Page
34
Wiring
Indoor unit
Outdoor unit
Red
Black
White
Grn/Yel
1
L1
L2
Interconnecting
Cable
Black
Red
Grn/Yel
Main Power
Cable
GND
L2
L1
2
3
1
2
3
Red
Black
White
Grn/Yel
*Main power cable from electrical panel to outdoor unit
Notes:
1. Main power is supplied to outdoor unit only
2. System must be installed on a dedicated circuit
3. Follow all local building codes and NEC regulations
4. Use the above table to size your circuit breaker
Voltage
Minimum Circuit
Amps (MCA)
Max Overcurrent
Protection (MOP)
Main Power Wire
Size (AWG)
*
SENA/09HF/OZ
SENA/12HF/OZ
SENA/18HF/OZ
SENA/24HF/OZ
SENA/36HF/OZ
Model
Number
208/230V - 1ph 60Hz
208/230V - 1ph 60Hz
208/230V - 1ph 60Hz
208/230V - 1ph 60Hz
208/230V - 1ph 60Hz
9
9
18
20
25
20
20
20
30
40
12
12
12
10
8