General Information

Your Setra transducer has been carefully calibrated before shipment to you and, it should be handled 

with the same care given any precision instrument.  Pressure ranges and dimensions are reported on 

the specification bulletin for the transducer.

Installation

Do not use in ambient conditions corrosive to stainless steel, submerge in liquids, subject to spray 

or drip, or in a high vibration environment.  The 280G Series is slightly sensitive to acceleration in 

the pressure fitting axis, less than 0.05 psi/g typical.  Factory calibrated in the vertical position, with 

pressure port downward, this position often minimizes  potential damage from dripping of pressure 

system piping.

Installation of pressure fitting:

For very high pressure we suggest using a sealant such as Loctite hydraulic sealant.  For other pressure 

ranges, standard sealants such as Teflon pipe tape generally are satisfactory.  For the most sensitive 

pressure ranges, excessive torquing of a metal pressure fitting may cause slight zero shift which may 

be trimmed out using zero adjustment.  Use of plastic fittings often shows no noticeable zero shift.  

The torquing effect does not appreciably affect linearity or sensitivity.  Use the wrench flats on the 

280G when attaching to fittings.

Atmospheric Reference (Gauge pressure units only)

Lower range units are subject to excessive thermal zero shift unless vented to atmosphere.  The 280G 

Series gauge pressure transducers and transmitters are vented to atmosphere at the terminal strip.

Electrical Connections

280G (.08 - 5.08 VDC output)

For 24 VDC Excitation (Nominal)

+ IN 

Connect to 12-30 VDC Power Supply.

+ OUT 

Connect to Control of Pressure Monitor.

COM. 

Connect as Common Return Lead for + IN

 

and + OUT.

CAUTION:

Care must be taken when installing this transducer that the excitation voltage is not applied to the 

output lead by mistake.  Excitation power, or voltage in excess of 30 VDC, inadvertently applied to 

the output lead may damage the electrical circuit.  Shielding or other precautions should also be 

provided to assure that transient voltages in excess of 30 VDC are not applied to the output lead.

Wiring

Current Output (4-20 mA)

 

The circuit is designed to operate as a true two-wire 4 to 20 milliampere pressure transmitter 

and will deliver rated current into any external load between zero and 800 ohms.

Operating Instructions

Model 280G Pressure Transducer and Pressure Transmitter

Three-Wire, Voltage Output—Two Wire, Current Output