SolaStat™-2-3 User Guide 

 

Version 1.11 – November 2011 

 

Page 11 

P

ROGRAMMING 

T

ABLE

 

Your installer may enter special programming information for your controller in the table below. 
Settings can be changed by a qualified installer or maintenance technician. 

Programming Table for Adjustable Values 

Adjustable 

Values 

Function 

Light 

indication 

Pre-Set 

Value 

Range 

Installation 

Values 

Pump Off 

The temperature difference 

between the Roof and the Tank 

that will turn the pump off. 

PUMP Flash 

6°C 

11°F 

1-20°C 

2-36°F 

____ °C 

____ °F 

 

Pump On 

The temperature difference 

between the Roof and the Tank 

that will turn the pump on. 

PUMP On  

12°C 

22°F 

2-21°C 

4-38°F 

____ °C 

____ °F 

Holdoff 

Timer 

How long the timer will override 
the element coming on (as long 

as the tank temperature is 

above Reheat Lower).  

HWC on 

4 hours 

1-23 hours 

>23 hours = OFF 

<1 hour = thr 

 

____ hours 

Reheat 

Lower 

The tank temperature at which 

the heating element will 

automatically start to reheat the 

water in your cylinder. 

HWC slow 

flash 

 

40°C 

104°F 

1-70°C 

34-158°F 

<1ºC = OFF 

Set Holdoff Timer to 

thr = OFF 

____ °C 

____ °F 

Reheat 

Upper 

The temperature (in the tank) at 

which the heating element will 

automatically stop reheating the 

water in your cylinder. 

HWC fast 

flash 

 

55°C  

131°F 

 

2-90°C  

36-194°F 

Set Holdoff Timer to 

off = OFF 

____ °C 

____ °F 

BioSafe 

BioSafe target temperature. 

No lights 

(except PWR) 

 

60°C 

140°F 

50-70°C 

122-158°F 

<50°C = OFF 

____ °C 

____ °F 

Topout 

Maximum allowable tank 

temperature before the pump is 

de-activated to protect system 

from overheating. 

TOPOUT on  

80°C 

176°F 

1-120°C 

34-248°F 

<1°C = OFF  

____ °C 

____ °F 

 

Frost 

Minimum allowable panel 

temperature before the pump is 

activated to protect system from 

freezing damage. 

FROST on  

 

4°C  

39°F 

 

1-10°C 

34-50°F 

>10°C = OFF 

____ °C 

____ °F 

 

Содержание Solastat 2-3

Страница 1: ...USER GUIDE SolaStat 2 3 An Intelligent Technology Solution for Water Heating...

Страница 2: ......

Страница 3: ...Introducing your SolaStat Controller 1 The Display Panel 2 Saving Power with SolaStat 3 Using your SolaStat 4 Trouble Shooting Guide 10 Programming Table 11 For technical help contact your installer...

Страница 4: ...tem the collector ROOF the top of your hot water cylinder TANK and the bottom of your hot water cylinder INLET If the temperature at the ROOF is higher than the INLET temperature by a pre set amount t...

Страница 5: ...all the lights will be on at the same time for about two seconds All the lights except the PWR light will then flash and the display will show the number of times the pump has been on up to 999 The PU...

Страница 6: ...Controlling the activity of the heating element To ensure that the water in your tank is not heated by electricity unnecessarily for example when the water from your collector is already hot enough th...

Страница 7: ...de Celsius The Sola 2 3atTM 2F is factory set to display temperature in degrees Fahrenheit These settings cannot be changed Refer to the label on the side of the enclosure and the box Continued on nex...

Страница 8: ...e hot water tank After it has run for ten minutes on automatic or manual the pump automatically switches off for one minute to let air escape and prevent overheating Continued on next page Press the P...

Страница 9: ...k press the HWC button Press the HWC button again to turn it off However if Reheat is already on pressing the HWC button will not turn it off Continued on next page Press HWC for one off heat up mode...

Страница 10: ...ut two seconds Then all lights will flash and the display shows how many times the pump has been activated up to 999 for three seconds Continued on next page Then all the lights except the PWR light w...

Страница 11: ...ed you will see SSd on the display as shown on the screen below The ROOF sensor temperature may reduce to a safe level by itself and the uniit will return to normal operation SSd will no longer appear...

Страница 12: ...pump operates to protect the system from freezing Frost Mode The FROST value is set by your installer It is shown in the Programming Table on Page 11 This function is designed to protect your collect...

Страница 13: ...pump running times may be normal for a special installation Contact your installer or maintenance technician Hot water drops significantly at night yet little or no draw off be user System is reverse...

Страница 14: ...above Reheat Lower HWC on 4 hours 1 23 hours 23 hours OFF 1 hour thr ____ hours Reheat Lower The tank temperature at which the heating element will automatically start to reheat the water in your cyli...