Technical data:
Minilux Sensor UL-A
Supply voltage
24 V DC ± 10%
Power 180° Sensor
max. 18 mA
Power 360° Sensor
max. 33 mA
Lux range
(blue pot.meter)
10 - 1.000 lux. Man.
Timer
(black pot.meter)
8 - 40 min. Aut./Man.
Ultrasonic frequency
32 Khz, standard
Ambient temperature
0 - 40°C
Humidity
0 - 95 %
Protection class according to IEC 529
IP 40, flush mounting, indoor
Weight
142 gr.
Output:
Short-circuit-proofed
Blue core
(movement)
NPN, max. 50 mA, movement
Grey core
(movement light)
NPN, max. 50 mA, mo light
Relay
(movement)
Potentialfree change-over contact, max. 24 V DC, 500 mA
Blue/White = Common
Black/White = NC
(Unoccupied = Blue/Black, closed)
Yellow/White = NO (Occupied = Blue/Yellow, closed)
Settings:
Ultrasound
(green pot.meter)
Aut./man. (green LED lamp)
Automatic appear of setting
Green LED lamp
DIP switch in setting OFF
Automatic operation
DIP switch in setting ON
Manual setting
DIP switch from OFF to ON result in:
A1. Overrule
Constant signal on the blue core
Grey follows mo light
A2. Sensitivity IR + ultrasound
Hight sensitivity
A3. LED
Switch off LED
A4. Reset of settings
ON 5sec - OFF
B1. Air current compensation
Stronger compensation
B2. Installation above door
Stronger signal is required
B3. Time setting
Manual setting 8 - 40 min.
B4. Sensitivity IR + ultrasound
Manual setting of pot.meters
17(27)
Li
g
hts stay on
Li
g
hts stay off
Air conditionin
g
interference
Li
g
hts stay off
li
g
hts on too
lon
g
Hallway traffic
turns li
g
hts on
Bad low volta
g
e
wirin
g
Bad hi
g
h volta
g
e
wirin
g
Timer settin
g
too
hi
g
h
Sensor can "see"
into hallway
Reduce both
g
reen
and red knobs by 15%
Check switch settin
g
s and black
potentiometer
Pit in timer test mode
walk hallway
Move sensor
Reduce sensitivity
Force li
g
hts on
Force li
g
hts on
Typical settin
g
is
8 minutes
Move sensor
Problem
Possible Cause
Test
Result
TROUBLESHOOTING
NPN
Connect term. 9 with - 11
PNP
Connect term. 9 with + 7
Connect terminal 3 (COM)
with terminal 1 (NO)