Senville SENA 18HF MOZ Скачать руководство пользователя страница 29

Using a wire crimper, crimp u-lugs on the

ends.

b. Using wire strippers, strip the rubber

jacketfrom both ends of the signal cable

to reveal approximately 15cm (5.9”) of

wire.

c. Strip the insulation from the ends.
d.

NOTE: 

When connecting the wires, strictly

follow the wiring diagram found inside the

electrical box cover.

2. Remove the electric cover of the outdoor unit.

If there is no cover on the outdoor unit, take

off the bolts from the maintenance board

and remove the protection board.

3. Connect the u-lugs to the terminals

Match the wire colors/labels with the labels

on the terminal block. Firmly screw the u-lug

of each wire to its corresponding terminal.

4. Clamp down the cable with the cable clamp.

5. Insulate unused wires with electrical tape.

Keep them away from any electrical or metal

parts.

6. Reinstall the cover of the electric control box.

Page 

29

 

Wiring

Cover

Screw

Wiring Figure

NOTE:

 Refer to the following figures if end-users wish to perform their own wiring.

 Run the main power cord through the lower line-outlet of the cord clamp.

---- This symbol indicates field wiring.

 CAUTION

Connect the connective cables to the terminals, as identified, with their matching numbers 

on the terminal block of the indoor and outdoor units. For example

Terminal 1(A) of the 

outdoor unit must connect with terminal 1 on the indoor unit.

Содержание SENA 18HF MOZ

Страница 1: ...is manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference Please check the applicable models technical data F GAS if any and...

Страница 2: ...wner s Manual Table of Contents Safety Precautions Unit Parts And Major Functions 1 Unit Parts 2 Operating temperature 3 Features Manual Operations And Maintenance Troubleshooting 04 07 07 09 10 12 13...

Страница 3: ...efrigerant Piping Connection 1 Cut pipe 2 Remove burrs 3 Flare pipe ends 4 Connect pipes Wiring 1 Outdoor Uint Wiring 2 Wiring Figure Air Evacuation 1 Evacuation Instructions 2 Refrigerant Release Ins...

Страница 4: ...ock fire or injury Do not insert fingers rods or other objects into the air inlet or outlet This may cause injury since the fan may be rotating at high speeds Do not use flammable sprays such as hair...

Страница 5: ...ical shock If connecting power to fixed wiring an all pole disconnection device which has at least 3mm clearances in all poles and have a leakage current that may exceed 10mA the residual current devi...

Страница 6: ...ance to its support please read the information for details in indoor unit installation and outdoor unit installation sections For units that have an auxiliary electric heater do not install the unit...

Страница 7: ...5 Horizontal louver 6 LCD display window 7 Vertical louver 8 Manual control button behind 9 Remote controller holder Outdoor unit 10 Drain hose refrigerant connecting pipe 11 Connective cable 12 Stop...

Страница 8: ...controller 4 Installation part 5 Display panel Outdoor unit 6 Drain hose refrigerant connecting pipe 7 Connective cable 8 Stop valve 9 Fan hood Indoor unit 1 Drain pump drain water from indoor unit 2...

Страница 9: ...0 C 50 C 32 F 122 F 15 C 24 C 5 F 75 F 0 C 50 C 32 F 122 F 0 C 52 C 32 F 126 F For special tropical models 0 C 52 C 32 F 126 F For special tropical models 15 C 50 C 5 F 122 F For models with low temp...

Страница 10: ...F button on the remote control If the system has an auto restart function the unit will restart using the same settings White mist emerging from the indoor unit A white mist may be generated due to a...

Страница 11: ...erature If a comfortable temperature cannot be achieved with the air conditioner alone it is recommended that you use a supplementary heating device Lightning or a car wireless telephone operating nea...

Страница 12: ...eriodically Contact a local dealer or a customer service centre if the unit requires servicing When the air conditioner is to be used again Use a dry cloth to wipe off the dust accumulated on the rear...

Страница 13: ...The set temperature has been reached at which point the unit turns off the compressor The unit will resume operating when the temperature fluctuates again The indoor unit emits white mist In humid re...

Страница 14: ...mize product operation The indoor unit makes noises A squeaking sound is heard when the system is OFF or in COOL mode The noise is also heard when the drain pump optional is in operation A squeaking s...

Страница 15: ...oors and windows are closed while operating the unit Excessive heat is generated by sunlight Close windows and curtains during periods of high heat or bright sunshine Low refrigerant due to leak or lo...

Страница 16: ...speed has been out of control IPM malfunction or IGBT over strong current protection Over voltage or over low voltage protection High temperature protection of IPM module Outdoor ambient temperature t...

Страница 17: ...sed separately Manual 2 4 Name of Accessories Qty pc Shape Name of Accessories Qty pc Shape 1 1 2 Drain joint Seal ring Copper nut Name Shape Quantity pc per box Copper line set Liquid side Gas side 1...

Страница 18: ...lation Summary INSTALLATION ORDER L N 1 2 3 MC MC 4 5 Install the outdoor unit Evacuate the refrigeration system Connect the wires Connect the refrigerant pipes Perform a test run Installation Summary...

Страница 19: ...n of 3 metres is required to minimise vibration excessive noise Two of the A B and C air circulation pathways must be free from obstructions at all times NOTE The installation must be performed in acc...

Страница 20: ...Max Height difference SENA 18HF MOZ SENA 30HF MOZ Max length for all rooms 131 40m 197 60m Max length for one indoor unit 82 25m 98 30m Max height different between indoor and outdoor unit 49 15m 49...

Страница 21: ...rection of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong wind If the unit is frequently exposed to h...

Страница 22: ...nit in place you must install the drain joint at the bottom of the unit Note that there are two different types of drain joints depending on the type of outdoor unit If the drain joint comes with a ru...

Страница 23: ...hole make sure to avoid wires plumbing and other sensitive components 3 Place the protective wall cuff in the hole This protects the edges of the hole and helps seal it when you finish the installatio...

Страница 24: ...nance Connection Instructions Refrigerant Piping 1 Measure the distance between the indoor and outdoor units 2 Using a pipe cutter cut the pipe a little longer than the measured distance 3 Make sure t...

Страница 25: ...th the dimensions shown in the table below Fig 5 3 Fig 5 4 PIPING EXTENSION BEYOND FLARE FORM Outer Diameter of Pipe inch A inch Min Max 1 4 6 35mm 0 0275 0 7mm 0 05 1 3mm 3 8 9 52mm 0 04 1 0mm 0 063...

Страница 26: ...caps from ends of valves 3 Align flared pipe end with each valve and tighten the flare nut as tightly as possible by hand 4 Using a spanner grip the body of the valve Do not grip the nut that seals t...

Страница 27: ...MOZ 1 4 3 8 SENA 36HF MOZ SENA 48HF MOZ Port B Liquid Gas Port C Liquid Gas Port D Liquid Gas Port E Liquid Gas 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8...

Страница 28: ...or switch 7 Only connect the unit to an individual branch circuit outlet Do not connect another appliance to that outlet 8 9 10 11 12 Make sure to properly ground the air conditioner Every wire must b...

Страница 29: ...bels on the terminal block Firmly screw the u lug of each wire to its corresponding terminal 4 Clamp down the cable with the cable clamp 5 Insulate unused wires with electrical tape Keep them away fro...

Страница 30: ...18HF MOZ SENA 30HF MOZ Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Green Green Green...

Страница 31: ...lack White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black Whi...

Страница 32: ...age circuit breaker in wet or moist areas The following can be caused by a drop in voltage vibration of a magnetic switch damaging the contact point broken fuses and disturbance of normal functioning...

Страница 33: ...ork when outside temperature is not above 5 2 Check that the stop valves of the liquid pipe and gas pipe are open 3 Turn on the breaker and wait at least 2 minutes 4 Press the check switch on the outd...

Страница 34: ...r High Pressure Valve Manifold High Pressure Valve 0 0 3 50 100 150 200 250 300 350 0 100 200 300 400 500 500 600 Fig 6 1 Air Evacuation 4 5 Evacuation is now complete Close the left blue manifold low...

Страница 35: ...Note on Adding Refrigerant R410a ADDITIONAL REFRIGERANT PER PIPE LENGTH Depending on the length of the installed piping you may need to add additional refrigerant to your system The unit comes pre ch...

Страница 36: ...age check Turn off the unit immediately if leakage happens Try and evaluate different solutions until the unit operates properly Gas leak check 1 Soap water method Apply a soap water solution or a liq...

Страница 37: ...2 Turn on the main power switch and allow the unit to warm up 3 Set the air conditioner to COOL mode 4 For the Indoor Unit a Ensure the remote control and its buttons work properly b Ensure the louver...

Страница 38: ...s are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website please...

Отзывы: