Senztek Solastat 2-3 Скачать руководство пользователя страница 13

SolaStat™-2-3 User Guide 

 

Version 1.11 – November 2011 

 

Page 10 

T

ROUBLE 

S

HOOTING 

G

UIDE 

 

Symptom 

Cause 

Solution 

No operation, no 
display and no lights. 

 

No power/fault. 

 

 

Check mains outlet. 

 

Check fuses. 

POWER light ON but 
no display or 
corrupted display. 

 

Power brown out (mains power not 
running at full voltage). 

 

Unit faulty. 

 

Switch off power while mains 
power is in brown out condition.  

 

Switch off power for 10 minutes, 
switch on power and see if unit is 
operating. If not, unit needs repair. 
Contact installer. 

Display on, pump not 
running, but sunny 
outside. Pump light 
ON. 

 

Pump damaged or disconnected. 

 

Pump timer has turned pump off. 

 

See if the pump has become 
unplugged. 

 

Wait one minute for the pump to 
restart. 

Pump is running 
continuously. 

 

Pump is cavitating. 

 

Special installation. 

 

Setting is incorrect. 

 

Airlock in pipe. 

 

If pump sounds like stones are 
passing through it, the pump may 
be cavitating. Contact your 
installer or maintenance 
technician. 

 

Long pump running times may be 
normal for a special installation. 

 

Contact your installer or 
maintenance technician. 

Hot water drops 
significantly at night, 
yet little or no draw off 
be user. 

 

System is reverse thermo-
siphoning. 

 

System is in a high frost area. 

 

Tank is losing heat. 

 

The non-return valve is not fitted 
correctly or is malfunctioning. 

 

Discuss non-frost sensitive options 
with your energy provider. 

 

Install better insulation on the hot 
water tank. 

HWC light never 
comes on. 

 

Collectors are heating tank to 
greater than adjustable values. 

 

Normal operation. 

HWC light flashing.  

 

HWC Reheat Upper adjustable 
value has not been reached. 

 

Tank Thermostat incorrectly set  

 

Wait for the tank to heat up to 
Reheat Upper temperature. 

 

Contact your installer or 
maintenance technician. 

‘Lo’ on display. 

 

Sensor below -20°C/-4°F. 

 

Check outside temperature. 

‘Hi’ on display. 

 

Sensor above 139°C/284°F. 

 

Check collector has water in it. 

‘SSd’ on display.  

 

 

System is in ‘Smart Shutdown’ 
Mode. 

 

Contact your installer or 
maintenance technician if the 
display shows’ SSd’ for more than 
12 hours. 

Note: When power is removed, the internal timer will keep running for at least 7 days. 

Содержание Solastat 2-3

Страница 1: ...USER GUIDE SolaStat 2 3 An Intelligent Technology Solution for Water Heating...

Страница 2: ......

Страница 3: ...Introducing your SolaStat Controller 1 The Display Panel 2 Saving Power with SolaStat 3 Using your SolaStat 4 Trouble Shooting Guide 10 Programming Table 11 For technical help contact your installer...

Страница 4: ...tem the collector ROOF the top of your hot water cylinder TANK and the bottom of your hot water cylinder INLET If the temperature at the ROOF is higher than the INLET temperature by a pre set amount t...

Страница 5: ...all the lights will be on at the same time for about two seconds All the lights except the PWR light will then flash and the display will show the number of times the pump has been on up to 999 The PU...

Страница 6: ...Controlling the activity of the heating element To ensure that the water in your tank is not heated by electricity unnecessarily for example when the water from your collector is already hot enough th...

Страница 7: ...de Celsius The Sola 2 3atTM 2F is factory set to display temperature in degrees Fahrenheit These settings cannot be changed Refer to the label on the side of the enclosure and the box Continued on nex...

Страница 8: ...e hot water tank After it has run for ten minutes on automatic or manual the pump automatically switches off for one minute to let air escape and prevent overheating Continued on next page Press the P...

Страница 9: ...k press the HWC button Press the HWC button again to turn it off However if Reheat is already on pressing the HWC button will not turn it off Continued on next page Press HWC for one off heat up mode...

Страница 10: ...ut two seconds Then all lights will flash and the display shows how many times the pump has been activated up to 999 for three seconds Continued on next page Then all the lights except the PWR light w...

Страница 11: ...ed you will see SSd on the display as shown on the screen below The ROOF sensor temperature may reduce to a safe level by itself and the uniit will return to normal operation SSd will no longer appear...

Страница 12: ...pump operates to protect the system from freezing Frost Mode The FROST value is set by your installer It is shown in the Programming Table on Page 11 This function is designed to protect your collect...

Страница 13: ...pump running times may be normal for a special installation Contact your installer or maintenance technician Hot water drops significantly at night yet little or no draw off be user System is reverse...

Страница 14: ...above Reheat Lower HWC on 4 hours 1 23 hours 23 hours OFF 1 hour thr ____ hours Reheat Lower The tank temperature at which the heating element will automatically start to reheat the water in your cyli...