TECH TIPS
On low current loads, wrap sensor multiple
times to increase sensitivity
CAUTION: Do not exceed sensor
maximum current. The current
detected by the sensor will
increase 1X with each wrap.
To monitor loads greater than the current sensor
maximum rating
Use a properly rated 5A CT as shown below
CAUTION!
5A CTs can present
hazardous voltages. Install
CTs in accordance with
manufacturers instructions.
Terminate the CT secondary
wiring before energizing
primary conductor.
Part Number
C-2300
Amperage Range
0.35A (on)~100A (200A Max)
Output Type
NO, solid-state FET
Output Rating
1.0A@30VAC/DC Max.
Temperature Rating
-15~60 ° C
Insulation Class
600V RMS. For use on insulated conductors only!
Use minimum 75 ° C insulated conductor
Sensor Power
Induced
Frequency Range
50/60Hz
Dimensions ( LxWxH)
2.94” x 2.23” x 0.82” (1.4” H with optional relay module)
Sensor Aperture
0.75”
OPERATION
The C-2300 output changes state whenever current above 0.35A is
present. This provides “go/no” status on loads that are not subject to
mechanical failures.
Typical on/off status applications include:
z
Lighting circuits
z
Heater elements
z
Direct drive fans (e.g. exhaust fans)
z
Process motors
DIMENSIONS
200-500
AMPS
500:5A CT
2-5
AMPS
Troubleshooting
Symptom
Causes
Remedy
Sensor output does
not change state
Amperage is below sensor
minimum threshold
Wrap monitored conductor
turns through sensor. See
Tech Tip
Testing with ohm meter
yields incorrect results
Solid state output may show
approx. 1 ohm or less.
Incorrect control wiring
Ensure control loop voltage
is present
2.23
2.50
2.12
O .18
.57
.82
Monitored Load
Sensor
Minimum
Current 0.35A
Sensor
Output
Energized
OFF
RUN
Maximum surrounding air ambient, 60 ° C.
For use in Pollution Degree 2 Environment.