SFA SANICUBIC 1 SC Series Скачать руководство пользователя страница 6

6

1.7 Unauthorised modification and spare parts production

Modifications or changes to the machine shall be permissible only after consultation with the 

manufacturer. Original spare parts and accessories authorised by the manufacturer serve to 

ensure safety. The use of other parts may results in the loss of liability for the consequences 

that may occur.

1.8 Impermissible operating modes

The operational safety of the machine supplied is ensured only when used as intended 

according to Section 

2-General aspects

 of the operating instructions. The threshold values 

indicated in the data sheet must by no means be exceeded.

2. GENERAL ASPECTS

2.1 Affiliation

These operating instruction are valid for the sewage lifting units of the SANICUBIC

®

 SC series.

In case of non-observation to the operating instructions - in particular the safety instructions 
- as well as unauthorised modification of the device or the installation of non-original spare 
parts the warranty claims will automatically become void. The manufacturer assumes no lia-
bility for any damage resulting from this!
As any other electrical appliance, this product can also fail due to missing main power or a 
technical defect. If a damage can occur as a result, an emergency power generator, a man-
ual membrane pump, a second system (double system) and/or a mains-independent alarm 
system should be planned according to the application. We as manufacturers will be happy 
to advise you also after the purchase. In case of defects or damages, please get in touch with 
your dealer.

Products in the range :

SANICUBIC

®

 1 SC3.0 T

SANICUBIC

®

 1 SC4.0 T

SANICUBIC

®

 1 SC5.5 T

SANICUBIC

®

 1 SC7.5 T

SANICUBIC

®

 2 SC3.0 T

SANICUBIC

®

 2 SC4.0 T

SANICUBIC

®

 2 SC5.5 T

SANICUBIC

®

 2 SC7.5 T

2.2 Inquiries and purchase orders

Please send your inqueries and orders to your specialist dealer.

2.3 Technical data

Single systems:

Type

Input

Power

P1 [kW]

Nominal

Power

P2 [kW]

Voltage

U [V]

Rated

current

I

MAX

 [A]

Speed

(50 Hz) 

[min

-1

]

Feed

volume

[m

3

/h]

Pumping

head

[m]

Pressure

connection

SANICUBIC

®

 1 SC3.0 T

4.0

3.0

400

6.9

1400

130

10

DN 100

SANICUBIC

®

 1 SC4.0 T

5.5

4.0

400

11.2

1400

140

13

DN 100

SANICUBIC

®

 1 SC5.5 T

6.3

5.5

400

12.1

1400

160

18

DN 100

SANICUBIC

®

 1 SC7.5 T

8.7

7.5

400

16.9

1400

165

22

DN 100

Содержание SANICUBIC 1 SC Series

Страница 1: ...Mode d emploi Stazione di pompaggio acque reflue Istruzioni per l uso Afvalwater Opvoerinstallaties Gebruikshandleiding Equipos elevadores de aguas residuales Manual de instrucciones Unidades elevatórias de águas residuais Manual de instruções SANICUBIC SC SANICUBIC 1 SC SANICUBIC 2 SC IT NL ES PT UK DE FR 9011 10 19 ...

Страница 2: ...English 3 Deutsch 17 Français 31 Italiano 45 Nederlands 59 Español 73 Português 87 ...

Страница 3: ...ce inspection and installation work pg 5 1 7 Unauthorised modification and spare parts production pg 6 1 8 Impermissible operating modes pg 6 2 GENERAL ASPECTS pg 6 2 1 Affiliation pg 6 2 2 Inquiries and purchase orders pg 6 2 3 Technical data pg 6 2 4 Field of application pg 7 2 5 Accessories pg 8 3 TRANSPORT AND INTERMEDIATE WAREHOUSING pg 8 3 1 Transport pg 8 3 2 Intermediate warehousing conser...

Страница 4: ...mer service team or a similarly qualified individual These operating instructions contain basic instructions which have to be observed during set up operation and maintenance For this reason these operating instructions must by all means be read before installation and commissioning by the installation technician as well as by the competent specialist staff user and must be permanently available a...

Страница 5: ...ating instructions the existing national regulations on accident prevention as well as potential in company work operating and safety instructions of the user must be observed 1 5 Safety instructions for user operator If hot or cold machine parts could lead to hazards these parts have to be protected against touch by the user Touch protection for moving parts e g coupling must not be removed from ...

Страница 6: ...ufacturer assumes no lia bility for any damage resulting from this As any other electrical appliance this product can also fail due to missing main power or a technical defect If a damage can occur as a result an emergency power generator a man ual membrane pump a second system double system and or a mains independent alarm system should be planned according to the application We as manufacturers ...

Страница 7: ...quirement m SANICUBIC 2 SC3 0 T 1000 500 DN 150 80 370 1450x950 2 5x1 5 SANICUBIC 2 SC4 0 T 1000 500 DN 150 80 385 1450x950 2 5x1 5 SANICUBIC 2 SC5 5 T 1000 500 DN 150 100 400 1450x950 2 5x1 5 SANICUBIC 1 SC7 5 T 1000 500 DN 150 100 425 1450x950 2 5x1 5 Maximum media temperature 55 C Materials Shaft sealing Motor side Shaft seal Pump side up to 4 kW mechanical seal from 5 5 kW chilled casting seal...

Страница 8: ...r natural gradient flows into the collecting tank of the sewage lifting unit SANICUBIC SC The collecting tank is designed for pressureless operation that is the occurring waste water is buffered without pressure and then conveyed into the sewage channel In the dip tube that is screwed on the upper side of the tank the water rises and keeps compressing the air being in the dip tube so long until th...

Страница 9: ...unit has to be secured by means of suitable attachment equipment on site against twisting and buoyant floating 5 2 2 Inlet The inlet line is connected to the flange DN 150 It must always be installed on a downhill incline Uphill sections in the inlet are not permitted 5 2 3 Discharge line Installation of a non return valve in the discharge line of the lifting unit must always be installed DIN 19 7...

Страница 10: ...he socket and the pump s direction of rotation checked This is done by briefly setting the manual 0 automatic switch to Manual When the motor comes to a standstill the direction of rotation can be compared with the correct direction of rotation rotation arrow on the top surface at the sight glass If the pump rotates the wrong way round two of the three phases will have to be interchanged All power...

Страница 11: ...e spare parts list must not be loosened because otherwise the mechanical seal is destroyed oil escapes and the warranty will become void If only the motor unit shall be dismounted all 4 screws Item 13 of the spare parts list have to be loosened If the complete pump shall be dismounted from the tank all 4 nuts item 23 of the spare parts list must be loosened Malfunction Cause Troubleshooting 1 Moto...

Страница 12: ...omer service Customer service 4 Motor does not switch off Controlling error Pitot tube clogged Customer service department Replacement Customer service department 9 WARRANTY As manufacturer we assume a warranty for this device for 24 months as of purchase date The sales receipt is considered as proof of warranty Within this warranty period we will at our dis cretion either by means of repair or re...

Страница 13: ...13 Appendix A Assembly example ...

Страница 14: ...14 Appendix B Dimensions SANICUBIC 1 SC SANICUBIC 2 SC ...

Страница 15: ...ctional drawing Spare parts list Switchgears Quantity Designation Article No 1 Switchgear ZPS1 3 0 4 0 5 5 kW 256300 1 Switchgear ZPS1 SD 7 5 kW 215402 1 Switchgear ZPS2 3 0 4 0 5 5 kW 255400 1 Switchgear ZPS2 SD 7 5 kW 215403 1 1 Small compressor set 71035 ...

Страница 16: ... screw M 10 x 30 SANICUBIC SC 3 0 and 4 0 ZE1237 8 16 Hexagon screw M 12 x 30 SANICUBIC SC 5 5 and 7 5 ZE1516 15 1 2 Motor unit 3 0 kW with impeller 111103 1 2 Motor unit 4 0 kW with impeller 111104 1 2 Motor unit 5 5 kW with impeller 111107 1 2 Motor unit 7 5 kW with impeller 111108 16 4 8 Hexagon screw M 12 x 25 ZE1130 4 8 Spring washer B 12 ZE1302 17 1 2 Impeller D 200 mm 3 0 kW 120134c 1 2 Imp...

Страница 17: ......

Страница 18: ...ROMANIA SFA SANIFLO S R L 145B Foisorului Street District 3 31177 BUCURESTI Tel 40 787 634 557 info saniflo ro TÜRKIYE SFA SANIHYDRO LTD ŞTİ Mecidiye Cad No 36 B Sevencan Apt 34394 MECIDIYEKOY ISTANBUL Tel 90 212 275 30 88 CHINA SFA 中国 上海市静安区石门二路333弄3号振安广 场恒安大厦27C室 200041 Tel 86 0 21 6218 8969 Fax 86 0 21 6218 8970 BRAZIL SFA Brasil Equipamentos Sanitários Rua Maria Figueiredo 595 CEP 04002 003 Sã...

Отзывы: