Series
SDR 63 have been designed as vertically discharging,
direct-drive feed appliances for corrosive gases and
vapours. The medium handled is drawn in axially by the
rotating impeller and by deflection downstream of the
horizontal impeller outlet again passed axially around the
enclosed motor and to the outlet branch.

SDR fans of sizes 355 - 710 are of welded construction
and consist of the following sub-assemblies: enclosure,
motor support, impeller, air intake and tubular liner. Motor
support as well as the top and bottom section of the
enclosure are welded together. For Sizes 355 and 400, 450
and 500 as well as 560 and 630, identical enclosures are
used respectively. This makes it possible to convert the
fans also after delivery and installation by changing the
impeller and air intake to the other respective size.

The motor support is designed for the installation of six
motor sizes (71 - 132) in the design B5. The motors are
screened against the medium; cooling air supply is via
ventilation hoses (fig. 1). The impellers used have eight
backward curved blades and are balanced electrodyna-
mically in two planes. Minimum balancing quality Q 6.3 to
ISO 1940.

CONTENTS

1. General notes

2

2. Construction and operating principle

2-  3

3. Realization of the safety requirements

4

4. Transport/Storage

4

5. Installation

4

6. Drive

5

7. Installation of the motors

5

8. Commissioning

5

9. Inspection/Maintenance

6

10. Servicing/Conversion

6

Appendix: Characteristics diagrams

8-11

Issued: PA S

Operating manual No. 28.95.103

Valid from: Serial No. 29956

Date: 01.03.2001

Plastic Radial Roof Mounted Fans

              SDR 63 Sizes 355-710

Содержание SDR 63

Страница 1: ...OPERATING INSTRUCTIONS PLASTIC CENTRIFUGAL ROOF MOUNTED FANS SDR 63 3 SIZES 355 710 ...

Страница 2: ...tating impeller and by deflection downstream of the horizontal impeller outlet again passed axially around the enclosed motor and to the outlet branch SDR fans of sizes 355 710 are of welded construction and consist of the following sub assemblies enclosure motor support impeller air intake and tubular liner Motor support as well as the top and bottom section of the enclosure are welded together F...

Страница 3: ...ion hose 9 Motor 10 Motor lead 11 Fan supply cable 12 Terminal box 13 Moisture proof union 14 Roof mount 15 Roof covering 16 Roof penetration 17 Roof liner 18 Hitching point 19 Fixing screw motor 20 Fixing screw motor flange 21 Fixing screw fan 7 9 18 2 19 20 3 1 4 21 5 17 15 16 14 13 6 11 8 10 12 Issued PA S Operating manual No 28 95 103 Valid from Serial No 29956 Date 01 03 2001 Plastic Radial R...

Страница 4: ...perations must only be carried out with the fan at rest and the power supply shut off The removal of information instruction and prohibition plates from the product is not permissible In all cases the fan must also be operated in accordance with all local safety and accident prevention regulations 4 Transport and storage The fans must be transported carefully and safely to prevent damage through e...

Страница 5: ... of the cooling air exceeds 40o C a performance reduction of the motors must be taken into account Values are shown in the catalogues of the motor manufacturers 8 Commissioning Commissioning and operation of the fans must only be carried out by appropriately trained persons who are familiar with the applicable operating and safety regulations After installation of the fan and connection of the suc...

Страница 6: ...structions and must only be carried out by authorized and qualified persons who are familiar with this operating manual Below only work is described which must be carried out within the scope of the replacement of original parts e g impeller or when converting the fan Important Before starting work stop the fan switch off the main switch and secure against unintentional or unauthorized switching o...

Страница 7: ... in the motor support 2 the motor lead 10 must be passed through the lower fan hose 8 All unused motor fixing bores in the support flange must be sealed with PE plugs GPN 300 V7 V10 V041 Note For conversion of the fans only original components must be used The selection of the drive motors must be made according to the respective characteristic diagrams Consultation with the fan manufacturer is re...

Страница 8: ... 355 Characteristics Fan speed rpm Motor output kW Circumferential velocity m s Total pressure differential pt Pa Noise level dB Fan speed rpm Motor output kW Circumferential velocity m s Total pressure differential pt Pa Noise level dB ...

Страница 9: ... 500 Characteristics Fan speed rpm Motor output kW Circumferential velocity m s Total pressure differential pt Pa Noise level dB Fan speed rpm Motor output kW Circumferential velocity m s Total pressure differential pt Pa Noise level dB ...

Страница 10: ...3 560 Characteristics Fan speed rpm Motor output kW Circumferential velocity m s Total pressure differential pt Pa Noise level dB Fan speed rpm Motor output kW Circumferential velocity m s Total pressure differential pt Pa Noise level dB ...

Страница 11: ...11 SDR 63 710 Characteristics Fan speed rpm Motor output kW Circumferential velocity m s Total pressure differential pt Pa Noise level dB ...

Страница 12: ...CARBON GROUP companies This information is based on our present state of knowledge and is intended to provide general notes on our products and their uses It should therefore not be construed as guaranteeing specific properties of the products described or their suitability for a particular application Any existing industrial property rights must be observed The quality of our products is guarante...

Отзывы: