
WIRING EXAMPLES
INSTALLATION INSTRUCTIONS
INSTALLATION
1. Determine mounting location for the sensor near the
conductor to be monitored. The sensor should be located AT
LEAST 1/2” from any uninsulated conductor.
2. Sensor features a flexible iris which allows the sensor to
hang on the conductor if local codes permit. A bracket is
included for screw mounting or attaching to DIN rail. For screw
mounting, drill two 3/32” pilot holes using the bracket as a
template; ensure no drill shavings are present in enclosure.
Attach bracket with screws provided.
3. Clamp sensor around INSULATED CONDUCTOR ONLY,
600VAC MAX to be monitored.
4. Snap the sensor into the mounting bracket.
5. Wire the output of the sensor to a control panel digital
input loop not to exceed 30VAC/DC wetting voltage. Tighten
terminals to 3.5 in-lb.
senvainc.com 1-866-660-8864 (F)1-503-296-2529 9290 SW Nimbus Ave. Beaverton Oregon 97008
C-2300, Go/No
Mini Split-Core
Digital Output
Failure to follow these instructions will result in
death or serious injury.
• Follow ALL requirements in NFPA 70E for safe work practices
and for Personal Protective Equipment (USA) and other appli-
cable local codes when installing this product
• Only qualified electrical personnel should install this product.
• Read, understand, and follow all instructions thoroughly
• Install only on insulated conductors
• Lock out and tag out all power sources prior to installation.
Use properly rated voltage sensing instrument to determine
no voltage is present
Failure to follow these instructions could result in
death or serious injury.
• Equipment monitored/operated by this device may start with-
out warning. Keep clear of apparatus at all times
IMPORTANT WARNINGS
• Only qualified trade installers should install this product
• This product is not intended for life-safety applications
• Do not install in hazardous or classified locations
• The installer is responsible for all applicable codes
• This product must be installed in a suitable electrical enclosure
Automated equipment may
start without warnng
DANGER
WARNING
!
Hazard of electrical shock, explosion,
and arc flash
DANGER
WARNING
!
PRODUCT APPLICATION LIMITATION:
Senva products are not designed for life or safety applications. Senva products
are not intended for use in critical applications such as nuclear facilities, human
implantable device or life support. Senva is not liable, in whole or in part, for any
claims or damages arising from such uses.
V+
DI
CONTROLLER
(SINKING)
(SOURCING)
(AC)
INSULATED PRIMARY
AC CONDUCTOR
600VAC MAX
V+
DI
24VAC
DI
V+
DI
ALTERNATE
CONTROLLER ARRANGEMENTS
DI
DI
VAC
GND
NOTE: Device is NOT polarity sensitive.
v
Status Output
0.5A @ 30VAC/DC
Normally Open
3PZS
Disconnect, lock out and tag out all
power supplies during installation