Manual – MOVIFIT® SNI Fieldbus Gateway UFF41B for MOVIGEAR® SNI
33
5
SNI gateway configuration
Startup
Confirm with [OK]. The "SNI gateway settings" window opens again. This means the
configuration has been completed successfully. Click [Next] to continue.
Overview of
process data
The "SNI gateway process data overview" window opens (see following figure).
This window provides an overview of the configuration. The PD start addresses of the
relevant drives are displayed. 1 PD is always assigned to the fieldbus gateway.
Click [Next] to download the configuration.
Example
3 MOVIFIT
®
SNI with a total of 24 MOVIGEAR
®
SNI drives are controlled.
• 20 drives are operated with variable speed. The initiators of 4 of these drives are read
using the GIO12A application option (see MOVGEAR
®
SNI system manual).
• 4 drives are operated with fixed speeds.
This will result in the following process data overview:
• 1 PD for the fieldbus gateway
• 3
×
1 PD for MOVIFIT
®
SNI (without local DO/DI)
• 16
×
2 PD for MOVIGEAR
®
SNI with variable speed
• 4
×
3 PD for MOVIGEAR
®
SNI with variable speed and IOs
• 4
×
1 PD for MOVIGEAR
®
SNI with fixed speed
Result:
One fieldbus gateway is sufficient. The number of process data words used is 52.
12145AEN
0
0
I