senva EM Pulse Series Скачать руководство пользователя страница 2

2

   | 

 

866-660-8864  |   fax  503-296-2529  |   www.senvainc.com

k

 Mounting

Meter Mounting Options

The EM-PULSE features four mounting options for convenience: 

rare-earth magnets, mounting tabs, horizontal DIN rail and 

vertical DIN rail.

DIN Rail (horizontal)

DIN Rail (vertical)

Snap-in mounting tabs

Magnetic mount--no drilling!

Current Voltage Transducer (CVT) Mounting

The CVTs have a preferred mounting angle relative to the 

conductor that will help maintain maximum accuracy. See 

below for instructions. 

  

Ensure orientation of CVT to load is as shown. 

Installation Environment

This product is intended for environments which control 

conductive pollution and the possibility of condensation or 

high humidity (Pollution level 2). High voltage components 

shall be mounted in an appropriate electrical enclosure. Meter 

base is class 2 device. 
CVTs may not be installed in a panel where they exceed 75% of 

the wiring space of any cross-sectional area within the panel. 

Meter shall be enclosed in a certified enclosure.

LOAD

LOAD

Wire tie
Label 

Facing

Out

!

j

 Description

EM-PULSE

The EM-PULSE is a 3 channel pulse meter with two pulse inputs 

and two pulse outputs. The EM-PULSE supports the use of all 

Senva Current Voltage Transducers (CVTs), interchangeably. 

The EM-PULSE meter base is a class 2 low voltage device 

for mounting flexibility. See 

Section 9 - Specifications

 for 

recommended conductor gauge and terminal tightening 

torque.

EM-PULSE

2

1

1

2

Power
Ground
Pulse Input 1

Pulse Input Ground 
Pulse Input 2

Pulse Output 1 
Pulse Output Common 

Pulse Output 2 

Setup Button

Line Status 

LED

Device 

Status LED

CV

St

at

us

 LE

Ds

CV

Co

nn

ec

tio

ns

CVT

Data Communication

Cable (to meter)

Neutral Lead 

(white)

Voltage Lead 

(color)

Zip Tie

Accomodations

Coil Insert into

Housing Clasp

Rogowski

Release Clasp

Rogowski

Coil

Current Voltage Transducer (CVT)

The Current/Voltage Transducer (CVT) senses both current and 

voltage. Each CVT is independently calibrated and uses digital 

communication with the meter for superior noise immunity 

and accuracy. Each CVT will automatically configure with the 

meter during installation, eliminating the need for manual 

configuration.
DO NOT modify the length of the CVT Data Communication 

Cable. Field modifications to the CVT Data Communication 

Cable will void factory warranty.

Opening the CVT Clasp

Slide On

Slide On

Press

Содержание EM Pulse Series

Страница 1: ...eter EM PULSE and Current Voltage Transducers LET S GET STARTED INSTALLATION INSTRUCTIONS HAZARDOFELECTRICSHOCK EXPLOSION ORARCFLASH Failuretofollowtheseinstrutionsmaycauseseriousinjuryordeath Failure...

Страница 2: ...PULSE is a 3 channel pulse meter with two pulse inputs and two pulse outputs The EM PULSE supports the use of all Senva Current Voltage Transducers CVTs interchangeably The EM PULSE meter base is a c...

Страница 3: ...d on the meter will combine the total import and export energy through output 1 Output 2 will be a normally open alarm See Section 7 2 Configuration Settings for further details on Pulse Alarm Options...

Страница 4: ...pattern will apply to a specific channel R S or T on which the condition is present 3 Press P Setup Button to view next code and repeat Step 2 to diagnose condition 4 Continue to diagnose conditions...

Страница 5: ...configuation of the following settings 1 Pulse Scale 2 Pulse Alarm Options 3 Energy Output Type 4 Balanced Load Multiplier 5 Powerprint Each setting has factory default which can be found in Section...

Страница 6: ...ls in a multi phase installation Alarm mode will also convert output 1 to the total import and export energy sensed by the meter See Section 3 Wiring Pulse Output Wiring Options PowerPrint Alarm Mode...

Страница 7: ...en 1 to 5 times repeating every 3 seconds to indicate which Setting Group is being displayed STEP 5 To Exit View Settings Mode Press and hold Setup Button until Line LED rapidly blinks green approxima...

Страница 8: ...press and hold the Setup Button until the Line LED rapidly blinks green approximately 2 second 2s hold Release and and meter returns to View Settings Mode with new setting saved STEP 6 Exit Resume No...

Страница 9: ...L N through 600VL L Frequency 45 65 Hz Performance Accuracy 1 for V A kW kVAR kVA PF Current Voltage TransducerTM Small Rope Circumference Medium Rope Circumference Large Rope Circumference Grande Rop...

Отзывы: