54
5 Maintenance
z
Press and hold the release button on the test set until the con-
centration displayed on the device has reached a stable value.
z
Press the On/Off key to confirm.
5.3.2
LEL range and % vol. range
Tools:
z
Test head HG 4
z
Test set (see Accessories)
Zero point test gas:
Fresh air
Indication accuracy
test gas:
2.20 % vol. CH
4
for 50 % LEL adjustment
100 % vol. CH
4
for 100 % LEL adjustment
Setting the zero point
Tools are not required to set the zero point.
The zero points for the LEL range and the % vol. range are always
set together in one step.
z
Switch on the device.
z
Add fresh air as the test gas.
z
Wait until the value on the LCD no longer flashes.
z
Press the On/Off key to confirm.
Setting the indication accuracy
z
Connect the device to the test set.
To do so, follow the steps indicated in the operating instruc
-
tions for the tester.
z
Place the test head on the device.
z
Press and hold the release button on the test set for
at least
1 minute
. Do not let go of the release button until the concen
-
tration displayed on the device has reached a stable value.
z
Press the On/Off key to confirm.
z
Remove the test head and wait until the zero point has reset
itself.