Senville SENA 18HF MOZ Скачать руководство пользователя страница 21

Outdoor Unit 

Installation

Outdoor Unit Installation

ev

o

ba 

)

ni

42

mc

06

60cm (24in) 

on righ

t

30cm (12in) 

on left

200cm (79in) 

in fron

t

30cm (12in) 

from back wall

Installation Instructions – Outdoor unit 

Step 1: Select installation location

Before installing the outdoor unit, you must 

choose an appropriate location. The following are 

standards that will help you choose an appropriate

location for the unit.  

Proper installation locations meet the 

following standards:

Meets all spatial requirements shown in

Installation Space Requirements above.

Good air circulation and ventilation

Firm and solid—the location can support the

unit and will not vibrate

Noise from the unit will not disturb others

Install the unit by following local codes and 

regulations , there may be differ slightly 

between different regions.  

SPECIAL CONSIDERATIONS FOR EXTREME 

WEATHER

If the unit is exposed to heavy wind:

Install unit so that air outlet fan is at a 90° 

angle to the direction of the wind. If needed, 

build a barrier in front of the unit to protect it 

from extremely heavy winds.

See Figures below

.

 

Strong

 wind

Strong wind

Strong wind

If the unit is frequently exposed to heavy 

rain or snow:

Build a shelter above the unit to protect 

it from the rain or snow.  Be careful not to 

obstruct air flow around the unit.

If the unit is frequently exposed to salty air 

(seaside): 

Use outdoor unit that is specially designed to 

resist corrosion.

Wind Baffle

Protected from prolonged periods of direct

sunlight or rain

 

DO NOT

 install unit in the following locations:

 

Near an obstacle that will block air inlets 

and outlets

 

Near a public street, crowded areas, or 

where noise from the unit will disturb others 

 

Near animals or plants that will be harmed 

by hot air discharge

 

Near any source of combustible gas

 

In a location that is exposed to large 

amounts of dust

 

In a location exposed to a excessive amounts 

of salty air

Where snowfall is anticipated, raise the

unit above the base pad to prevent ice

buildup and coil damage. Mount the unit

high enough to be above the average

accumulated area snowfall. The minimum

height must be 18 inches

Содержание SENA 18HF MOZ

Страница 1: ...is manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference Please check the applicable models technical data F GAS if any and...

Страница 2: ...wner s Manual Table of Contents Safety Precautions Unit Parts And Major Functions 1 Unit Parts 2 Operating temperature 3 Features Manual Operations And Maintenance Troubleshooting 04 07 07 09 10 12 13...

Страница 3: ...efrigerant Piping Connection 1 Cut pipe 2 Remove burrs 3 Flare pipe ends 4 Connect pipes Wiring 1 Outdoor Uint Wiring 2 Wiring Figure Air Evacuation 1 Evacuation Instructions 2 Refrigerant Release Ins...

Страница 4: ...ock fire or injury Do not insert fingers rods or other objects into the air inlet or outlet This may cause injury since the fan may be rotating at high speeds Do not use flammable sprays such as hair...

Страница 5: ...ical shock If connecting power to fixed wiring an all pole disconnection device which has at least 3mm clearances in all poles and have a leakage current that may exceed 10mA the residual current devi...

Страница 6: ...ance to its support please read the information for details in indoor unit installation and outdoor unit installation sections For units that have an auxiliary electric heater do not install the unit...

Страница 7: ...5 Horizontal louver 6 LCD display window 7 Vertical louver 8 Manual control button behind 9 Remote controller holder Outdoor unit 10 Drain hose refrigerant connecting pipe 11 Connective cable 12 Stop...

Страница 8: ...controller 4 Installation part 5 Display panel Outdoor unit 6 Drain hose refrigerant connecting pipe 7 Connective cable 8 Stop valve 9 Fan hood Indoor unit 1 Drain pump drain water from indoor unit 2...

Страница 9: ...0 C 50 C 32 F 122 F 15 C 24 C 5 F 75 F 0 C 50 C 32 F 122 F 0 C 52 C 32 F 126 F For special tropical models 0 C 52 C 32 F 126 F For special tropical models 15 C 50 C 5 F 122 F For models with low temp...

Страница 10: ...F button on the remote control If the system has an auto restart function the unit will restart using the same settings White mist emerging from the indoor unit A white mist may be generated due to a...

Страница 11: ...erature If a comfortable temperature cannot be achieved with the air conditioner alone it is recommended that you use a supplementary heating device Lightning or a car wireless telephone operating nea...

Страница 12: ...eriodically Contact a local dealer or a customer service centre if the unit requires servicing When the air conditioner is to be used again Use a dry cloth to wipe off the dust accumulated on the rear...

Страница 13: ...The set temperature has been reached at which point the unit turns off the compressor The unit will resume operating when the temperature fluctuates again The indoor unit emits white mist In humid re...

Страница 14: ...mize product operation The indoor unit makes noises A squeaking sound is heard when the system is OFF or in COOL mode The noise is also heard when the drain pump optional is in operation A squeaking s...

Страница 15: ...oors and windows are closed while operating the unit Excessive heat is generated by sunlight Close windows and curtains during periods of high heat or bright sunshine Low refrigerant due to leak or lo...

Страница 16: ...speed has been out of control IPM malfunction or IGBT over strong current protection Over voltage or over low voltage protection High temperature protection of IPM module Outdoor ambient temperature t...

Страница 17: ...sed separately Manual 2 4 Name of Accessories Qty pc Shape Name of Accessories Qty pc Shape 1 1 2 Drain joint Seal ring Copper nut Name Shape Quantity pc per box Copper line set Liquid side Gas side 1...

Страница 18: ...lation Summary INSTALLATION ORDER L N 1 2 3 MC MC 4 5 Install the outdoor unit Evacuate the refrigeration system Connect the wires Connect the refrigerant pipes Perform a test run Installation Summary...

Страница 19: ...n of 3 metres is required to minimise vibration excessive noise Two of the A B and C air circulation pathways must be free from obstructions at all times NOTE The installation must be performed in acc...

Страница 20: ...Max Height difference SENA 18HF MOZ SENA 30HF MOZ Max length for all rooms 131 40m 197 60m Max length for one indoor unit 82 25m 98 30m Max height different between indoor and outdoor unit 49 15m 49...

Страница 21: ...rection of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong wind If the unit is frequently exposed to h...

Страница 22: ...nit in place you must install the drain joint at the bottom of the unit Note that there are two different types of drain joints depending on the type of outdoor unit If the drain joint comes with a ru...

Страница 23: ...hole make sure to avoid wires plumbing and other sensitive components 3 Place the protective wall cuff in the hole This protects the edges of the hole and helps seal it when you finish the installatio...

Страница 24: ...nance Connection Instructions Refrigerant Piping 1 Measure the distance between the indoor and outdoor units 2 Using a pipe cutter cut the pipe a little longer than the measured distance 3 Make sure t...

Страница 25: ...th the dimensions shown in the table below Fig 5 3 Fig 5 4 PIPING EXTENSION BEYOND FLARE FORM Outer Diameter of Pipe inch A inch Min Max 1 4 6 35mm 0 0275 0 7mm 0 05 1 3mm 3 8 9 52mm 0 04 1 0mm 0 063...

Страница 26: ...caps from ends of valves 3 Align flared pipe end with each valve and tighten the flare nut as tightly as possible by hand 4 Using a spanner grip the body of the valve Do not grip the nut that seals t...

Страница 27: ...MOZ 1 4 3 8 SENA 36HF MOZ SENA 48HF MOZ Port B Liquid Gas Port C Liquid Gas Port D Liquid Gas Port E Liquid Gas 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8 1 4 3 8...

Страница 28: ...or switch 7 Only connect the unit to an individual branch circuit outlet Do not connect another appliance to that outlet 8 9 10 11 12 Make sure to properly ground the air conditioner Every wire must b...

Страница 29: ...bels on the terminal block Firmly screw the u lug of each wire to its corresponding terminal 4 Clamp down the cable with the cable clamp 5 Insulate unused wires with electrical tape Keep them away fro...

Страница 30: ...18HF MOZ SENA 30HF MOZ Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Green Green Green...

Страница 31: ...lack White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black White Red Black Whi...

Страница 32: ...age circuit breaker in wet or moist areas The following can be caused by a drop in voltage vibration of a magnetic switch damaging the contact point broken fuses and disturbance of normal functioning...

Страница 33: ...ork when outside temperature is not above 5 2 Check that the stop valves of the liquid pipe and gas pipe are open 3 Turn on the breaker and wait at least 2 minutes 4 Press the check switch on the outd...

Страница 34: ...r High Pressure Valve Manifold High Pressure Valve 0 0 3 50 100 150 200 250 300 350 0 100 200 300 400 500 500 600 Fig 6 1 Air Evacuation 4 5 Evacuation is now complete Close the left blue manifold low...

Страница 35: ...Note on Adding Refrigerant R410a ADDITIONAL REFRIGERANT PER PIPE LENGTH Depending on the length of the installed piping you may need to add additional refrigerant to your system The unit comes pre ch...

Страница 36: ...age check Turn off the unit immediately if leakage happens Try and evaluate different solutions until the unit operates properly Gas leak check 1 Soap water method Apply a soap water solution or a liq...

Страница 37: ...2 Turn on the main power switch and allow the unit to warm up 3 Set the air conditioner to COOL mode 4 For the Indoor Unit a Ensure the remote control and its buttons work properly b Ensure the louver...

Страница 38: ...s are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website please...

Отзывы: