MOVITRAC
®
31.. PROFIBUS Fieldbus Interface
19
The PROFIBUS-DP
Interface
3
Fig. 14 shows the communication between the automation unit (DP master) and the MOVITRAC
®
31.. frequency inverter via one process data word only. This configuration could be used, for exam-
ple, to control the inverter with control word 1 and status word 1 (see SEW documentation
Field-
bus Unit Profile User Manual).
01165AEN
Fig. 14: Control of the inverter via 1 process data word
3 .1.3
Configuring for 2 Process Data Words (2 PD)
Control of the MOVITRAC
®
31.. inverter using two process data words requires that the Cfg_Data
identifier byte is coded as shown in Fig. 15. This code must be sent to the inverter by the DP mas-
ter when PROFIBUS-DP is started so that the DP master and DP slave can exchange two process
data words.
01168A
Fig. 15: Configuration data example for setting 2 input/output words (2PD)
Fig. 16 shows the communication between the automation unit (DP master) and the MOVITRAC
®
31.. frequency inverter via two process data words. The higher-level control system could use this
configuration, for example, to send the process output data
Control Word 1 and Speed Setpoint
and read in the process input data
Status Word 1 and Speed Actual Value (see SEW documentation
Fieldbus Unit Profile User Manual).
01166AEN
Fig. 16: Control of the inverter via 2 process data words
MO
VI
TR
AC
®
841
E
Q
RUN
BUS
FAULT
PD1
PD1
Feldbus
STEUERMODE
MO
VI
TR
AC
®
841
E
Q
RUN
BUS
FAULT
PD1
PD1
Fieldbus
CONTROL MODE
1
LSB
MSB
= F1
= 241
hex
dez
1
1
1
0
0
0
1
Data length: 2 words
Input/output
Word structure
Consistency over the complete length
Cfg_Data identifier byte
MO
VI
TR
AC
®
841
E
Q
RUN
BUS
FAULT
PD1
PD2
PD1
PD2
Fieldbus
CONTROL MODE