CABLES INPUT
Seats for fairleads PG11 and PG 13,5 which are easy to break through, are envisioned in the lower part of the
container for the passage of input cables
!
Cables passage
ATTENTION: Close all inputs well to prevent the entry of insects,
which may damage the control unit.
FIXING THE CONTROL UNIT TO THE WALL
Ø 6 ÷ 8 mm
It is recommended to position the appliance in
proximity of the gate in a way to reduce the length of
the connection cable, to the rest of the system, to a
minimum.
The control unit must be fixed via the cable passage
holes facing downwards.
Page 8/18
NO
NO
YES
OPENING AND CLOSING THE BOX
When opening the box, make sure that most of the hinges
escape from the guide on the bottom of the control unit in order
to guarantee that the lid remains open without obstructing the
control unit wiring operations.
In the closing phase, accompany the lid until complete return of
the hinges. Pay attention that the gasket is inserted correctly
Close the lid using the appropriate screws.
Recommendations for connections in general rooms according to the Italian
Standards (IEC 64-8).
1. Upstream from the system, prepare an omnipolar isolating switch with distance of 3 mm
or more between the contacts. As an alternative, use a 10A magnet circuit breaker
switch.
2. Make any type of connections always with the system not powered, i.e. with the
isolating switch in the "open" position ("0" symbol). In particular, the control unit must
never be powered during wiring or while any expansion cards are being inserted.
3. When installing the plant, use the following cables:
- for the power supplies of the control unit, motors and the electric locks: section 1.5mm2
for maximum length of 19m, section 2.5mm2 for lengths up to 31m,
- for the flashing light section 0.75mm2 for maximum lengths of 3m, section 1.5mm2 for
lengths up to 19m.
- for low voltage and current lines, such as photocells, control buttons, electro-
mechanical key, sensitive edges and other safety devices: section 0.5mm2 for
maximum length of 50m, section 0.75mm2 for lengths up to 100m,
4. Make the "earth" connection as envisioned by the Standards.