Input LEDs (

Fig. 1

):

You can choose between different operating modes, i.e. analog 
control 0-10V, analog control 1-10V, 1-button mode or 2-button 
mode (see 4. Programming). The input LEDs indicate which 
operating mode has been selected.
In case of 

normal operation

, the input LEDs can have the 

following meaning:

LED’s  

 

     Meaning

Upper LED lights 
continuously

Current operating mode: 0 -10 V

Middle LED lights 
continuously

Current operating mode: 1 -10 V

Lower LED lights 
continuously

Current operating mode:
1-button mode

None of the 3 LEDs 
lights.

Current operating mode: 
2-button mode

Troubleshooting

Possible causes if the error indication LED and the load LED blink:
- the lamp is defective
- the load is not connected

Possible causes of dimmer malfunction, no LED indication:
-  no power on the mains
-  there is no control signal
-  thermal protection is activated
-  combination of the above causes.
-  The dimmer is provided with a thermal protection. If the 

temperature rises too high, the light is automatically dimmed 
to ±40%. If the temperature continues to rise, the dimmer is 
switched off. If this happens:

  - check whether the load is not too high. Take into account the 

reactive power of ferromagnetic transformers.

  - check the temperature in the distribution board (max. 35°C). If 

the temperature is too high, provide additional ventilation. 

  - If several modules are installed next to each other,  provide 

min. 1 module distance via adapted blank plates.

The dimmer is automatically switched on again as soon as the 
temperature has dropped suffi ciently.

-  The error indication LED continuously blinks or lights. This 

indicates:

 - overload
  - overvoltage or overcurrent
  - short circuit
  - the load is not dimmable, neither in phase control, nor in 

reverse phase control.

Operation & maintenance

No maintenance.
Contact a qualifi ed electrician in the event of fault or breakdown.

Technical data

Input:
Power supply ......................... 230 V ±10%, 50 Hz
Maximum voltage drop 
over dimmer .......................... -5%
Own consumption ................. ±1W
Input impedance:
 0-10V 

.................................. 33k

 1-10V 

.................................. 22k

Output:
Minimum load ........................ 60W
Maximum load ....................... 750VA resistive, inductive and
  

capacitive(t°<35°C)

Max. output voltage .............. Supply voltage x 0.95 (dissipated 
   

power = max. 1% of the absorbed 

   

power = max. 7W)

Protections ............................ Elektric, thermal protection (105°C) 
   

with automatic rebooth function 

   

(light is reduced to min.  intensity). If 

   

the temperature does not drop, the 

   

load is switched off.

   

-single thermal overload protection 

  

(135°C)

Preformance:
Allowed ambient temperature .. see load table
Max. cover temperature (tc) ... 90°C
Maximum distance to last 
push button ........................... 100m
Wiring of analog control:

Control circuit and power circuit of the dimmer are galvanically 
isolated.
The control inputs of the dimmer comply with the 
requirements for extra low safety voltage (SELV). If the control 
signals originate from appliances that also meet the SELV 
requirements, no specifi c requirements in terms of wire 
diameter or insulation of the control wires apply. You do have to 
keep the control wires apart from the 230V~ wires (min. 10mm). 
In this is not the cases, the SELV guarantees do not apply.

Humidity ................................ Designed for use in an environment 
   

with a non-condensing atmospheric 

   

humidity (30% - 70%)

Installation ............................. DIN rail (2U)
Weight ................................... ±144g
Max. wire diameter per connection terminal:
  Power supply and load ...... 2 x 2,5mm

2

 or 1 x 4mm

2

  Input ................................... 2 x 2,5mm

2

 or 1 x 4mm

2

Approval:
CE according to .....................  EN60669-2-1 and EN55015

Load table

: power in function of ambient temperature

power (W/V

A)

800
700
600
500
400
300
200
100

0

0

20

35

50

temperature (°C)

If the dimmers are placed next to each other, they can be loaded 
for max. 80%.  

Содержание 74-350

Страница 1: ...Dette apparat er ikke egnet til at styre motorer Hvis der anvendes en jernkernetransformator skal man sikre sig at denne er egnet til anvendelse sammen med elektronisk styring Hvis der anvendes halogenbelysning sammen med jernkerne transformatorer skal der tages højde for transformatorernes ydeevne Transformatorerne skal belastes med mindst 80 af deres nominelle effekt Tag højde for transformatore...

Страница 2: ...e går ikke tabt i tilfælde af strømsvigt Når hukommelsesfunktionen er slået til vil lysdæmperen først tændes ved min lysintensitet Derefter vil lysdæmperen skifte til den lysværdi som sidst blev indstillet Med hukommelse Kort tryk Tænd Sluk Tænd ved forrige niveau Langt tryk dæmp op ned Langt tryk mens lysdæmperen er slukket lysdæmperen regulere op fra min Når der reguleres op lysdæmperen stopper ...

Страница 3: ...pænding eller overstrøm kortslutning belastningen kan ikke dæmpes hverken i forkants eller i bagkantsstyring Drift vedligeholdelse Ingen vedligeholdelse Ved fejl eller driftforstyrrelser skal en autoriseret el installatør kontaktes Tekniske data Input Forsyning 230 V 10 50 Hz Maks spændingsfald over lysdæmper 5 Egetforbrug 1 W Indgangsimpedans 0 10 V 33 k 1 10 V 22 k Udgang Mindste belastning 60 W...

Страница 4: ... électriques doivent exclusivement être exécutés par un électricien agréé En cas de défaut ou de perturbation du fonctionnement contacter un installateur électricien agréé Sous réserve de modifications 1 2 3 1 Lastanschlussklemmen N 2 Anschlussklemmen Netz 230 V L N 3 Last LED 4 Fehleranzeige LED 5 Input LED s Mode 6 Auswahl Taste Mode 7 Anschlussklemmen Ansteuerung 1 bis 3 1 Belastningstilslutnin...

Страница 5: ...ble Preferably place the dimmers at the bottom of the distribution board Check the temperature If the temperature in the distribution board rises too high max 35 C provide additional ventilation This appliance is not suitable for controlling motors When using a ferromagnetic transformer check whether it is suitable for use in combination with an electronic control When using halogen lighting with ...

Страница 6: ...With memory function the dimmer first switches on at min light intensity Then the dimmer switches on at the last set light value With memory Press briefly switching on off on at previous level Press long dimming up dimming down Press long when dimmer is off dimmer dims up from min When dimming up dimmer stops at max value When dimming down dimmer stops 2s at min value and then dims up A renewed lo...

Страница 7: ...voltage or overcurrent short circuit the load is not dimmable neither in phase control nor in reverse phase control Operation maintenance No maintenance Contact a qualified electrician in the event of fault or breakdown Technical data Input Power supply 230 V 10 50 Hz Maximum voltage drop over dimmer 5 Own consumption 1W Input impedance 0 10V 33k 1 10V 22k Output Minimum load 60W Maximum load 750V...

Страница 8: ...weise Falls mehrere Dimmer direkt nebeneinander installiert werden beachten Sie einen min Abstand von 1 Modul mittels angepassten Blindplatten Falls mehrere Dimmer übereinander oder direkt nebeneinander installiert werden kann es erforderlich sein die max Belastung einzuschränken siehe Belastungstabelle Montieren Sie die Dimmer vorzugsweise unten in den Verteiler kasten Kontrollieren Sie die Tempe...

Страница 9: ...gang 2 unterschiedliche und unabhängige Funktionen Eingang 1 hat eine 1 Tasterdimmfunktion einstellbar mit oder ohne Lichtwertspeicher Mit Eingang 2 ist es möglich Lichtszenen abzuspeichern und jederzeit wieder aufzurufen Funktionsweise Eingang 1 Anschlussklemmen 1 und 3 Eingang 1 hat eine 1 Tasterdimmfunktion Siehe Fig 3 Lichtwertspeicherfunktion Der Dimmer kann sowohl mit als auch ohne Lichtwert...

Страница 10: ... blinkt Input LED s Fig 1 Es können verschiedene Ansteuerungsmethoden gewählt werden z B 0 10V Analogsteuerung 1 10V Analogsteuerung 1 Tasterbedienung oder 2 Tasterbedienung Die Input LED s zeigen an welche Ansteuerungsmethode gewählt ist Im normalen Betrieb können die Input LED s folgendes anzeigen LED s Bedeutung Obere LED leuchtet ständig Aktuelle Ansteuerungsmethode 0 10V Mittele LED leuchtet ...

Страница 11: ...Verdrahtungslänge bis zum letzten Taster 100m Verdrahtung der Analogsteuerung Steuerstromkreis und Leistungsteil des Dimmers sind galvanisch getrennt Die Ansteuereingänge des Dimmers entsprechen den Anforderungen für Schutzkleinspannung SELV Falls die Steuer signale ebenfalls aus SELV Geräten kommen werden keine speziellen Drahtquerschnittsanforde rungen oder Isolations anforderungen an die Steuer...

Страница 12: ...laissant des plaques vides Si vous installez plusieurs variateurs l un au dessus de l autre ou l un à côté de l autre il peut s avérer nécessaire de réduire la puissance maximale voir le tableau de charge Il est préférable de positionner les variateurs en bas du tableau de distribution Vérifier la température Si la température dans le tableau de distribution monte trop max 35 C assurer une ventila...

Страница 13: ...mémoire L entrée 2 permet de sauvegarder et d extraire les ambiances lumineuses à tout moment Fonctionnement de l entrée 1 bornes 1 et 3 L entrée 1 a un mode de fonctionnement 1 bouton Voir Fig 3 Fonction mémoire Le variateur peut être utilisé avec ou sans mémoire Le variateur est réglé sur le mode 1 bouton avec fonction mémoire en standard Pour paramétrer le variateur sans fonction mémoire il suf...

Страница 14: ... bouton ou 2 boutons Les LED d entrée indiquent le mode de fonctionnement sélectionné En cas de fonctionnement normal les LED d entrée peuvent avoir les significations suivantes LED Signification La LED supérieure s allume en continu Mode en cours 0 à 10 V La LED intermédiaire s allume en continu Mode en cours 1 à 10 V La LED inférieure s allume en continu Mode en cours mode 1 bouton Aucune des tr...

Страница 15: ...circuit électrique du variateur ont une isolation galvanisée Les entrées de commande du variateur sont conformes aux exigences applicables aux tensions extra faibles de sécurité SELV Si les signaux de commande viennent d appareils électriques respectant eux aussi les exigences SELV aucune exigence particulière n est applicable en ce qui concerne le diamètre des câbles ou l isolation des câbles de ...

Отзывы: