background image

6

   | 

 

866-660-8864  |   fax  503-296-2529  |   www.senvainc.com

PowerPrint can only learn and save characteristics for channels 

with a properly installed CVT. If the CVT is displaying a 

warning or error condition during Normal Operation, take 

the corrective action to resolve the installation error prior to 

enabling PowerPrint. 
When PowerPrint is enabled, it will identify which channels are 

active (have properly installed CVTs) and apply the learn and 

save characteristics to those channels:

Setting

PowerPrint Function

PowerPrint off - default

PowerPrint is disabled

PowerPrint on Channel R

PowerPrint enabled for all channels with a 

properly installed CVT. 

PowerPrint should not be saved if any channels 

display an error condition (red LED) during 

Normal Operation (See Section 4 - Normal 

Operation Mode).

PowerPrint on Channel S
PowerPrint on Channels RT
PowerPrint on Channel T
PowerPrint on Channel RT
PowerPrint on Channel ST
PowerPrint on Channel RST

Once PowerPrint has been turned on and the system 

characteristics have been saved, the alarm conditions below 

will be displayed on the meter LEDs as a warning or error 

during Normal Operation (

See Section 4 - Normal Operation 

Mode

):

Alarm Condition

Parameter

Missing sensor

CVT missing on one or more channels 

Unexpected sensor

CVT identity does not match original CVT 

saved in Powerprint

Brown out voltage

Voltage < 10% from saved voltage

Surge voltage

Voltage > 10% from saved voltage

Frequency drift

1

Frequency not /-0.2Hz from saved 

frequency

Phase drift

Phase voltage angle variance > +/-30

o

 from 

saved angle

1

PowerPrint will not monitor frequency variance if system frequency is not 

50 or 60Hz when PowerPrint is initiated.

PowerPrint Diagnostic Codes

: The following alarm codes are to 

be used in addition to 

Table 1. Diagnostic Codes

 in 

Section 5 - 

Diagnostics Mode

 with PowerPrint On:

Table 2.  PowerPrint Diagnostic Codes

 

CVT LEDs

Indication

Corrective Action

Missing sensor

Reconnect original CVT to meter

Unexpected sensor Reconnect original CVT to meter

Brown out voltage

Verify system voltage

Surge voltage

Verify system voltage

 

Line LED 

Indication

Corrective Action

Frequency drift

Verify system voltage

Phase drift

Verify system voltage

PowerPrint Alarm Mode

: In addition to the LED indicators 

above, the PowerPrint can also alert via an output alarm when 

a PowerPrint warning condition is present. This requires the 

user to select Alarm Mode in 

Setting 2. Pulse/Alarm Options

With PowerPrint On and Alarm Mode selected, the meter will 

now display warning conditions on the LEDs and provide an 

alarm output to the controller.

Alarm Mode

: Output 2 provides a normally open alarm output. 

The default alarm is for phase loss of one or more channels 

in a multi-phase installation. Alarm mode will also convert 

output 1 to the total import and export energy sensed by the 

meter. See 

Section 3 - Wiring: Pulse Output Wiring Options.

PowerPrint Alarm Mode

: When PowerPrint is turned on Output 

2 provides a normally open alarm output for all PowerPrint 

alarm conditions. See 

Setting 5. PowerPrint

 below for all alarm 

conditions. Alarm mode will also convert output 1 to the total 

import and export energy sensed by the meter. See 

Section 3 - 

Wiring: Pulse Output Wiring Options.

Setting 3. Energy Output Type

There are 4 Energy Output Type settings in the EM-PULSE 

meter: Total Real ‘Active’ Energy, Net Real ‘Active’ Energy, 

Reactive Energy, and Apparent Energy.

Setting

Energy Units

Total Real ‘Active’ Energy

1

 

(P) - default

Measured in watts (Wh or kWh)

Meter will output total import and export 

energy of all CVT channels

Net Real ‘Active’ Energy

2

 (P

net

)

Measured in watts (Wh or kWh)

Meter will output net energy

Reactive Energy (Q)

Measured in volt-amperes reactive 

(VARh or kVARh)

Apparent Energy (S)

Measured in volt-amperes (VAh or kVAh)

1

Total Real ‘Active Energy outputs both import and export pulses as the 

energy is accumulated by the meter.

2

Net Real ‘Active’ Energy sums the channels internally before outputting, so 

import and export energy will cancel, resulting in the net energy output.

 

Setting 4. Balanced Load Multiplier

The Balanced Load Multiplier is utilized so that one CVT can 

extrapolate power of a balanced load (e.g. motor) without 

actually monitoring all 3 phases. The multiplier can be applied 

to one or more CVT channels, meaning the EM-PULSE can 

monitor up to three motors with one meter: 

Setting

Balanced Load Multiplier Function

Disable all balanced 

load multiplers - Default

All balanced load multipliers are disabled

Enable R balanced load 

multiplier

Output for R channel = 3X power measurement 

Enable S balanced load 

multiplier

Output for S channel = 3X power measurement

Enable RS balanced 

load multipliers

Output for R & S channels = 3X power 

measurement

Enable T balanced load 

multiplier

Output for T channel = 3X power measurement

Enable RT balanced 

load multipliers

Output for R & T channels = 3X power 

measurement

Enable ST balanced 

load multipliers

Output for S & T channels = 3X power 

measurement

Enable RST balanced 

load multipliers

Output for all channels = 3X power 

measurement

Setting 5. PowerPrint

PowerPrint is a power quality alarm that enables the meter to 

learn and save characteristics of the system being monitored. 

Based on recorded values, the meter can provide alarm 

conditions and allow user to evaluate system status at a later 

time. This is an optional feature, but as PowerPrint is turned 

on, the meter identifies each CVT connection and saves 

settings on the following parameters:
1.  Which channels have a CVT connected

2.  Amperage rating and internal serial number of each CVT

3.  System voltage

4.  System frequency

5.  Phase voltage angle

Содержание EM Pulse Series

Страница 1: ...eter EM PULSE and Current Voltage Transducers LET S GET STARTED INSTALLATION INSTRUCTIONS HAZARDOFELECTRICSHOCK EXPLOSION ORARCFLASH Failuretofollowtheseinstrutionsmaycauseseriousinjuryordeath Failure...

Страница 2: ...PULSE is a 3 channel pulse meter with two pulse inputs and two pulse outputs The EM PULSE supports the use of all Senva Current Voltage Transducers CVTs interchangeably The EM PULSE meter base is a c...

Страница 3: ...d on the meter will combine the total import and export energy through output 1 Output 2 will be a normally open alarm See Section 7 2 Configuration Settings for further details on Pulse Alarm Options...

Страница 4: ...pattern will apply to a specific channel R S or T on which the condition is present 3 Press P Setup Button to view next code and repeat Step 2 to diagnose condition 4 Continue to diagnose conditions...

Страница 5: ...configuation of the following settings 1 Pulse Scale 2 Pulse Alarm Options 3 Energy Output Type 4 Balanced Load Multiplier 5 Powerprint Each setting has factory default which can be found in Section...

Страница 6: ...ls in a multi phase installation Alarm mode will also convert output 1 to the total import and export energy sensed by the meter See Section 3 Wiring Pulse Output Wiring Options PowerPrint Alarm Mode...

Страница 7: ...en 1 to 5 times repeating every 3 seconds to indicate which Setting Group is being displayed STEP 5 To Exit View Settings Mode Press and hold Setup Button until Line LED rapidly blinks green approxima...

Страница 8: ...press and hold the Setup Button until the Line LED rapidly blinks green approximately 2 second 2s hold Release and and meter returns to View Settings Mode with new setting saved STEP 6 Exit Resume No...

Страница 9: ...L N through 600VL L Frequency 45 65 Hz Performance Accuracy 1 for V A kW kVAR kVA PF Current Voltage TransducerTM Small Rope Circumference Medium Rope Circumference Large Rope Circumference Grande Rop...

Отзывы: