background image

20

 

 

 

 
 

Step 1: Close PUMP 1 RUN switch 
Step 2: PUMP 1 RUN indicator light ON 
Step 3: Buzzer not on. 
Step 4: Open the PUMP 1 RUN switch 
Step 5: Indicator light off 
 

 
 

 
Step 1: Close PUMP 1 STOP switch 
Step 2: PUMP 1 STOP indicator light on 
Step 3: Buzzer not on. 
Step 4: Open the PUMP 1 STOP switch 
Step 5: Indicator light off 

 
 
PUMP 2 RUN & STOP 

-To repeat PUMP 1 RUN & STOP test. 
 

 

POWER 1 FAIL 
Step 1: P 24V DC to the ECR input terminal at P4A 
Step 2: POWER 1 FAIL indicator light is blinking for all the panels. 
Step 3: Buzzer sound. 
Step 4: Press the silence button, the POWER 1 FAIL indicator light is steady and buzzer is off 
Step 5: Press the alarm reset button, the buzzer sound again and indicator is blinking again 
Step 6: Repeat Step 4. 
Step 7: Stop 24V DC to the terminal input, the power 1 fail indicator is still on. 
Step 8: Press alarm reset button again, the alarm indicator light off. 
Step 9: Check out signal to other equipment at ECR panel when alarm activated. 
   
*All the other alarm testing has the same testing procedure as POWER 1 FAIL test procedure. 

 

TIME DELAY TEST 

 
LOW OIL LEVEL: 

3 second

   

HYDRAULC LOCK: 

1 second

 

PHASE FAIL: 

2 second

 

FU FAIL: 

1 second

 

*The testing steps are same as POWER 1 FAIL.   
 
Step 1: Provide alarm input signal to the respect alarm input terminal. 
Step 2: Count the time between signal input and alarm activate.   
Step 3: Compare the time between the setting an count. 
Step 4: The time delay setting and count should follow the setting time 
 
 

PUMP 1 RUN 

PUMP 1 STOP 

Содержание AL101S

Страница 1: ...Chapter 1 Operation of AL101S series ECR FWD AFT Description of AL101S series keypad Description of AL101S series lamp Chapter 2 Size of AL101S series ECR FWD AFT Chapter 3 Input Output signal termin...

Страница 2: ...Dip Switch 1 2 Resistor Termination ON OFF switch OFF Switch ON OFF Default 1 Operation Mode Test Mode ON 2 No DC blinking DC blinking Available ON 3 Full Relay output Mode Half relay output Mode ON...

Страница 3: ...switch OFF CAUTION ECR FWD AFT Relay output mode Full Half run independently Switch ON OFF Default 1 Operation Mode Test Mode ON 2 No DC blinking DC blinking Available ON 3 Full Relay output Mode Half...

Страница 4: ...4 AL101S Steering Gear Alarm System Chapter 1 ECR FWD AFT Operation...

Страница 5: ...5 AL101S ECR AL101S FWD AL101S AFT...

Страница 6: ...6 AL101S FWD...

Страница 7: ...7 AL101S AFT...

Страница 8: ...etting Dip Switch 3 setting done ON relay output will be working full mode Meanwhile if setting Dip switch 3 OFF relay output will be working half mode 2 RESET Key This key able to re boot to all lamp...

Страница 9: ...n or deactivation This key check to LAMP itself working If on pressing this key both of activation and deactivation lamp ON at once Then if release this key the deactivation lamp will be OFF 4 DIMMER...

Страница 10: ...ignal 2 second later LAMP activate 4 PUMP LOW OIL LEVEL LAMP Input signal 3 second later LAMP activate 5 DC ON LAMP Depend on input signal LAMP will be activate to RED or GREEN Please see the chapter...

Страница 11: ...11 AL101S Steering Gear Alarm System Chapter 2 ECR FWD AFT Case size...

Страница 12: ...12 Cut hole dimension...

Страница 13: ...13 Fontal case dimension...

Страница 14: ...14 AL101S Steering Gear Alarm System Chapter 3 ECR FWD AFT Input output signal terminal...

Страница 15: ...15 ECR input output signal terminal...

Страница 16: ...16 FWD input output signal terminal...

Страница 17: ...17 AFT input output signal terminal...

Страница 18: ...18 AL101S Steering Gear Alarm System Chapter 4 Test flow...

Страница 19: ...activated AUTOPILOT FAIL Step 1 Close AUTOPILOT FAIL contact at the FWD panel input Step 2 Autopilot fail indicator Red light is blinking for all the panels Step 3 Buzzer sound Step 4 Press the Silen...

Страница 20: ...t button the buzzer sound again and indicator is blinking again Step 6 Repeat Step 4 Step 7 Stop supply 24V DC to the terminal input the power 1 fail indicator is still on Step 8 Press alarm reset but...

Страница 21: ...21 4 6 Testing for signal output to other equipment FWD AFT alarm panel relay Signal output...

Отзывы: